If there are any steps you do not
complete or if you respond with ‘No’,
please explain in the comments field!
Tick as appropriate or
enter a value/number
Comments/settings
Yes
No
Controller settings
1
Which potable water temperature
was set?
°C
2
Was the circulation activated (see
the circulation section in the con-
troller operating instructions)?
¨
¨
2.1
Which mode was activated?
3
Is the controller LED lit up green?
¨
¨
4
Have additional changes been
made to the controller settings?
¨
¨
If there are any steps you do not
complete or if you respond with ‘No’,
please explain in the comments field!
Tick as appropriate or
enter a value/number
Comments/settings
Yes
No
Final inspection
1
Was the installation checked for
leaks (DIN EN 806)?
¨
¨
2
Was commissioning carried out
in accordance with the operating
instructions?
¨
¨
Instruction/Handover
The installer is responsible for briefing the user on the functions and intended use of the fresh water
station.
¨
The installer is responsible for pointing out the correct operation of potable water installations to the
user.
¨
The installer has provided the user with the necessary documents.
¨
Information on correct operation of potable water systems:
- Stagnation must be avoided; a regular exchange of the potable water must be ensured
- TPWH must be maintained at >= 60 °C at the hot water outlet
- The circulation system must be designed in such a way that the potable water temperature does not fall more
than 5 K below the station outlet temperature of >= 60 °C
- TPWC must be maintained at < 25 °C at the cold water outlet
Installer / Installation company
_____________________________________________________________
Date / Signature / Stamp
User
Handover report received
_____________________________________________________________
Date / Signature