32
– Please protect the components of the cascade
control set against external forces (e.g. impacts,
vibrations etc.).
– External components like handwheels, pressure
test points or actuators must not be misused
for the absorption of external forces, e.g. as
carrying handle or connection point for lever
tools etc.
– Suitable transport and lifting devices are to be
used.
– Check all connections before initial operation
and tighten if necessary.
3.2 Storage
The cascade control set “Regumaq K” and the fresh
water stations must only be stored under the following
conditions:
– Do not store in open air, keep dry and free from dust.
– Do not expose to aggressive fluids or heat sources.
– Protect from direct sunlight and mechanical
agitation.
– Storage temperature: -20 °C up to +60 °C
– Max. relative humidity of air: 95 %
3.3 Packaging material
The packaging material is to be disposed of in an
environmentally friendly manner.
Number OV item no.
Component
Marking
on plug
1
138108X11
Actuator “Master”
Master 24V
X - 1
13810826..
Actuator “Slave”
Bus 24V
X
138108214
Ball valve
X
138108222
Bus connecting cable
Bus 24V
1
138108223
Distribution box
Various
X - 1
138108224
T-distributor
1
138108231
Transformer
24 V/5 V
1
13810843
Flow sensor
VFS
1
138108280
Installation and operating instructions
4 Technical data
4.1 Performance data complete system
Max. operating pressure:
PN 10
Safety valve in the potable water circuit: 10 bar
Max. operating temperature
(heating water – supply):
95˚ C
Min. cold water pressure:
2.5 bar
Possible potable water temperature
(control range):
20-75˚ C
Recommended nominal potable
water temperature:
60˚ C
Recommended circulation temperature: 60˚ C
Min. storage cylinder flow temperature:
Nominal potable water value +8K
Max. flow rate storage cylinder circuit
per fresh water station approximately:
30 l/min.
Max. flow rate potable water circuit
per fresh water station approximately:
30 l/min.
4.2 Performance range for cascading systems
Cascading of 2 stations:
Max. discharge capacity (PWH):
60 l/min
Max. transferable heat output capacity
at dT=50K:
210 kW
Cascading of 3 stations:
Max. discharge capacity (PWH):
90 l/min
Max. transferable heat output capacity
at dT=50K:
315 KW
Cascading of 4 stations:
Max. discharge capacity (PWH):
120 l/min
Max. transferable heat output capacity
at dT=50K
420 KW
Fluid primary side:
Heating water
Fluid secondary side:
Potable water
4.3 Materials
Plate heat exchanger:
Stainless steel 1.4401 brazed
copper
alternatively:
Stainless steel 1.4401
brazed stainless steel
Pipes:
Stainless steel 1.4404/1.4401
Valves and fitting:
Brass/brass resistant to
dezincification
Seals:
EPDM/PTFE
4.4 Connections:
To and from the fresh water stations: G 1 flat sealing
To and from the cascade ball valves: G 1¼ flat sealing
Suitable measures have to be taken to ensure that
the maximum operating pressures and maximum
and minimum operating temperatures are not
exceeded or undercut.
NOTE!
The specifications and performance charts in the
technical data sheets “Fresh water stations
Regumaq X-30/XZ-30” must be observed. A filter with
a mesh size ≤ 140
μ
m which is suitable for potable
water should be installed on the cold water side.
���
NOTICE
DANGER
!
Bus connecting cables are only required for the slave
actuator. Depending on the system design, a bus
connecting cable may be left over or can be used as
extension.
Before installation, the useable cable lengths must be
observed, see system example 4.7!
The actuators of several cascade control sets must
not be interchanged. The master is programmed to
the corresponding number of salves. Each
Master/Slave actuator 2/3/4 must only be used once
within one cascade.
Content cascade control set “Regumaq KX”:
(X = number of fresh water stations)