Suitable measures (e.g. safety valves) have to be
taken to ensure that the maximum operating pres-
sures and maximum and minimum operating tem-
peratures are not exceeded or undercut.

Heavy control unit!
Risk of injury!

Suitable transport and lifting devi-

ces are to be used. Wear suitable protective clot-
hing (e.g. safety shoes) during installation and use
safety devices. External components like hand -
wheels or pressure test points must not be misu-
sed for the absorption of external forces, e.g. as
connection point for lever tools etc.  

Hot and cold surfaces!
Risk of injury! 

Do not touch the control unit without

safety gloves. It may get very hot during operation.

Sharp edges!
Risk of injury! 

Store and install the control unit out

of reach of children.

Small components!
Risk of ingestion! 

Store and install the control unit

out of reach of children.

Allergies!
Health hazard!

Do not touch the control unit and

avoid any contact if allergies against the used ma-
terials are known.

3.2 Storage

The control unit “Regufloor HC” must only be stored
under the following conditions:
– Do not store in open air, keep dry and free from dust.
– Do not expose to aggressive fluids or heat sources.
– Protect  from  direct  sunlight  and  mechanical  agita-

tion.

– Storage temperature: –20°C up to +60°C,  

max. relative humidity of air: 95 %

3.3 Packaging

Packaging material is to be disposed of environmen-
tally friendly.

4 Technical data

4.1 Performance data

Control unit

Max. operating pressure p

s

:

6 bar

Max. differential pressure:

0.75 bar

Max. operating temperature
t

s

primary side:

90˚ C

Max. operating temperature
t

s

secondary side:

50˚ C

k

vs

value:

4

Performance range:

up to 15 kW or a
heating  surface  up  to
200 m

2

with a heat

demand of 75 W/m

2

Pump:
Technical  data  of  the  pump  is  detailed  in  separate
operating instructions. 

Fluid: 

Non-aggressive fluids (e.g. water and suitable

water and glycol mixtures according to VDI 2035). Not
suitable for steam, oily and aggressive fluids.

4.2 Dimensions/Connection sizes

Illustr. 4.1 Dimensions with actuator (optional)

a

p

p

ro

x

1

3

0

2

0

0

G

 1

G

 1

G

 1

G

 1

316

100

134

~145

WARNING

!

DANGER

!

3 Transport, storage and

packaging

3.1 Transport inspection

Upon receipt check delivery for any damages caused
during transit.
Any damage must be reported immediately upon re-
ceipt.

2 Safety notes

2.1 Correct use

Safety  in  operation  is  only  guaranteed  if  the  control
unit is used correctly.
The control unit “Regufloor HC” is used for flow tem-
perature control or surface heating and cooling sys-
tems. 
Any use of the control unit outside the above applica-
tions will be considered as non-compliant and misuse.
Claims  of  any  kind  against  the  manufacturer  and/or
his authorised representatives due to damages caused
by incorrect use cannot be accepted.
The  observance  of  the  installation  and  operating  in-
structions is part of the compliance terms.

2.2 Possible dangers at the installation location 

The case of an external fire has not been taken into
consideration when constructing the control unit.

Depth inside

the cabinet

Summary of Contents for Regufloor HC

Page 1: ...ehen können wenn die Sicherheitsmaßnahmen nicht befolgt werden 1 Allgemeine Hinweise 1 1 Informationen zur Einbau und Betriebsanleitung Diese Einbau und Betriebsanleitung dient dem ge schulten Fachpersonal dazu die Regufloor HC Re gelstation fachgerecht zu installieren und in Betrieb zu nehmen Mitgeltende Unterlagen Anleitungen aller Anlagen komponenten sowie geltende technische Regeln sind einzuh...

Page 2: ...ax Differenzdruck 0 75 bar Max Betriebstemperatur ts Primärseite 90 C Max Betriebstemperatur ts Sekundärseite 50 C kvs Wert 4 Leistungsbereich bis 15 kW bzw bis 200 m2 Heizfläche bei 75 W m2 Wärmebedarf Pumpe Die technischen Daten der Pumpe sind der separaten Einbau und Betriebsanleitung zu entnehmen Medium Nicht aggressive Flüssigkeiten z B Wasser und geeignete Wasser Glykolgemische gemäß VDI 203...

Page 3: ...hen Stellantriebes 24 V 0 10 V aus dem optional erhält lichen Vorlauftemperaturregelset Art Nr 115 20 20 Abb 5 2 zum witterungsgeführten Heizen und Kühlen siehe auch Abschnitt 8 Zubehör Der Stellantrieb er hält dabei seine Signale von einem elektrischen Regler Heizen Kühlen Um eine Einbaulage senkrecht nach unten zu vermeiden wird der Stellantrieb zusammen mit einem Winkeladapter auf das Dreiwegev...

Page 4: ...ndet werden da diese die Dichtungen zer stören können Schmutzpartikel sowie Fett und Ölreste sind ggf aus den Zuleitungen herauszu spülen Bei der Auswahl des Betriebsmediums ist der allgemeine Stand der Technik zu beachten z B VDI 2035 Gegen äußere Gewalt z B Schlag Stoß Vibra tion schützen Nach der Montage sind alle Montagestellen auf Dichtheit zu überprüfen 7 Betrieb 7 1 Entlüftung der Anlage Vo...

Page 5: ...ous injury if the safety guidelines are not obser ved NOTICE indicates a possi ble damage to property which may occur if the safety guidelines are not observed 1 General information 1 1 Information regarding installation and opera ting instructions These installation and operating instructions serve the installer to install the control unit Regufloor HX pro fessionally and to put it into operation...

Page 6: ... 1 Performance data Control unit Max operating pressure ps 6 bar Max differential pressure 0 75 bar Max operating temperature ts primary side 90 C Max operating temperature ts secondary side 50 C kvs value 4 Performance range up to 15 kW or a heating surface up to 200 m2 with a heat demand of 75 W m2 Pump Technical data of the pump is detailed in separate operating instructions Fluid Non aggressiv...

Page 7: ... the help of the electromotive actuator 24 V 0 10 v which is part of the optional flow temperature regulating set item no 115 20 20 illustr 5 2 for weather guided heating and cooling see paragraph 8 Accessories The actuator receives its signals from an electric controller heating cooling To avoid a vertical downward installation the actuator is mounted onto the three way valve with an angle pat te...

Page 8: ...rt particles and lubricant or oil re sidues must be removed from the pipework by flushing the latter When choosing the operating fluid the latest technical development has to be considered e g VDI 2035 Please protect against external forces e g im pacts vibrations etc After installation check all installation points for le aks 7 Operation 7 1 Bleeding the system Before initial operation the system...

Page 9: ...iels qui peuvent résulter de la non obser vation des consignes de sécurité 1 Généralités 1 1 Informations sur la notice d installation et d utilisation Cette notice d installation et d utilisation a pour but d aider le professionnel à installer et mettre en service l ensemble de réglage Regufloor HC dans le respect des règles techniques d usage Les autres documents de référence Les notices de tous...

Page 10: ... côté primaire 90 C Température de service max ts côté secondaire 50 C Valeur kvs 4 Plage de puissance jusqu à 15 kW ou 200m de surface chauffante pour un besoin calori que de 75 W m Circulateur Les données techniques du circulateur figurent dans la notice d installation et d utilisation jointe avec le produit Fluides compatibles Fluides non agressifs par ex eau et mélanges eau glycol adéquats sel...

Page 11: ...éf 115 20 20 fig 5 2 pour le chauffage et le rafraîchissement voir chapitre 8 Accessoires ajuste la position du clapet du robinet à trois voies en fonction de la température extérieure Le moteur reçoit des sig naux d un régulateur électrique chauffage rafraîchis sement Afin d éviter une installation verticale vers le bas le montage du moteur sur le robinet à trois voies se fait à l aide d un adapt...

Page 12: ...ent endommager les joints du robinet Si nécessaire des impuretés ou résidus de graisse ou d huile doivent être en levés de la tuyauterie par rinçage Choix du fluide de service selon la technologie actuelle par ex VDI 2035 Protéger des nuisances extérieures chocs se cousses vibrations etc Après le montage contrôler l étanchéité de tous les points de montage 7 Service 7 1 Purge de l installation L i...

Page 13: ...ono rispettate ATTENZIONE indica possi bili danni materiali che possono insorgere se le misure di sicurezza non vengono rispettate 1 Note generali 1 1 Informazioni sulle istruzioni di montaggio e di funzionamento Queste istruzioni di montaggio e di funzionamento servono al personale tecnico addestrato per installare e mettere in funzione il gruppo di regolazione Regu floor HC in modo professionale...

Page 14: ...ferenziale 0 75 bar Max temperatura di esercizio ts lato secondario 90 C Max temperatura di esercizio ts lato secondario 50 C Valore kvs 4 Campo di applicazione fino a 15 kW ossia fino a 200m superficie radiante con 75 W m di fabbisogno calorico Pompa I dati tecnici della pompa si desumono dalle istruzioni di montaggio e di funzionamento allegate separata mente Mezzo π Fluidi non aggressivi ad es ...

Page 15: ...troter mico 24 V 0 10V contenuto nel set di regolazione della temperatura di mandata Codice 115 20 20 Fig 5 2 per il riscaldamento e il raffrescamento in funzione delle condizioni meteorologiche si veda anche il pa ragrafo 8 Accessori Il servomotore riceve i segnali da un centralina climatica riscaldamento raffresca mento Per evitare una posizione di montaggio verti cale verso il basso il servomot...

Page 16: ...acquo le eventuali particelle di sporco o residui di grasso e olio dalle tubazioni Nella scelta del fluido è necessario attenersi allo stato della tecnica ad es VDI 2035 Proteggere da eventi violenti esterni ad esempio colpi urti vibrazioni Dopo il montaggio verificare la tenuta di tutti i rac cordi 7 Funzionamento 7 1 Sfiato dell impianto Prima della messa in funzione l impianto deve essere riemp...

Reviews: