D-582-3-E
2
Parameter
Setup Range or Item to be Selected
Units of Measure
Metered fluids
Select one from
・
Gas and steam
・
Liquid
Calculation
Select one from
・
Calculation on actual flow
・
Calculation corrected for temperature
and pressure
・
Saturated steam calculation
・
Superheated steam calculation
Reference temperature
for correction
・
With "Calculation on actual flow" or "Calculation corrected
for temperature and pressure at "Calculation,"
-250
≦
"Reference temperature for correction"
≦
50[
℃
]
・
With "Saturated steam calculation" or "Superheated steam
calculation" at "Calculation,"
00
≦
"Reference temperature for correction
≦
50[
℃
]
NOTE: By the "Temperature units" setup, convert the
temperature range above.
by "Temperature units"
Reference temp.
for measurement
(process temp.)
Same as "Reference temperature for correction".
by "Temperature units"
Reference pressure
for correction
-0.008
≦
"Reference pressure for correction"
≦
0.8[MPa]
NOTE: Relative to the pressure unit setup, convert the
pressure range above.
by "Pressure units"
Reference pressure
for measurement
(process pressure)
Same as "Reference pressure for correction".
by "Pressure units"
Fixed conversion
value
0.000
≦
"Fixed conversion value"
≦
When the mass flowrate units are selected with "Calculation
on actual flow" or "Calculation corrected for temperature and
pressure" at "Calculation", set the density (fixed value).
Deviation factor is set up, in practice, by setting[/deviation
factor].
Calculation on actual
flow in kg/m
3
[normal];
"Calculation corrected
for temperature and
pressure" in kg/m
3
[normal]
Zero flowrate
Always set to 0.
by "Instantaneous
flowrate units"
Span flowrate
(Full scale flowrate)
Min. flowrate
×
3
≦
"Span flowrater"
≦
Max. flowrate
×
.5
(See "General Specifications" for the max. and min. flowrates.)
by "Instantaneous
flowrate units"
Low cutoff flowrate
Set up such that 0<"Low cutoff flowrate <"Span flowrate"
or "High alarm flowrate".
by "Instantaneous
flowrate units"
High alarm flowrate
"High alarm flowrate" > 0
where "High alarm flowrate" > "Low cutoff flowrate"
by "Instantaneous
flowrate units"
Weight of totalized flow
and factored pulse output
0.0
≦
"Pulse weight"
≦
0000
(See "General Specifications".)
by "Totalized flow and
factored pulse units"
Pulse width
(factored pulse)
0
≦
"Pulse width"
≦
000
where pulse width duty at full scale must be below 50%.
Default setting: 50
ms
Pulse output type
Select one from
・
Factored
・
Unfactored
Damping (analog,
instantaneous rate)
0
≦
"Damping"
≦
00
Default setting: 2.5
s
※
"Sensor type (flowmeter type)" is represented by the following:
V
※
※
□
□
□
□
□ (
8-digit code
)
Output
・
Analog type: A
・
Pulse type: P
Fluid
・
Gas, steam: G
・
Liquid: L
Sensor nominal dia. is set in 3 digits.
Example: If sensor nominal dia. is 500mm, set to 050.
The first to 3 digits in the sensor model code is set.
Examples: VXS