15
Outdoor Lifestyles by Hearth & Home Technologies • Palazzo Installation Manual • 4082-311 Rev. A • 06/08/15
WARNING! Risk of Shock or Explosion! DO NOT wire
110-120 VAC to the valve or to the appliance wall switch.
Incorrect wiring will damage controls.
NOTICE: This appliance must be electrically wired
and grounded in accordance with local codes or, in the
absence of local codes, with
National Electric Code
ANSI/NFPA 70-latest edition
or the
Canadian Electric
Code CSA C22.1.
Total Electrial Requirements: 110-120Vac, 60Hz., less
than 12 Amperes
• Wire the appliance junction box to unswitched 110-
120 VAC. This is required for proper operation of the
appliance.
• A 110-120 VAC circuit for this appliance must be
protected with ground-fault circuit-interrupter protection
in compliance with the applicable electrical codes.
• Low voltage and 110-120 VAC voltage cannot be shared
within the same wall box.
5
Electrical Information
Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to dis-
connection when servicing controls. Wiring errors could
cause improper and dangerous operation. Verify proper
operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with
type 105º C rated wire. Wire must have high temperature
insulation.
Note:
The Palazzo appliance
MUST
be connected to
a GFCI (Ground Fault Circuit Interrupt) protected circuit
breaker.
A. wiring Requirements
B. IntelliFire Pilot Ignition System wiring
• Wire the appliance junction box to 110-120 VAC for
proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
IPI controlled appliance junction box to a switched circuit.
Incorrect wiring will override IPI safety lockout.
ThIS APPLIANCE SUPPLIED STANDARD WITh:
• IntelliFire control valve (3V)
• Wall Switch Control - Operates Unit On/Off, Power
Screen Up/Down and LED lights.
• 2 RGB LED outdoor rated light strips (12V)
• Linear actuator, for power screen (120V/5A).
• 12 conductor wall switch wire
C. Installing the Electrical
Note:
The Palazzo is supplied with two rubber grommets
installed on the left side of the appliance for gas and
electrical connections. See Figure 3.1 & 3.2. A cover
plate is also provided on the right side of the appliance
in the event that gas and electrical must be run from
the right. If it is determined that gas and electrical are
to be run through the right side of the appliance, the
grommets and cover plates must be repositioned. See
Figure 5.1
Figure 5.1 Cover Plate
Figure 5.2 Junction Box
• Remove Lower Access Panel by lifting up on the panel
to disengage from hook and pull panel away from unit.
Set aside.
• Remove screws securing Junction Box & Mounting
Bracket as shown in Figure 5.2.
• Unplug transformer and power supply.
Valve
Control Box
Gas & Electric
Pass Throughs
Manual
Shutoff Valve
Junction Box
Cover Plate
Screws
Cover
Plate
Junction Box
Valve Cover
Box