(with insulation)
COMPARATIVE WIRE SIZES
The following chart contains information on wire sizes, the DC resistance of the wires and the
corresponding diameters and areas of these wires. This information can be used to calculate the
voltage drop of the wires or to find an equivalent wire size.
SIZE
DC
CROSS-SECTIONAL AREA
APPROXIMATE DIAMETER
(AWG)
Resistance in Ohms
(1000 feet)
INCHES
MILLIMETERS
INCHES
MILLIMETERS
14
3.14
0.0032
2.08
.078
1.98
12
1.98
0.0051
3.31
.101
2.57
10
1.24
0.0082
5.26
.126
3.20
8
0.78
0.0130
8.37
.162
4.11
6
0.50
0.0206
13.30
.215
5.46
4
0.31
0.0328
21.15
.269
6.83
2
0.19
0.0521
33.62
.337
8.56
1
0.15
0.0657
42.41
.376
9.55
1/0
0.12
0.0829
53.50
.423
10.74
2/0
0.10
0.1045
67.43
.508
12.90
3/0
0.08
0.1318
85.01
.576
14.63
4/0
0.06
0.1662
107.20
.645
16.38
Size #14 #12 #10 #8 #6 #4 #3 #2 #1 1/0
Diameter 0.073 0.080 0.115 0.146 0.184 0.235 0.281 0.295 0.335 0.380
(inches)
Size 2/0 3/0 4/0 250 MCM 300 MCM 350 MCM 400 MCM 500 MCM
Diameter 0.420 0.475 0.530 0.580 0.635 0.690 0.730 0.820
(inches)
AWG Wire Sizes
Note:
These sizes represent the conductor only without any insulation.
Note:
These illustrations may not be to scale and are for example purposes only.
Summary of Contents for GTFX2012E
Page 1: ...International Series GTFX and GVFX Grid Interactive Inverter Charger Installation Manual ...
Page 22: ...20 notes ...
Page 31: ...29 Parallel Quad System ...
Page 33: ...31 Three Phase System ...
Page 34: ...32 this PAGE INTENTIONALLY LEFT BLANK ...
Page 52: ...50 this PAGE INTENTIONALLY LEFT BLANK ...
Page 54: ...52 this PAGE INTENTIONALLY LEFT BLANK ...