21
AC WIRING NOTES
AC HOT OUT
• AC hot output conductor (brown) wire
gauge must be sized to the breakers and
loads
.
AC NEUTRAL OUT/AC NEUTRAL IN
• Both neutral terminals are common with
each other within the FX.
• Only one neutral needs to connect at the
terminal if a separate common neutral bus
bar is installed.
CHASSIS GROUND
• Both CHASSIS GROUND terminals are
common within the FX.
• The AC input and AC output ground
wires can connect to these terminals, or
one ground wire can be connected if a
common ground bus bar is installed.
AC HOT IN
• The AC hot input conductor (brown) must
be supplied through an appropriately-
sized AC branch rated circuit breaker.
• 10.0 mm
2
(8 AWG) or larger wire is
recommended to accommodate the FX’s
AC transfer relay.
13.3 mm
2
(6 AWG) is the largest size of wire
that can be used with the input or output
terminals.
����������
��������������
�����������������
�����������������
�������������
���������
�
�
��
��
�
��
��
�
�
��
�
��
�
��
�
��
�
��
��
�
�
�
��
�
��
�
�
�
������������
��������
��
�
��
��
�
��
�
��
��
��
�
��
��
�
�
�
��
��
�
�
�
�
�
�
�
�
�
�
��
�
�
��