Installation
40
900-0033-01-00 Rev A
De-energize/Shutdown
WARNING: Lethal Voltage
Review the system configuration to identify all possible sources of energy.
Ensure ALL sources of power are disconnected before performing any
installation or maintenance on this equipment. Confirm that the terminals are
de-energized using a validated voltmeter (rated for a minimum 1000 Vac and
1000 Vdc) to verify the de-energized condition.
WARNING: Burn Hazard
Internal parts can become hot during operation. Do not remove the cover
during operation or touch any internal parts. Be sure to allow them sufficient
time to cool down before attempting to perform any maintenance.
1.
Open the PV Breakers.
1
2.
Open the AC Breakers.
2
3.
Open the DC Breaker for the Battery.
3
4.
Using a digital volt-meter, verify 0 Vdc on the Battery terminals
(i.e., Place voltmeter leads on
4+
and
4–
in Figure 29).
5.
Using a digital volt-meter, verify 0 Vdc on the PV terminal
(i.e., Place voltmeter leads on
and
in Figure 29).
6.
Using a digital volt-meter, verify 0 Vac on the AC Breakers
(i.e., Place voltmeter leads on
6+
and
6–
in Figure 29).
Figure 29
Shutdown Procedures
5–
3
1
2
6+
6–
4–
5+
4+
Summary of Contents for SmartRE 2500
Page 1: ...Installation Manual...
Page 19: ...Planning 900 0033 01 00 Rev A 17 Dimensions Figure 6 Enclosure Dimensions...
Page 28: ...Installation 26 900 0033 01 00 Rev A Figure 14 Correct Placement for Vertical Installations...
Page 54: ......
Page 56: ...Wiring Configurations 54 900 0033 01 00 Rev A This page intentionally left blank...
Page 64: ...Wiring Configurations 62 900 0033 01 00 Rev A This page intentionally left blank...