Setup and Programming
900-0213-01-00 REV B
Do not copy or distribute without permission.
!
Inverter Status LED Indicators
Green
Yellow
Red
Inverter on (solid) or standing by (flash)
AC source in use (solid) or standing by (flash)
Inverter error or warning (see manual)
Green
Yellow
Red
12.5 Vdc or higher
11.5 to 12.4 Vdc
11.4 Vdc or lower
Color
Battery Status LED Indicators
25.0 Vdc or higher
23.0 to 24.8 Vdc
22.8 Vdc or lower
50.0 Vdc or higher
46.0 to 49.6 Vdc
45.6 Vdc or lower
12 V Inverter
24 V Inverter
48 V Inverter
Monitoring
A
B
Profile Wizard
In the MATE3s system display, the
Profile Wizard
allows quick setup of parameters that apply to all systems. The
Profile Wizard
is
reached from the
Main Menu
as shown in
B
.
The Profile Wizard is useful for rapid setup of multiple parameters including date, time, battery charging, AC source size and limits, and
System Type. It can also configure functions such as High Battery Transfer and Grid Use times. Note that these two functions are not
available if the System Type is set to
Off Grid
.
NOTE
: The Wizard does not configure the entire system. It does not select AC input modes for the FXR inverter, parameters for
automatic generators, or “fully charged” parameters if the FLEXnet DC battery monitor is in use. If settings are made in the wrong order,
the Wizard can overwrite some customized settings. See MATE3s
Programming Guide
for more information.
The firmware revision of all devices can be confirmed by navigating from the
Main Menu
as shown in
A
. Upgrades to the firmware
revision can be downloaded from the OutBack Power website.
Profile Wizard
New Profile Initialized
Back
Continue
Wizard Date & Time
16:56
13 May 2022 Fri
Back
Continue
Wizard System Type
System Type Grid Tied
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah
Back
Continue
Grid Tied
Main Menu
Settings
>>
Profile Wizard
>>
Device Data Logs
>>
Event Logs
>>
Firmware Update
>>
Profile Wizard
Profile Wizard
New Profile
>>
Existing Profile
>>
Restore Profile
>>
New Profile
System Configuration
System Information >>
Save / Store Configuration >>
Firmware Version >>
Date and Time
>>
LCD Display
>>
Firmware Version
Firmware Versions
MATE3s
001.001.000
1:VFXR3648A
001.006.063
2:VFXR3648A
001.006.063
Main Menu
Settings
>>
Profile Wizard
>>
Device Data Logs
>>
Event Logs
>>
Firmware Update
>>
Profile Wizard
Settings Menu
System
>>
Inverter
>>
Charge Controller
>>
Battery Monitor
>>
MATE3s
>>
System
A
Wizard AC Configuration
AC Output Voltage 120 VAC
AC Phase Single
AC Input Breaker Size 60 A
Maximum Output Load 33 A
Back
Continue
120
Wizard AC Input Limits
Grid Lower Voltage Limit 105 VAC
Grid Upper Voltage Limit 132 VAC
Gen Lower Voltage Limit 108 VAC
Gen Upper Voltage Limit 140 VAC
Back
Continue
105
Wizard Generator Configuration
Generator Installed N
Generator Type
AC Size 5.0 kW
Generator Start
Manual
AUX Output Device Port 1
Back
Continue
N
Wizard Battery Charging
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back
Continue
The FLEXnet DC (FN-DC) is a battery monitor which
measures DC current flow on one or more shunts.
It provides battery state-of-charge (SoC) information.
Exact measurements and programming are performed with
the system display. (See the system display and FLEXnet
DC literature.) The LED indicators shown below provide
approximate measurements of the battery state of charge.
FLEXnet DC Battery Monitor
o
A green indicator (
F
ULL
) means the batteries have an adequate charge. It does
not always mean they are full.
o
A yellow indicator (
OK
) means the batteries are somewhat discharged.
o
A red indicator (
L
OW
) means the batteries are greatly discharged and may require
attention. A low battery error may be accompanied by a red
S
TATUS
indicator.
The
S
TATUS
indicators show the inverter’s operating condition as shown below.
Green
Color
Red
Yellow
Yellow
Yellow
≥
80%
≥
70%
≥
60%
≥
60% off, < 60% solid, < 50% blinks
Battery State of Charge
FN-DC LED Indicators
> 90% (blinks if charge parameters are met)
After commissioning and programming the FXR system, perform a full battery charge.
Reset the FN-DC by unplugging the communications cable and then plugging it back
in. (The system must be energized at the time.) The FN-DC will reset to 100% SoC,
matching the batteries if they have been charged.
NOTE
: The user must program the FN-DC with correct values for battery capacity
and charging requirements. The factory default values may not be correct. If not
programmed accurately, the FN-DC readings and LED indicators will not be accurate.
The same is true if the shunt(s) are not wired correctly. See the
FLEXnet DC
Overview Guide
for more information.
LED Indicators
The inverter has two sets of LED indicators. (See Sheet 2 for locations.)
The
B
ATTERY
indicators show the approximate battery state.
NOTE
: Due to different system states, battery voltage does not always indicate an
accurate state of charge. The FN-DC is more accurate.
See the inverter
Operator’s Manual
for full descriptions of these LED indicators.
A
This advances the display to the
Setup
Complete
screen.
B
If the FLEXnet DC is installed, the
display advances to the
Shunt
screens.
If the FLEXnet DC is not installed, see
.
C
If the
System Type
is
Grid Tied
or
Backup
, the
display advances to the
Grid Use Schedule
screens. If the System Type is
Off Grid
, see .
B
C
CAUTION: Equipment Damage
These procedures should be done by a qualified installer who is trained on programming inverter power systems. Failure to set accurate
parameters for the system could potentially cause equipment damage. Damage caused by inaccurate programming is not covered by the
limited warranty for the system.
IMPORTANT
Ensure all settings are correct for the system. The Profile Wizard can be used for rapid setup. For Grid Support functions it may be
necessary to load a .GIP file. This document assumes the use of the MATE3s System Display.
Verify the firmware revision of all OutBack Power devices before use. The FXR inverter and system display may not communicate or
operate correctly unless their firmware is above a specified revision number. Radian inverters with firmware revision 001.006.061 or
higher must use the MATE3s system display.
For firmware and .GIP file installation, see the
Installation Manual
. For settings and functions, see the
Operator’s Manual
.
If FN-DC
is installed...
If
System Type
is
Grid Tied
or
Backup
...
B
C
A
Wizard Grid Use Schedule
Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back
Continue
N
Wizard Grid Use Schedule
Period 2 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back
Continue
N
Wizard High Battery Transfer
Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%
Back
Continue
Disabled
Wizard Grid Use Schedule
Period 3 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back
Continue
N
Wizard Battery Monitor
Shunt A
Connection Inverter
Back
Continue
A
Wizard Battery Monitor
Shunt A
Connection Inverter
Back
Continue
B
Wizard Battery Monitor
Shunt A
Connection Inverter
Back
Continue
C
Profile Wizard
Setup Complete
Exit Program Save
4
5
2
3
1