2

Setup and Programming

900-0213-01-00 REV B

Do not copy or distribute without permission.

!

Inverter Status LED Indicators

Green

Yellow

Red

Inverter on (solid) or standing by (flash)

AC source in use (solid) or standing by (flash)

Inverter error or warning (see manual)

Green

Yellow

Red

12.5 Vdc or higher 

11.5 to 12.4 Vdc 

11.4 Vdc or lower 

Color

Battery Status LED Indicators

25.0 Vdc or higher 

23.0 to 24.8 Vdc 

22.8 Vdc or lower 

50.0 Vdc or higher 

46.0 to 49.6 Vdc 

45.6 Vdc or lower 

12 V Inverter

24 V Inverter

48 V Inverter

Monitoring

A

B

Profile Wizard

In the MATE3s system display, the 

Profile Wizard

 allows quick setup of parameters that apply to all systems.  The 

Profile Wizard

 is 

reached from the 

Main Menu

 as shown in     

B

  .

The Profile Wizard is useful for rapid setup of multiple parameters including date, time, battery charging, AC source size and limits, and 

System Type.  It can also configure functions such as High Battery Transfer and Grid Use times.  Note that these two functions are not 

available if the System Type is set to 

Off Grid

.

NOTE

:  The Wizard does not configure the entire system.  It does not select AC input modes for the FXR inverter, parameters for 

automatic generators, or “fully charged” parameters if the FLEXnet DC battery monitor is in use.  If settings are made in the wrong order, 

the Wizard can overwrite some customized settings.  See MATE3s 

Programming Guide

 for more information.   

3

The firmware revision of all devices can be confirmed by navigating from the 

Main Menu 

as shown in     

A

  .  Upgrades to the firmware

 

revision can be downloaded from the OutBack Power website.

 

4

Profile Wizard

New Profile Initialized

 Back

Continue

Wizard Date & Time

16:56 

 13  May  2022   Fri

Back    

Continue

Wizard System Type

System Type    Grid Tied  
System Voltage 48 VDC
Array Wattage  1000
Battery Type   FLA   Capacity 500 Ah   

Back

Continue

Grid Tied

Main Menu

Settings 

 >>

Profile Wizard  

 >>

Device Data Logs   

 >> 

Event Logs  

  >> 

Firmware Update 

 >> 

Profile Wizard

Profile Wizard

New Profile 

 >>

Existing Profile   

 >>

Restore Profile 

 >> 

New Profile 

System Configuration

System Information         >>
Save / Store Configuration >>
Firmware Version           >> 
Date and Time   

 >> 

LCD Display

  >> 

Firmware Version

Firmware Versions

MATE3s

001.001.000

1:VFXR3648A

001.006.063

2:VFXR3648A

001.006.063

Main Menu

Settings 

 >>

Profile Wizard  

 >>

Device Data Logs   

 >> 

Event Logs  

  >> 

Firmware Update 

  >> 

Profile Wizard

Settings Menu

System   

 >>

Inverter 

 >>

Charge Controller  

 >> 

Battery Monitor 

 >> 

MATE3s 

  >> 

System

A

Wizard AC Configuration

AC Output Voltage 120 VAC    
AC Phase          Single
AC Input Breaker Size 60 A
Maximum Output Load   33 A

 

  Back    

Continue

120

Wizard AC Input Limits

Grid Lower Voltage Limit  105  VAC
Grid Upper Voltage Limit  132  VAC
Gen  Lower Voltage Limit  108  VAC

Gen  Upper Voltage Limit  140  VAC

  Back    

Continue

105

Wizard Generator Configuration

Generator Installed  N
Generator Type  

  AC Size  5.0 kW

Generator Start 

  Manual

AUX Output Device Port 1

  Back    

Continue

N

Wizard Battery Charging

Absorb Voltage   57.6 VDC  Time  1.0
Float Voltage    54.4 VDC  Time  1.0
Equalize Voltage 60.0 VDC  Time  3.0
Re-Float Voltage 44.0 VDC

  Back

Continue   

The FLEXnet DC (FN-DC) is a battery monitor which 

measures DC current flow on one or more shunts. 

It provides battery state-of-charge (SoC) information. 
Exact measurements and programming are performed with 

the system display.  (See the system display and FLEXnet 

DC literature.)  The LED indicators shown below provide 

approximate measurements of the battery state of charge.

FLEXnet DC Battery Monitor

o

A green indicator (

F

ULL

) means the batteries have an adequate charge.  It does

not always mean they are full.

o

A yellow indicator (

OK

) means the batteries are somewhat discharged.

o

A red indicator (

L

OW

) means the batteries are greatly discharged and may require

attention.  A low battery error may be accompanied by a red 

S

TATUS

 

indicator.

The 

S

TATUS

 

indicators show the inverter’s operating condition as shown below.

Green

Color

Red

Yellow

Yellow

Yellow

 80%

 70% 

 60% 

 60% off, < 60% solid, < 50% blinks

Battery State of Charge

FN-DC LED Indicators

> 90% (blinks if charge parameters are met)

After commissioning and programming the FXR system, perform a full battery charge.  

Reset the FN-DC by unplugging the communications cable and then plugging it back 

in.  (The system must be energized at the time.)  The FN-DC will reset to 100% SoC, 

matching the batteries if they have been charged.

NOTE

:  The user must program the FN-DC with correct values for battery capacity 

and charging requirements.  The factory default values may not be correct.  If not 

programmed accurately, the FN-DC readings and LED indicators will not be accurate. 

The same is true if the shunt(s) are not wired correctly.  See the

 FLEXnet DC 

Overview Guide

 for more information.

 

5

LED Indicators

The inverter has two sets of LED indicators.  (See Sheet 2 for locations.)  
The 

B

ATTERY

 indicators show the approximate battery state.  

NOTE

:  Due to different system states, battery voltage does not always indicate an 

accurate state of charge.  The FN-DC is more accurate.

See the inverter 

Operator’s Manual 

for full descriptions of these LED indicators.

A

This advances the display to the 

Setup 

Complete 

screen. 

B

If the FLEXnet DC is installed, the

display advances to the 

Shunt 

screens.  

If the FLEXnet DC is not installed, see   

   

C

If the 

System Type 

is 

Grid Tied

 or 

Backup

, the 

display advances to the 

Grid Use Schedule

 

screens.  If the System Type is 

Off Grid

, see      .

B

C

CAUTION:  Equipment Damage

These procedures should be done by a qualified installer who is trained on programming inverter power systems.  Failure to set accurate 

parameters for the system could potentially cause equipment damage.  Damage caused by inaccurate programming is not covered by the 

limited warranty for the system.

IMPORTANT



Ensure all settings are correct for the system.  The Profile Wizard can be used for rapid setup.  For Grid Support functions it may be

necessary to load a .GIP file.  This document assumes the use of the MATE3s System Display. 



Verify the firmware revision of all OutBack Power devices before use.  The FXR inverter and system display may not communicate or

operate correctly unless their firmware is above a specified revision number.  Radian inverters with firmware revision 001.006.061 or 

higher must use the MATE3s system display.

 

 

For firmware and .GIP file installation, see the 

Installation Manual

.            For settings and functions, see the 

Operator’s Manual

.

If FN-DC 

is installed...

If

 System Type

 

is 

Grid Tied 

or 

Backup

...

B

C

A

Wizard Grid Use Schedule

  Period 1 Enable  N

 Weekday Use  0:00  Drop 0:00
 Weekend Use  0:00  Drop 0:00 

Back    

Continue

N

Wizard Grid Use Schedule

  Period 2 Enable  N

 Weekday Use  0:00  Drop 0:00
 Weekend Use  0:00  Drop 0:00 

Back    

Continue

N

Wizard High Battery Transfer

Mode Disabled
Grid Connect    48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%  

Back    

Continue

Disabled

Wizard Grid Use Schedule

  Period 3 Enable  N

 Weekday Use  0:00  Drop 0:00
 Weekend Use  0:00  Drop 0:00 

Back    

Continue

N

Wizard Battery Monitor

    Shunt  A
    Connection  Inverter

  Back

Continue   

A

Wizard Battery Monitor

    Shunt  A
    Connection  Inverter

  Back

Continue   

B

Wizard Battery Monitor

    Shunt  A
    Connection  Inverter

  Back

Continue   

C

Profile Wizard

Setup Complete

Exit  Program    Save  

4

5

2

3

1

2

1