OutBack Power FXR Series Quick Start Manual Download Page 3

IMPORTANT



This product requires batteries for operation.

The required nominal voltage is either 12, 24, or 

48 Vdc, depending on model.



The default inverter/charger settings assume a

deep-cycle stationary lead-acid battery, such as 

OutBack Power’s EnergyCell RE or NC series 

batteries.  Ensure the settings are appropriate 

for the specific batteries used in the system.



Protection for the battery circuit external

to this product must be provided by the installer.



Protection for the AC circuit external to this

product must be provided by the installer.

   

For more information, see the FXR 

Installation

Manual

.

Wiring Data

Ground Lug

1

AC Neutral 

Terminals

2

3

4

Battery Positive Stud

Battery Negative Stud

5

AC Hot Out Terminal

6

Ground Terminals

Inverter On/Off Jumper

7

8

AC Hot In Terminal

9

10

Inverter On/Off Terminals
Auxiliary Terminals

11

12

13

14

Temperature Sensor Port
Communication Port
Battery LED Indicators
Status LED Indicators

900-0213-01-00 REV B

Do not copy or distribute without permission.

DC Wiring Notes

o

Battery cables should be no longer than 10 feet (3 m) each to minimize voltage loss and other possible effects.

o

Turn off DC circuit breakers before proceeding.

o

Tie, tape, or twist cables together to reduce self-inductance.  Run positive and negative cables through the same

knockouts and conduit.

o

Each inverter battery terminal is a threaded stud which accepts a ring terminal lug.  Use crimped and sealed copper ring

lugs with 

5

/

16

 inch (0.79 cm) holes, or use compression lugs.

o

Install overcurrent devices according to applicable codes.

o

The DC terminals must be installed in an enclosure to meet the requirements of some local or national codes.

AC Wiring Notes

o

Recommended conductor size is #6 AWG (16 mm

2

) or 0.021 in

2

.

o

Inverter output varies with model.  Size the loads accordingly.

o

The transfer relay is rated 60 Aac; AC input and output may need to be protected with branch-rated circuit breakers of

maximum 60 Aac size to meet applicable code requirements.

o

The neutral terminals are common.  Typically only one is used.

o

Only one AC source can be wired at a time.  Use an external selector switch if more than one source is available.

Generator Notes



A generator should be sized to provide enough power for maximum loads and charging at the same time.



Minimum generator size is recommended to be twice the power of the inverter(s) due to overload and/or
balancing issues.

1

2

3

4

5

5

6

7

8

9

10

11

12

13

14

6

Inverter 

(Wattage/Voltage)

Nominal 

DC Amps

(Derated 125%)

Conductor Size

(Minimum)

Breaker 

Size

(Minimum)

FXR2012A

VFXR2812A

FXR2524A

VFXR3524A

FXR3048A

VFXR3648A

Terminal Location

Inverter DC Terminals
Battery Terminals

200

4/0 AWG (120 mm

2

) or 0.186 in

2

250 Adc

280

4/0 AWG (120 mm

2

) or 0.186 in

2

250 Adc

125

2/0 AWG (70 mm

2

) or 0.109 in

2

175 Adc

175

4/0 AWG (120 mm

2

) or 0.186 in

2

250 Adc

75

1/0 AWG (70 mm

2

) or 0.109 in

2

125 Adc

90

1/0 AWG (70 mm

2

) or 0.109 in

2

125 Adc

Torque Requirements

60 in-lb (6.9 Nm)
See battery manufacturer’s recommendations

CAUTION:  

Equipment Damage 

When connecting battery cables to the 

inverter, observe the proper polarity.  

Incorrect connection can damage or 

destroy the equipment and void the 

product warranty.

!

M8 x 1.25 Stud  

Insulator

Mounting 

Surface

Battery 

Terminal Post

Lock Washer

Battery Cable Connections 

13 mm Nut

Battery 

Cable 

Lug

   CAUTION: Fire Hazard

Do not stack battery terminal hardware 

in any other order than shown here.  

Stacking terminal hardware in any other 

order can overheat the terminals.  

Other devices may be installed on 

the same inverter studs above the 

hardware shown here.

!

Grounding Notes

o

This product meets the IEC requirements of Protection Class I.

o

This product must be connected to a permanent wiring system that is grounded according to the IEC 60364 TN standard.

o

The input and output circuits are isolated from ground.  The installer is responsible for system grounding according to all

applicable codes.

o

The central AC ground terminals are common.  Typically only one is used.

WARNING:  Shock Hazard



For safety, the neutral and ground conductors should be mechanically bonded.  OutBack Power

does not bond these conductors within the inverter.  Some codes require the bond to be made at the 

main panel only.  Make sure that no more than one bond is present in the AC system at any time.  



For all installations, the negative battery conductor should be bonded to the grounding system at

only one point.  If the OutBack Power GFDI is present, it can provide the bond.

Terminal Location

Minimum Conductor Size

Torque Requirements

Central AC Terminals

DC Box Lug

#10 AWG (0.009 in²) or 6 mm²

25 in-lb (2.8 Nm)

#6 AWG* (0.025 in²) or 16 mm²

45 in-lb (5.1 Nm)

*Accepts up to 1/0 AWG (70 mm² or 0.109 in²) wire.  The DC Cover or Turbo Fan must be removed before making the ground connection.

Flat Washer

1

1