Dimensions  

width 105 mm, height 110 mm, depth 70 mm 

DIN rail-mounted module casing, 6 modules.

Weight

0.28 kg

Protection class 

IP 20

Operating temperature

0 ºC…+50 ºC

Storing temperature 

-20 ºC…+70 ºC

Power supply

   Operating voltage

24 VAC-33VAC (50-60 Hz) or 20 – 48VDC

   Power requirement  24VAC

9VA   With the optional accessories (M-LINK/GSM and external display) 12VA

   Power requirement  24VDC

4W  With the optional accessories (M-LINK/GSM and external display)  6.5W

Measurement inputs:

15 pcs, programmable

passive sensors  (Inputs M1...M15)

- NTC10:  

 

Measurement channel accuracy in the measuring range -50 ... 130 ° C: 

Measurement channels 1-3 +0.1 ºC 

Measurement channels  4-15  +0.1 ºC  between -20 ºC…+120 ºC,    

+0.3 ºC  between -50 ºC…-20  and  +0.2 ºC b120 ...130 ºC

- NTC-20: Measurement channels  1-3  +0.1 ºC  

Measurement channels  4-15  +0.1 ºC  between 0 ºC…-120 ºC,   

+0.7 ºC between -50 ºC…0 ºC and   +0.2 ºC between  +120 ºC…+130 ºC

-NTC 1.8 and NTC 2.2: +0.2 ºC between -50ºC…+100 ºC,   +0.5 ºC b100 ºC…+130 ºC 

-Ni1000LG/DIN: +0,3 ºC between   -50 ºC…+130 ºC

-Pt1000: +0,3 ºC between -50 ºC…+130 ºC 

Also sensor tolerances and the effect of cables must be considered when calculating 

total accuracy.

Digital inputs   (Inputs M1...M15)

Contact voltage 5 Vdc, Switching current 0.5 mA  

Transfer resistance max. 1,9 Ω (closed), min. 11 k Ω (open). 

Active sensors (Inputs M4...M15)

Voltage measurement 0-10 V, meas. accuracy 0,5 %  

Current measurement  0/4...20mA, meas. accuracy 1,5 % .

Pulse inputs (Inputs  M1...M3)

Minimum pulse length 30ms 

Analog outputs  (Y1...Y4)

4 pcs. Output voltage range 0…10 V.  Output current max 7 mA /output.

PWM output:

1 piece that works in parallel with the Y1 output . The open circuit voltage of 15V.  

Output current is max. 50 mA, when output voltage is 10V

Relay outputs

6 pcs relays normally open contacts,  230V,  5A max,

Data transfer connections
 RS-485 connections 

 

(A1, B1 and A2, B2)

2 pcs, not optoisolated (Modbus RTU master or 1  RTU slave)  

COM2 and COM4.

  RS-232

1 ,  support to the external display (Ouman  LCD), COM1/ RJ-12 connector

  RS-232

1 , support to the GSM modem or M-LINK COM3/RJ-45 connector. 

 

NOTE! GSM modem and M-LINK can not be used simultaneously.

 USB device connector

1, Ouflex BA Tool online connection, COM5

 MicroSD memory card

Memory card is not included in the delivery.
Technical requirements to microSD memory card: Standard micro SDHC, UHS,  

Capacity 512 MB ...32 GB, File system FAT 32, Class: 4...10+

Freely programmable

Yes, with Ouman’s Ouflex BA Tool

Ouman ACCESS security solution

yes with M-LINK

Options

M-LINK

M-LINK network adapter provides Modbus TCP / IP interface for Ouflex M BA device

GSM modem

By connecting the Ouman GSM modem to the Ouflex M BA, you can communicate with 

text messages to device and receive alarms to GSM phone. 

Additional Control panel 

The Ouman LCD external display is connected to the flap cover over the RJ12 jack. 

 

Use Ouman cable LCD CABLE M.

APPROVALS

EMC-directive

2014/30/EU

Interference tolerance

EN 61000-6-1

Interference emissions 

EN 61000-6-3 

YM0015D_Ouflex M BA_User manual_ENG_ 20210930

Technical information

OUFLEX M BA

110mm

70mm

105mm

OUFLE

X M B

A

Saving energy, creating comfort

Summary of Contents for OUFLEX M BA

Page 1: ...ia M LINK DIN rail mounted module casing 6M Detachable strip connectors make installation easier Can be as a master device and slave device in the Modbus bus Compact freely programmable automation uni...

Page 2: ...arms go into the menu Alarms Active alarms Unacknowledged alarms are marked with an exclamation mark at the start of the line Some of the information in your Ouflex M BA device may be hidden You can s...

Page 3: ...ngs 8 1 5 Display settings 8 1 6 Type information 9 1 7 Lock code 9 1 8Restoresettingsandupdates 10 2 Alarms 11 3 Point info 13 3 1 Wiringinfo 13 3 2 Buspoints 13 3 3 Time programs 13 4 Settings 15 5...

Page 4: ...OK to accept 3 Set year and press OK to accept 4 To exit without saving and changes press Esc The language of the user interface can be changed here Service System settings Time System settings Date...

Page 5: ...ter number has not been inserted manually Press OK button for a few seconds to display hidden menus Remove message center number clear the first digit and press OK button for a few seconds Switch powe...

Page 6: ...user interface Otherwise check the network connections and ensure that DHCP server is available in the network Setting the IP address via DHCP function SettingtheIPaddressmanually 1 3 Network setting...

Page 7: ...IP address in Ounet SNMP SNMP function can be used to send notifications about alarms activating inactivating and being acknowledged via SNMP protocol to a desired server IP address The IP address of...

Page 8: ...o Modbus RTU It is shown in the first line in which the bus Ouflex M BA is the master device All the devices in the same bus should be set to the same setting value of the baud rate data bits stopbits...

Page 9: ...eturn to the previous square 3 Press OK for a number of seconds to accept the code Press ESC for a number of seconds to cancel System settings Network settings Display settings Type info Lock code Not...

Page 10: ...DHC UHS Capacity 512 MB 32 GB File system FAT 32 Class 4 10 Restore backup Internal memory Memory card Restore backup If you created a backup you can restore the backup by press ingOK Youcanrestorethe...

Page 11: ...alarm history Routing schedule Alarm receivers Alarm signal On Alarm params 2 Active alarms 07 11 2019 12 24 52 Risk 28 10 2019 01 12 40 Sen 2 Active alarms You can acknowledge all alarms by pressing...

Page 12: ...a new switch time 1 Press OK at the Add new row 2 Press OK Set the switch time for alarm routing set hours and minutes separately and press OK 3 Press OK and then use or knob to set the alarm team or...

Page 13: ...control just now When the automatic control is in use it is shown in the dis play what is state of the control according to the time program at the moment Control command can be either a weekly sched...

Page 14: ...chedule You can easily make changes that differ from normal routine use by using the exception schedule The date time and mode to which control will be changed in the period in question are entered in...

Page 15: ...t require maintenance code There is a symbol in front of these settings If you try to change one of these settings your Ouflex device asks you to enter the maintenance code Changing a setting Choose t...

Page 16: ...ss and hold OK Cancel Press and hold ESC Name of room 1 6 Naming Huoneiden valinta Huoneen 1 nimi Huone 1 Huoneen 2 nimi Huone 2 r m Automaticcontrolisthemodethatisnormallyused Ifyourapplica tion allo...

Page 17: ...ly one key word per message Store the key words into your phone s memory If a GSM modem is connected to the Ouflex M BA you can com municate with the controller by text messages using command words Se...

Page 18: ...erly attached to slot The SIM card can be removed by using a flat object such as a screwdriver with flat head To be able to use the SMS connection the PIN code has to be in stalled in the controller N...

Page 19: ...10V or 0 4 20mA 27 M4 28 GND 29 M5 30 GND 41 M6 42 GND 43 M7 44 GND 45 M8 46 GND 47 M9 48 GND 49 M10 50 GND 51 M11 52 GND 53 M12 54 GND 55 M13 56 GND 57 M14 58 GND 59 M15 60 GND Detachable strip conne...

Page 20: ...0ms Analog outputs Y1 Y4 4 pcs Output voltage range 0 10 V Output current max 7 mA output PWM output 1 piece that works in parallel with the Y1 output The open circuit voltage of 15V Output current is...

Reviews: