First Time Activation
To activate the detector, press and hold down button for approx 5 seconds. When activated, the detector will vibrate,
flash, and sound the audible alarm. A successful activation will display the life remaining in months on the detector as
24 months.
Display Details
The detector utilizes a special high viewing angle LCD that is designed to enhance the screen visibility. In the absence of
gas, it displays life remaining. In those cases where gas is present, the display will automatically shift to a display that
shows gas concentration and a battery icon.
NOTE: The display mode can be changed in the IR Link software with the "Sensor Reading" and "Life
Remaining" user options.
WARNING: Users must familiarize themselves with the icons in both non-alarm and alarm states
WARNING: If the display is missing icons or cannot be clearly read, please contact your local Otis
Instruments representative immediately.
1
Alarm Condition Icon
2
Self-Test Status Icon
3
Test Reminder Icon
4
Gas Type Icon
5
Battery Indicator Icon (used during Real-Time Gas
Reading)
6
Instrument Life Remaining or Real-Time Gas Reading Data
7
High and Low Alarm Set Point Icons
1 / 7
Alarm Condition Icons
6 / 8
Instrument Life Remaining Icons
9
Infrared Data Transfer Icon
10 / 11
Months / Days / Hours Since Last Maximum Exposure
6 / 11
Instrument Life Remaining Data and Icon
5