40
SERVICE MENU: “SUPPLY LIMITS”
In this menu the upper and lower limits for the supply air temperature at room or extract air regulation is set.
Press and then in order to choose a
minimum limit value
(15°C–19°C).
Press again and then in order to choose a
maximum limit value
(20°C–Max temperature).
ENTER
ENTER
i
UP
UP
DOWN
DOWN
ENTER
i
UP
UP
DOWN
DOWN
ENTER
ENTER
ENTER
UP
UP
DOWN
DOWN
UP
UP
DOWN
DOWN
ENTER
ENTER
SERVICE MENU: “REGULATION MODE”
2 different types of regulation modes can be used.
• At a
constant supply air regulation
the temperature sensor (GT7) is placed in the supply air duct and
a constant incoming air temperature is obtained.
• At
room regulation
a sensor (GT8) is placed in the room and a sensor (GT7) in the supply air duct
(min./max. limitation) and a constant room temperature is obtained (suitable when a cooling coil is installed).
Press again and then in order to choose
Supply reg.
or
Room reg.
i
UP
UP
DOWN
DOWN
a
ENTER
UP
UP
DOWN
DOWN
ENTER
ENTER
ENTER
UP
UP
DOWN
DOWN
UP
UP
DOWN
DOWN
ENTER
ENTER
UP
UP
DOWN
DOWN
ENTER
Continues
SERVICE MENU: “MODBUS”
Modbus communicate via RS485.
For this you need complete Modbus index which can be downloaded from www.ostberg.com.
ID, Baud
and
Parity
rate must match the client settings.
1270431_utg1_SAU_EC_sv_en.indd 40
2019-01-11 12:53:21