Montage-/installationsanvisning

Assembly/Installation instructions

 

 TILLUFTSAGGREGAT SAU EC 

SUPPLY AIR UNIT SAU EC

1270431_utg1_SAU_EC_sv_en.indd   1

2019-01-11   12:52:24

Summary of Contents for SAU 125 EC

Page 1: ...SVENSK ENGLISH VERSION Montage installationsanvisning Assembly Installation instructions TILLUFTSAGGREGAT SAU EC SUPPLY AIR UNIT SAU EC ...

Page 2: ...nvändning eller arbeten som orsakas av att användaren under låtit att beakta varnings eller installations anvisningar eller utredning av sådant Garantgivaren ansvarar enbart för funktionen om godkända tillbehör används Garantin omfattar inte fel på produkten som orsa kats av tillbehör utrustning av annat fabrikat Aggregatets aktuella inställningar ska nertecknas i installations montageanvisningen ...

Page 3: ... UNIT DESCRIPTION 26 SAU EC WITH HEATER 26 SAU EC WITH HEATING COIL 26 SECURITY AND INSTALLATION 27 SECURITY HOW TO HANDLE USE INSTALLATION OPERATION 27 ASSEMBLY INSTRUCTIONS 28 CONTROL DIAGRAMS 29 REGULATION FUNCTIONS 30 OPERATING THE CONTROL UNIT 31 MAIN MENU 32 FAN SPEED MENU 32 TEMPERATURE MENU 32 WEEK TIMER MENU 33 POWER ON OFF MENU 34 SETTINGS MENU 34 SERVICE MENU 35 41 CONSTANT PRESSURE 35 ...

Page 4: ...tflödet genereras av en tystgående radialfläkt med EC motor Energieffektiv ytterrotormotor med underhållsfria dubbelkapslade kullager Fläkthjul med bakåtböjda skovlar som är enkelt att ta ur för rengöring genom att lossa två skruvar Med den externt placerade displayen som tråd ansluts till aggregatet ställs önskad temperatur in Olika lägen som bortaläge och normalläge kan även schemaläggas En lysd...

Page 5: ...p om de ej övervakas eller instrue ras angående produktens användning av en person ansvarig för deras säkerhet Barn skall hållas under uppsikt för att försäkra att de inte leker med produkten Aggregatet ska användas för transport av ren luft m a o den är ej avsedd för transport av brand och explosionsfarliga ämnen slipdamm sot o dyl För maximal livslängd vid installation i fuktig eller kall miljö ...

Page 6: ...NTERAD VÄGGMONTERAD Serviceområde FRAMIFRÅN FRÅN SIDAN Montera på golv vägg eller tak med fästelement anpassade efter dess konstruktion och beskaffenhet Slot 12x6 mm x4 658 mm Serviceområde 658 mm Serviceområde Slot 12x6 mm x4 658 mm Slot 12x6 mm x4 ...

Page 7: ...7 REGLERSCHEMAN SAU EC som visar samtliga givare ...

Page 8: ...ås ningstemperatur aktiveras eftervärmaren och värmer tilluften till önskad temperatur 3 Kyla När utetemeperaturen överstiger önskad inblås ningstemperatur aktiveras kylbatteriet och kyler tilluften till önskad temperatur Kräver kringutrustning FLÄKTKAPACITET Via manöverenheten kan man manuellt styra fläkt hastigheten och även forcera luftflödet under angiven tidslängd Luftflödet fläkthastigheten ...

Page 9: ...ryckt i 3 sekunder Nedre raden visar möjliga val med tangent Översta raden och mittersta fältet visar aktuella värden och aktiviteter Statuslampa Grön Aggregat i drift Röd blinkande Larm Släckt Aggregat av UPP NED ENTER BACK UPP NED ENTER BACK VISNINGSLÄGE 2 Visningsläge 2 visar givarnas data UPP UPP NED NED SYMBOLER SOM KAN VISAS PÅ VISNINGSLÄGE 1 Funktion för tangent upp och ned för visningsläge...

Page 10: ...eringen från Visningsläge till Huvudmenyn tryck I Huvudmenyn används för att markera önskad meny sedan görs valet med I undermenyn är sedan tillvägagångssättet detsamma För att återkomma till föregående sida tryck HUVUDMENY Utfört val överstyrs av veckoursfunktionen om den är aktiverad Utfört val överstyrs om veckoursfunktionen är aktiverad ENTER ENTER BACK f ENTER ENTER ENTER UPP UPP NED NED UPP ...

Page 11: ...ma vidare till val av veckodag starttid stopptid fläkthastighet och temperatur Använd tagenterna för inställningar av veckodag tid fläkthastighet Normal Borta Forcering och temperatur 15 C 30 C MENY VECKOUR OBS Veckoursfunktionen överstyr manuella inställningar av fläkthastighet och temperatur Program som har lägst index får företräde då program överlappar varandra t ex Program 1 har företräde fra...

Page 12: ...t sedan för att ställa in tid Tryck för att ställa in språk Tryck och sedan för att välja språk Bekräfta med 10 språk finns att tillgå svenska finska danska norska ryska tyska italienska franska engelska och spanska Tryck för att ställa in måttenhet Tryck igen och sedan för att välja måttenhet Välj mellan Metrisk och Imperial Bekräfta med MENY INSTÄLLNINGAR UPP UPP NED NED ENTER ENTER ENTER Vent P...

Page 13: ...a och varje siffra bekräftas med Efter lösenord 1199 till Servicemenyn kommer frågan Är du säker Tryck för Ja eller för Nej För att komma vidare i Servicemenyn till de olika rubrikerna Tryck MENY SERVICEMENY f ENTER t UPP UPP S NED S i S NED ENTER f ENTER f BACK UPP UPP NED NED UPP UPP NED NED ENTER ENTER Kod Veckour Vent På Av Inställningar Servicemeny Är du säker Nej Ja f ENTER f BACK f UPP UPP ...

Page 14: ...Se Servicemeny Larm SERVICEMENY TRYCKGIVARE Om tryckgivare installeras ska kompatibelt mätområde på tryckgivare anges 50 50 Pa 0 100 Pa 0 150 Pa 0 300 Pa 0 500 Pa 0 1000 Pa 0 1600 Pa och 0 2500 Pa Signal från tryckgivare ska vara 0 10 V DC Om filtervakter är installerade kan dessa aktiveras i denna meny Om man anger Ingen aktiveras filtertimer automatiskt UPP UPP NED NED ENTER ENTER ENTER Tryckgiv...

Page 15: ...ENTER ENTER UPP UPP NED NED ENTER UPP UPP NED NED ENTER NED NED NED NED EC motor setup EC motor setup Normal Borta Forcering Normal Borta Forcering Tilluft 20 Tilluft 50 Borta Forcering Tilluft 20 Tilluft 50 Borta Forcering Filtermätning EC motor setup Display kontrast Forcering Kontrast Kontrast ENTER ENTER UPP UPP NED NED ENTER SERVICEMENY FORCERING Inställning av tid för forcering Forcering bet...

Page 16: ...stemperatur visas i displayen då temperaturen i tilluftskanalen GT7 understiger inställt värde Gräns B Larmgränsvärdet kan ställas från 5 till 12 C men kan inte ställas lägre än Gräns A 1 C Om temperaturen i tilluftskanalen GT7 understiger inställt värde avaktiveras forceringsläget om detta är aktivt I meny Brandsensor görs inställning av vilken typ av brandsensor som är installerad Välj typ Norma...

Page 17: ... Tryck igen och sedan för att välja Ramp 2 200 h Vid nivåer över gränsvärdet ökar fläkten enligt inställt Ramp värde 200 ger 2 varvs påslag per timme I nedanstående exempel kommer fläktens hastighet att öka med 50 h då luftens koldioxidhalt överstiger 900 PPM Aktuellt CO2 värde kan sedan ses i Visningsläge 2 SERVICEMENY KYLVATTENBATTERI I denna meny kan ett kylvattenbatteri aktiveras om sådant är ...

Page 18: ...lles en konstant inblåsningstemperatur Vid Rumsreglering placeras en givare GT8 i rummet samt en givare GT7 i tilluftskanalen min max begränsning då erhålles en konstant rumstemperatur lämpligt då kylvattenbatteri är monterat Tryck igen och sedan för att välja Konst tilluft eller Rumsregl SERVICEMENY MODBUS Modbu kommunicerar via RS485 Till detta behövs komplett modbusregister som kan laddas ned f...

Page 19: ...g UPP UPP NED NED ENTER Modbus Frysskydd Sensorjustering Ladda Spara Sensorjustering Sensorjustering Forts UPP UPP NED NED ENTER UPP UPP NED NED ENTER UPP UPP NED NED ENTER Sensorjustering Sensorjustering Sensorjustering f UPP UPP NED NED i ENTER ENTER NED NED ENTER BACK ENTER BACK Frysskydd Sensorjustering Ladda Spara Version info Ladda Spara Ladda installation Spara installation Är det säkert Fö...

Page 20: ...kanter Skruva loss motorplattan från fläkthuset de yttre skruvarna och lyft ur motor med fläkthjul Fläkthusochfläkthjultorkasrentmedenfuktigtrasa Vid rengöring av fläkten får högtryckstvätt eller starka lösningsmedel ej användas Rengöring måste ske på ett sådant sätt att fläkthjulets balansvikter ej rubbas eller fläkthjulet skadas Vid behov torkas aggregathuset Fläktmotorns lager är underhållsfria...

Page 21: ...nnat Att aggregatet har ström Kontrollera säkring samt säkerhetsbrytare Om larm löst ut Kontrollera varför det larmar se nedan åtgärda felet När orsakande fel är åtgärdat återställ larm Filtermätning går ej att aktivera Att tryckgivare är installerade Aktivera givare Se sidan 14 Övriga larm Filter Om filtren är smutsiga Byt filter Om inställd tid för filtermätning är uppnådd Byt filter Återställ t...

Page 22: ...På Av Fabriksinställning Av Vatten På Av Fabriksinställning Av Kyla På Av Fabriksinställning Av Min 15 C 19 C Fabriksinställning 17 C Max 20 C Max temp Fabriksinställning 26 C Reglertyp Konstant tilluft Rumsreglering Fabriksinställning Konstant tilluft ID 1 254 Fabriksinställning 1 Baud 2400 57600 Fabriksinställning 9600 Paritet Jämn Udda Ingen Fabriksinställning Jämn Gräns 5 C 10 C Fabriksinställ...

Page 23: ...NWURPDJQHWLVND IlOW PHG DYVHHQGH Sn H SRQHULQJ LUHNWLYHW I U HOHNWURPDJQHWLVN NRPSDWLELOLWHW 0 8 DUPRQLVHUDQGH VWDQGDUGHU x 1 OHNWURPDJQHWLVN NRPSDWLELOLWHW 0 HQHUHOOD IRUGULQJDU PPXQLWHW KRV XWUXVWQLQJ L ERVWlGHU NRQWRU EXWLNHU RFK OLNQDQGH PLOM HU x 1 OHNWURPDJQHWLVN NRPSDWLELOLWHW 0 HQHUHOOD IRUGULQJDU PPXQLWHW KRV XWUXVWQLQJ L LQGXVWULPLOM x 1 OHNWURPDJQHWLVN NRPSDWLELOLWHW 0 HQHUHOOD IRUGULQJ...

Page 24: ...o not impact operation e g surface scratches Parts that through handling or normal wear are exposed to greater than average hazard e g lamps glass ceramic paper and plastic parts and filters and fuses are not covered by the warranty Settings information on use care handling service or cleaning that are customarily described in the instructions for use or works caused by the user neglecting to obse...

Page 25: ...NSORJUSTERING LADDA SPARA VERSION INFO 19 SERVICE 20 AVINSTALLATION 20 AVFALLSHANTERING 20 FELSÖKNING 21 TILLBEHÖR 21 RESERVDELSFÖRTECKNING 21 EGNA INSTÄLLNINGAR 22 EU FÖRSÄKRAN 23 WARRANTY 24 UNIT DESCRIPTION 26 SAU EC WITH HEATER 26 SAU EC WITH HEATING COIL 26 SECURITY AND INSTALLATION 27 SECURITY HOW TO HANDLE USE INSTALLATION OPERATION 27 ASSEMBLY INSTRUCTIONS 28 CONTROL DIAGRAMS 29 REGULATION...

Page 26: ...o screws The unit has an external control unit for operating and to preset the required temperature as well as monitor the unit s status Different modes such as Away and Normal mode can also be scheduled A Led light simply shows the status of the unit The control unit is designed to be placed recessed on the wall 10 m cable is included as standard The unit can also be controlled with a room sensor...

Page 27: ...use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance The unit is used for transportation of clean air meaning not intended for fire dangerous substan ces explosives grinding dust soot etc To achieve maximum life time for installations in damp or cold environments the unit should be operating continuously The ...

Page 28: ...EILING FLOOR MOUNTED WALL MOUNTED Service area FRONT VIEW FROM THE SIDE Mount on floor wall or ceiling with fasteners adapted to its structure and quality Slot 12x6 mm x4 658 mm Service area 658 mm Service area Slot 12x6 mm x4 658 mm Slot 12x6 mm x4 ...

Page 29: ...29 CONTROL DIAGRAMS SAU EC that shows all sensors ...

Page 30: ...mperature the heater is activat ed and heats the supply air to desired temperature 3 Cooling When the outside temperature is higher than desired supply air temperature the cooling coil is activated and cooling the supply air to desired temperature Requires accessories FAN CAPACITY With the control unit it is possible to control the fan speed and also boost the airflow during a specific time Airflo...

Page 31: ... disable the keylock press down the key for 3 seconds Bottom row shows the possible choices with key Top row and middle field displays current values and activities Status light Green Unit is running Red flashing Alarm Light off Unit is off UP DOWN ENTER BACK UP DOWN ENTER BACK VIEW MODE 2 View mode 2 shows data of sensors UP UP DOWN DOWN Function of keys up and down for view mode 2 Alarm Symbol i...

Page 32: ...red temperature Confirm with FAN SPEED MENU TEMPERATURE MENU In order to go forward in the menu from the View mode to the Main Menu press In the Main Menu is used to select the desired menu when the choice is made press The procedure is the same in the submenu In order to return to the previous page press MAIN MENU Made settings is overridden if Week Timer is activated Made settings is overridden ...

Page 33: ... There are 5 programs for the adjustment of the fan speed and temperature available Press to choose a program Press in order to go forward to choose a weekday start time end time fan speed and temperature Use the keys to choose the settings of weekday start time end time fan speed Normal Away Boost and temperature 15 C 30 C WEEK TIMER MENU N B The activated Week Timer overrides the manuel settings...

Page 34: ...ess in order to go forward from the Main Menu Press again and then in order to choose weekday Press again and then in order to enter the time Press in order to enter a language Press and then in order to choose a language Confirm with 10 languages are available Swedish Finnish Danish Norwegian Russian German Italian French English and Spanish Press in order to enter a unit system Press and then in...

Page 35: ... required in order to make adjustments The password is 1199 and it can not be changed Press in order to go forward from the Main Menu The password is entered with the keys and every number is confirmed with After the password 1199 to the Service Menu the question Are you sure will be displayed Press f or Yes or for No To go further to the different functions in the Service menu press t ENTER t BAC...

Page 36: ...p in filter SAU EC with CPC Filter measurement becomes active if the analog pressure sensor is selected and CPC Constant Pressure Control is activated and benchmarks are set and saved Alarm is displayed when the bench marks and increased fan speed exceeded set value In this case with 15 to keep constant pressure in duct It is possible to choose 5 50 increased speed or Off to disable If filter guar...

Page 37: ...ER ENTER ENTER UP UP DOWN DOWN ENTER UP UP DOWN DOWN ENTER NED NED NED NED ENTER ENTER UP UP DOWN DOWN ENTER SERVICE MENU BOOST Time settings for Boost Boost means that during a limited time the air flow increases which can be good for example at larger gatherings This boost can then be activated in the Main Menu Fan speed Press in order to go forward to Boost in the Service menu Press again and t...

Page 38: ...OWN DOWN ENTER ENTER UP UP DOWN DOWN ENTER ENTER BACK Alarm limits for Low temperature Alarm limit A 2 till 10ºC but must be lower than Alarm limit B 1 C The unit is stopped and alarm Low supply temperature is displayed when the temperature in supply air duct GT7 is lower than set value Alarm limit B Can be set from 5 to 12ºC but have to be higher than Alarm limit A 1 C If the temperature in suppl...

Page 39: ...speed will increase with 50 h when the relative air humidity level is higher than 70 Current RH value is displayed in View mode 2 SERVICE MENU CO2 Carbon dioxide level in PPM part per million In this menu settings are made for regulation with installed CO2 sensor Press and then in order to choose the Limit value 500 1400 PPM Press again and then in order to choose Ramp 2 200 h At levels above the ...

Page 40: ...r regulation the temperature sensor GT7 is placed in the supply air duct and a constant incoming air temperature is obtained At room regulation a sensor GT8 is placed in the room and a sensor GT7 in the supply air duct min max limitation and a constant room temperature is obtained suitable when a cooling coil is installed Press again and then in order to choose Supply reg or Room reg i UP UP DOWN ...

Page 41: ...ss again and then in order to choose Load Settings or Save settings After Load or Saved it may take a minute before the unit reconnect to the control unit and the right data is displayed ENTER ENTER ENTER ENTER UP UP DOWN DOWN ENTER UP UP DOWN DOWN ENTER UP UP DOWN DOWN ENTER UP UP DOWN DOWN ENTER i UP UP DOWN DOWN a ENTER ENTER DOWN DOWN ENTER BACK ENTER BACK a ENTER Continue SERVICE MENU SENSOR ...

Page 42: ...e outer screws 3 and pull the motor out of the fan housing The fan housing and fan wheel are cleaned with a damp cloth When cleaning the fan high pressure cleaning or strong dissolvent must not be used Cleaning should be done without dislodging or damaging the impel ler When needed wipe the unit inside Thefanbearingsaremaintenance freeandshouldbe renewed only when necessary Reassemble all details ...

Page 43: ...tion to relay card If error remains change broken sensor Overheating If the heat protection of the duct heater is Restore the manual overheating protection and triggered NB The unit must be disconnected reset the alarm Low supply air temperature If filters are dirty Change filter If the heater works Ensure function before startup Fire alarm Why the fire alarm is triggered Ensure function before st...

Page 44: ...talled Default Not installed Autom reset Off On Default Off Alarm indication None Fire alarm Sensor open Sensor shorted Overheat prot Freeze alarm Supply temp low Fan failure Filter Filter timer Default None Limit 500 1400 PPM Default 900 PPM Ramp 2 200 h Default 50 h Limit 50 100 Default 70 Ramp 2 200 h Default 50 h Electric On Off Default Off Water On Off Default Off Cooler On Off Default Off Mi...

Page 45: ...OLDQFHV DQG VLPLODU DSSDUDWXV ZLWK UHJDUG WR KXPDQ H SRVXUH LUHFWLYH IRU OHFWURPDJQHWLF RPSDWLELOLW 0 8 DUPRQLVHG VWDQGDUGV x 1 OHFWURPDJQHWLF FRPSDWLELOLW 0 HQHULF VWDQGDUGV PPXQLW IRU UHVLGHQWLDO FRPPHUFLDO DQG OLJKW LQGXVWULDO HQYLURQPHQWV x 1 OHFWURPDJQHWLF FRPSDWLELOLW 0 HQHULF VWDQGDUGV PPXQLW IRU LQGXVWULDO HQYLURQPHQWV x 1 OHFWURPDJQHWLF FRPSDWLELOLW 0 HQHULF VWDQGDUGV PLVVLRQ VWDQGDUG IRU...

Page 46: ...46 ...

Page 47: ...ISKA DATA 49 LJUDDATA 50 52 TRYCK FLÖDESDIAGRAM 53 KOPPLINGSSCHEMAN 54 55 DIMENSIONS 48 TECHNICAL DATA 49 SOUND DATA 50 52 PRESSURE FLOW DIAGRAMS 53 WIRING DIAGRAMS 54 55 TEKNISK INFORMATION 47 55 TECHNICAL INFORMATION 47 55 ...

Page 48: ...48 DIMENSIONS MÅTTSKISSER mm SAU 125 EC SAU 200 EC SAU 250 EC ...

Page 49: ... i oktavband i dB A ref 10 12 W I Tekniska Data återfinns total ljudtrycksnivå LpA i dB A ref 20 x 10 6 Pa beräknat på den totala ljudeffektnivån för aggregatljud vid 230 V Relationen mellan ljudtryck och ljudeffekt är LpA LwA 10 x log där Q är riktningsfaktor r är avstånd från aggregatet och AEkv är ekvivalent absorbtions area Vid beräkning av LpA har det antagits att Q 2 r 3 m och AEkv 20 m2 vil...

Page 50: ...ft 58 50 53 54 46 38 44 39 27 Supply Tilluft 69 55 59 62 61 59 64 55 46 7V 55 I s 220 Pa Surrounding Omgivning 47 27 40 44 38 30 29 28 28 Extract Frånluft 55 47 51 51 42 36 41 36 23 Supply Tilluft 66 54 58 60 57 55 61 52 42 6V 47 I s 170 Pa Surrounding Omgivning 44 22 37 41 34 28 26 27 28 Extract Frånluft 53 46 49 48 39 32 37 32 19 Supply Tilluft 63 51 54 58 53 51 57 47 36 5V 40 I s 120 Pa Surroun...

Page 51: ...luft 59 47 51 58 47 39 38 36 24 Supply Tilluft 69 53 56 67 63 58 56 54 47 7V 89 I s 165 Pa Surrounding Omgivning 48 26 37 46 39 29 26 26 27 Extract Frånluft 59 45 48 58 44 36 35 33 20 Supply Tilluft 69 51 55 67 60 55 53 51 42 6V 78 I s 125 Pa Surrounding Omgivning 45 24 34 44 35 27 24 25 27 Extract Frånluft 55 43 46 53 41 33 32 29 15 Supply Tilluft 65 49 53 64 56 51 50 46 36 5V 67 I s 95 Pa Surrou...

Page 52: ...uft 54 45 43 52 35 35 34 34 23 Supply Tilluft 65 49 50 62 58 56 52 52 42 6V 115 I s 180 Pa Surrounding Omgivning 46 30 31 45 34 29 26 26 26 Extract Frånluft 53 42 41 52 34 32 32 30 18 Supply Tilluft 64 45 48 62 55 52 50 48 36 5V 98 I s 130 Pa Surrounding Omgivning 40 22 27 39 30 26 24 25 26 Extract Frånluft 53 39 37 53 31 28 29 26 14 Supply Tilluft 58 42 45 56 49 48 46 41 29 4V 79 I s 80 Pa Surrou...

Page 53: ... 3 s Flow m3 h Flow m3 s Flow m3 s Flow m3 s SFP PRESSURE FLOW TOTAL POWER FLOW Static pressure Pa Power W kW m 3 s Flow m3 h Flow m3 s Flow m3 s Flow m3 s SFP PRESSURE FLOW TOTAL POWER FLOW Static pressure Pa Power W kW m 3 s Flow m3 h Flow m3 s Flow m3 s Flow m3 s ΔT SUPPLY AIR ΔT C Flow m3 s ΔT SUPPLY AIR ΔT C Flow m3 s ΔT SUPPLY AIR ΔT C Flow m3 s ...

Page 54: ...54 WIRING DIAGRAM KOPPLINGSSCHEMA 4040206 SAU 125 C1 EC ...

Page 55: ...WIRING DIAGRAM KOPPLINGSSCHEMA 4040207 SAU 200 B3 EC SAU 250 B3 EC 1270431_utg1_SAU_EC_sv_en indd 55 1270431_utg1_SAU_EC_sv_en indd 55 2019 01 21 14 32 16 2019 01 21 14 32 16 ...

Page 56: ... E mail info ostberg com www ostberg com ÖSTBERG NORGE AS Løxaveien 13 1351 Rud Norge Tel 67 17 77 00 Faks 67 17 77 10 E mail post ostbergnorge no www ostbergnorge no H ÖSTBERG OY Lakimiehenkatu 8B 20780 Kaarina Suomi Puh 075 758 7000 E mail suomi ostberg com www ostberg com 1270431 utg 1 ...