background image

Immersion heaters

All units are fitted with one immersion heater which is located behind the lower electrical box.

Wiring instructions for the immersion heater is located on the reverse side of the lower lid. Follow 

the wiring instructions connecting the live, neutral and earth as indicated. The electrical connection 

to the immersion heater must conform to current IEE wiring regulations. The unit must be 

permanently connected to the electrical supply through a double-pole linked switch with a 

minimum break capacity of 13 amps. All internal wiring is factory mounted. Each immersion 

heater has a working thermostat adjustable between 40°C - 70°C. A safety cut-out is also 

incorporated within the thermostat and will operate at 85°C ± 3°C. Should this happen, press the 

reset button.

Important: Before resetting the safety cut-out or altering the thermostat setting, isolate 

electrical supply to the unit prior to removal of the lid. Ensure the lid to the electrical box 

is replaced correctly and the retaining screw is fitted.

Indirect Units upper coil

Motorised valve

To comply with regulations governing the installation of indirect unvented cylinders, a motorised 

valve must be fitted in the primary flow. Your OSO unit has been supplied with a two port 

motorised valve, which will act as a positive energy cut-out should the safety cut-out operate. 

The motorised valve will also control the temperature of the domestic stored water via the 

cylinder thermostat, which is located in the upper electrical box. The unit should be installed on 

an “S” or “Y” plan system. Cylinder temperature control can also be achieved via the solar 

thermostat when the boiler is not operational.

Please follow the instructions carefully.

 All electrical connections must conform to current IEE 

wiring regulations. The working thermostat is adjustable between 40°C - 70°C. A safety cut-out 

is also incorporated within the thermostat and will operate at 85°C ± 3°C. Should the safety 

cut-out be brought into operation, the motorised valve will operate and close down the primary 

flow to the cylinder. To reset the safety cut-out and the motorised valve the reset button must be 

pressed in (see fig.4 page 8).

Lower (Solar) coil

Heat sources to unvented hot water cylinders must be controlled by a thermal cut-out as well as 

a thermostat. The OSO Solarcyl is supplied both with bosses for solar sensor pockets and the 

pockets themselves.

The top half of the thermostats fitted to the cylinder is a thermal cut-out. The solar controller (not

supplied) and solar sensor point should be wired through the OSO thermal cut-out. See fig. 4 

pages 8 & 10.

Please note that the direction of flow in the solar coil is reversed compared to the boiler coil. If 

the cylinder is not being used for solar use, connect the boiler to the lower coil with the primary 

flow in a bottom to top direction.

OSO Hotwater (UK) Limited can not be responsible if alternative wiring plans are used.

Important: Before resetting the safety cut-out or altering the thermostat setting isolate 

electrical supply to the unit before removal of the lid.

ELECTRICAL INSTALLATION

-7-

Summary of Contents for Solarcyl IM/SC2

Page 1: ...sed valve indirect only Components factory fitted Immersion heater s Thermostats thermal cut out Temperature and pressure relief valve Installation details The OSO unvented unit is designed for use wi...

Page 2: ...8 Cold Feed Tube Not supplied see Table 2 9 Hot Water Outlet 3 4 BSP 10 Flexible Hose 202108 12 Secondary Return Connection Blanking Plug 13 Elbow Drain Cock 250445 14 Cable Entry 15 Electrical Box 16...

Page 3: ...all close to the water heater using the enclosed mounting bracket Connect the expansion vessel hose to the T piece in the cold feed pipe to the cylinder Hot water supply 15 Connect the hot water suppl...

Page 4: ...before resetting the safety cut out or altering the thermostat setting isolate electrical supply to the unit prior to removal of the electrical box lid 3 Reduce thermostat setting and press the reset...

Page 5: ...s Failure to do this may result in irreparable damage to the controls and will invalidate the warranty 3 The MULTIBLOC can be fitted in any orientation to suit the installation as long as it is fitted...

Page 6: ...in reverse order Do not overtighten Expansion valve cartridge and seat Part No 214009 8 0 Bar Complete Expansion Valve Part No 510 505 8 0 Bar It is recommended that annually a competent person a Insp...

Page 7: ...r thermostat which is located in the upper electrical box The unit should be installed on an S or Y plan system Cylinder temperature control can also be achieved via the solar thermostat when the boil...

Page 8: ...an shown is based on the use of a 10 way Junction Box Honeywell Part no 42002116 001 Junction Box terminal 8 is switched live and if needed terminal 10 is pump live 8 FIGURE 4 SOLAR CONTROLLER WIRING...

Page 9: ...Automatic bypass Sensor Pocket Solar Collector 9...

Page 10: ...n shown is based on the use of a 10 way Junction Box Honeywell Part no 42002116 001 Junction Box terminal 8 is switched live and if needed terminal 10 is pump live 10 FIGURE 4 1 3 2 1 2 4 RESET Safety...

Page 11: ...Automatic bypass Sensor Pocket Solar Collector 11...

Page 12: ...on vessel Follow recommissioning instructions on page 4 2 Switch off power to immersion heater s and boiler supply to the unit When discharge has stopped check thermal controls replace it faulty Conta...

Page 13: ...Repressurize expansion ves sel Follow recommissioning instructions on page 4...

Page 14: ......

Page 15: ..._______________________ _____________________________________________________________________________ _____________________________________________________________________________ ____________________...

Page 16: ...of flats the number served should be limited to not more than 6 systems so that any installation discharging can be traced reasonably easily The single common discharge pipe should be at least one pip...

Reviews: