11
Forandringer forbeholdes - Subject to change without notice - Ändringar kan förekomma
Installation – important!
The heater must be filled with water before the electricity is connect
-
ed. Otherwise the warranty does not apply. If the heater is installed
but not in use, it must be flushed with water once a week by opening
a hot water tap for at least 15 min.
Electrical installation
IMPORTANT: The water heater must be connected to a separate
switch. Fill unit with water BEFORE power on. Otherwise guaran
-
tee is void.
Electrical connections – technical data:
Electric element: RG 3 kW (RI SD 1,95 kW) 230V 1 phase, 1 ¼” connection
Electric element up to 4,5 kW can be installed.
Thermostat:
Adjustable 60-90ºC.
Safety cut-off:
98ºC
Electric central:
Internally connected from factory. Splash proof IP21.
Power cable:
2,3 mtrs cable. Output >3kW or when 400V 3 phase is
installed requires fixed connection
For installation in sanitary rooms special regulations apply.
Important: All alterations or repair concerning the electrical equipment must be per-
formed by authorized electricians only, and in accordance with the diagrams shown.
All connections must be pulled tight. This must be repeated after approximately
three months’ operation.
230V 1-phase
1
3
2
4
RESET
1
2
BA
CK
ER
19
96
R
5/4
"
Reset
button
Safety
thermostat
Temperature
adjustment
Thermostat
Element 5/4”
Electrical connection - Warranty
The OSO stainless steel inner vessel is guaranteed against material defect or manufacturing faults for a period of 10 years from the date of purchase.
All other parts including, but not limited to factory fitted electrical elements (damage caused by lime scale and aggressive water excluded), expansion
vessel, thermostats and valves are guaranteed against material defects or manufacturing faults for 2 years from the date of purchase. In the event of a
replacement component being required OSO Hotwater will supply such part(s) free of charge and freight paid, on condition that the defective component
is delivered, freight paid to OSO Hotwater within 2 weeks of written notice being given to OSO Hotwater of the defect. Such replacement parts shall be
guaranteed under the terms of this guarantee to the unexpired period of the aforementioned 2 year period.
This warranty is conditional upon the OSO cylinder being installed in compliance with the OSO Installation & Maintenace Instructions, all current legislation, codes
of practice and regulations governing the installation of unvented hot water cylinders in force at the date of installation and provided that:
1. The water quality shall be in accordance with European Council Directive 98/83 EC, or revised version at the date of installation,
and is not fed with water from a private supply.
Particular: Chloride content:
Max. 250 mg/l
Sulphate content:
Max. 250 mg/l
Combination Chloride/sulphate:
Max. 300 mg/l (in total)
2. The OSO cylinder is filled with water before turning the electricity supply on to the heater elements.
3. If the newly fitted water heater is not in regular use then it must be flushed through with fresh water for at least 15 minutes.
Open at least one hot water tap once per week, during a period of at least 4 weeks.
4. The OSO unvented cylinder has not been modified in any way other than by OSO Hotwater and is only used for the storage
of potable water.
5. No factory fitted parts have been removed for unauthorised repair or replacement.
6. Defects caused by frost, excess pressure, salt dehardner process, transient voltage, lightning strikes or incorrect installation,
repair or use, are not covered by this warranty. A laboratory evaluation of possible defects can be ordered by the user,
however the user must pay for this where the above mentioned conditions have not been fulfilled. Evidence of the purchase
date and the date of supply must also be submitted with your claim.
This guarantee does not confer any rights other than those expressly set out above and does not cover any claims for consequential loss or damage. This
guarantee is offered as an extra benefit and does not affect your statutory rights as a consumer.
Warranty
Electrical equipment - description:
Thermostat
TS2, adjustable from 60-90°C. Temperature is adjusted by turning the arrow on the temperature adjustment
scale to the preferred temperature. IMPORTANT: When the internal temperature in the water heater is set
close to 60°C there is a slight risk of bacterial growth in the unit. A temperature setting of 65°C or above is
preferable. The factory setting is 75°C.
Reset button
Located on the upper part of the TS2 thermostat, this button will release and cut all power to the heating
element if the internal temperature in the water heater rises above 98°C. If this occurs, the function of the
thermostat must be checked by authorized personnel before the reset button is pressed.
Internal wiring
All internal wiring is factory fitted. 2.5 mm² wires are standard. The RI SD is also factory fitted with a standard
external power cable, complete with plug for grounded sockets. Lenght 3 m.
Heating element
RG 5/4”. The element is resistant to up to 250 mg. Cl/litre.
An RG 5/4” - 4,5 kW - 230V 2-phase element is also available as an option if shorter heat-up time is required.