background image

10

Forandringer forbeholdes - Subject to change without notice - Ändringar kan förekomma

Elements 

     

Product No.

RG 5/4” 1,95 kW 230V 1-phase with o-ring seal 

 

801 5191

RG 5/4”  3 kW 230V 1-phase with o-ring seal   

 

801 5044

RG 5/4”  4,5 kW 400V 3-phase with o-ring seal (for higher effect) 

801 5189

O-ring for 5/4” element  

 

 

 

    73 650

Internal wire from thermostat to element (up to 2 kW) 

 

801 5295

KN 5/4” wrench for 5/4” element   

 

 

801 5195

Thermostat

TS2  60-90°C with safety  thermostat 98°C 

 

 

801 5823

Valves etc.

SV 2 - 9 bar safety valve 

 

 

 

801 5741

TPR15 P&T valve 1/2”  

 

 

 

    92 020

UX 15 - mixing valve   

 

 

 

801 5729

UXT 15 - thermostatic mixing valve for RI SD   

 

801 5755

Sensor pocket 

 

 

 

 

    81 020

Spare parts

Safety valve SV9 bar (RI HP and RI TC)

The safety valve is fitted near the bottom of the 

unit, directly below the electric central. 

The plug D can be used as a drain. It is also pos

-

sible to drain the unit by opening the safety valve 

itself, by turning knob K counter-clockwise until it 

stays open. To close valve continue turning coun

-

ter-clockwise until the valve snaps shut.  

RI SD

 is fitted with a P&T valve 10 bar/95°C. Can 

be drained through 1/4” outlet at the bottom.

Warning

Do  not  remove  or  plug  the  factory  fitted  safety 

valve.  The  valve  must  have  a  free  flowing,  non 

closeable 3/4” (min. internal diameter 18 mm) out

-

let to a visible and frost free drain/gully! The safety 

valve should be operated annually (first time after 

approx. 3 months) to ensure the water is free flow

-

ing, see “Safety valve” above. 

Mixing valve

The Ecoline series is fitted with an OSO UX 15 me

-

chanic mixing valve (RI SD & TC has a UXT 15 ther

-

mostatic valve). It is adjustable from 45-75°C. Preset 

at 55°C. The UX/UXT has an integrated stop valve 

for use when servicing the water heater. 

Connections

 

ø15 mm. cold and hot water pipes are inserted into 

the appropriate connection on the mixing valve as 

shown. Then tighten nut.

For RI SD pipes approved for the appropriate temp. 

must be fitted.

Temperature adjustment

The water temperature from the water heater to the 

taps is adjusted using knob A. 

Start by turning A fully counter-clockwise. Then ad

-

just to requested temperature according to the dia

-

gramme shown by turning A clockwise. 

 

Hw

Cw

ø15 mm pipe

Copper or PEX

with approved fitting

Nut

Olive

Thread

mixing

 

valve

Valves - Spare parts

RG 5/4”

SV2

UX 15

TPR 15

TS2

1

3

2

4

RESET

1

2

KN 5/4”

O-ring

R

D

K

Overflow 3/4” int. thread

Overflow 1/2” 

thread or ø15 mm 

compression fitting

SV

P&T

30

35

40

45

50

55

60

65

70

75

80

85

0

 

1/4

 

1/2

 

3/4

 

Mixed 

te

mp

er

atu

re

 [°C]

 

Turns clockwise

Cold water 

temperature: 8-10°C

 

UX

  &  UXT

65°C

75°C

Thermostat

setting:

85°C

Packing box

Summary of Contents for RI HP 200

Page 1: ...Installasjon vedlikehold og servicemanual s 2 Installation maintenance and service manual p 8 Installation uppehåll och servicemanual s 14 OSO Ecoline RI 145028 04 8 2014 MADE IN NORWAY NO SE EN ...

Page 2: ...er tappekap for 200 300 l lik std Super S hhv 120 200 l Twin Coil RI TC 100 200 300 for lav og høytemp energikilde RI TC har twin coil og er designet for oppv av forbruksvann fra to eksterne varmekilder el backup Skumisolert med ECO Foam ISO 3582 sertifisert El element 5 4 3kW 230V 1 fas m termostat 60 90 C krever fast el tilkobling 2 stk følerlommer medfølger Kan monteres mellom coilanslutningene...

Page 3: ...20 mm 0 40 mm 1 4 avt drain 200 300 l 115 mm 3 4 Coil ret 200 300 l 220 mm 1 2 Sensor 200 l 565 mm 300 l 690 mm 1 2 P T 200 300 l 415 mm 1 2 Sensor 200 300 l 335 mm H 200 l 1130 mm 300 l 1580 mm Vv Kv Hw Cw 200 l 1210 mm 300 l 1660 mm 3 4 Coil tur flow 200 300 l 445 mm 0 40 mm SV safety valve 100 l 80 mm 200 300 l 110 mm 3 4 Coil ret 100 l 180 mm 200 300 l 220 mm 3 4 Coil tur flow 100 l 520 mm 200...

Page 4: ...d Tømmes med 1 4 tømmeplugg nede i front Advarsel Sikkerhetsventiler må IKKE fjernes eller plugges Om overløpsrør R monteres min innv ø18 mm skal dette legges med fall uavstengbart og frostfritt til sluk Ventilens funksjon kontrolleres årlig første gang etter ca 3 måneders drift ved å åpne ventilen og sjekke at vannet renner fritt til avløp Blandeventil Ecoline serien er utstyrt med en OSO UX15 me...

Page 5: ...Internledninger Alle interne ledninger er ferdig koblet fra fabrikk 2 5 mm ledning er standard RI SD leveres med en standard el tilførselskabel med plugg for jordet stikkontakt NB I Norge skal berederen monteres i henhold til NEK 400 Dette krever fast el tilførsel ved 2 kW eller mer v nyinstallasjon Skal utføres av autorisert elektriker Varmeelement RG 5 4 Elementet motstår opptil 250 mg Cl l Et R...

Page 6: ...en muligens byttes Noe drypp en periode bygges trykk opp som er normalt Alternativt kan et ekspan fører til at sikkerhetsventilen åpner sjonskar monteres Varmeelementet er ikke tiltrukket godt Kontrollér elementets o ringstetning Drypp fra varselhull nede i front nok eller det har blitt en lekkasje i og sjekk trekk til alle rørkoblinger en anslutning eller trykktanken Andre problemer eller hvis de...

Page 7: ... korrekt Trekk elementet godt til H Åpne blandeventilen 1 med rattet A og kontrollér at elementet er tett I Sett ledningene tilbake på elementet trekk koblingene godt til J Montér elboks lokket før strømtilførselen kobles på 8 K Justér blandeventilen til den ønskede temperatur se diagram på side 4 ved å stille inn ratt A A Bytte av termostat a Koble fra strømtilførselen 8 b Demontér elboks lokket ...

Page 8: ...ween coil connections and above the element One sensor pocket is supplied with unit UXT15 mixing valve w built in stop cock supplied with unit Adj able 45 80 C P T valve 9 bar 90 95 C is factory fitted Power cable 3 m factory fitted Without solar the draw off cap is comparable to a std 120 200 l water heater Twin Coil RI TC 100 200 300 for low and high temp energy source RI TC has twin coils and i...

Page 9: ...Coil ret 100 l 180 mm 200 300 l 220 mm 3 4 Coil tur flow 100 l 520 mm 200 300 l 450 mm 1 2 Sensor 100 300 l 340 mm 1 2 Sensor 100 l 770 mm 200 l 690 mm 300 l 790 mm H 100 200 l 1130 mm 300 l 1580 mm Vv Kv Hw Cw 100 200 l 1210 mm 300 l 1660 mm 3 4 Coil 100 l 940 mm 200 l 830 mm 300 l 930 mm 3 4 Coil 100 l 600 mm 200 l 550 mm 300 l 650 mm Installation connection measurements Installation OSO Ecoline...

Page 10: ...e The valve must have a free flowing non closeable 3 4 min internal diameter 18 mm out let to a visible and frost free drain gully The safety valve should be operated annually first time after approx 3 months to ensure the water is free flow ing see Safety valve above Mixing valve The Ecoline series is fitted with an OSO UX 15 me chanic mixing valve RI SD TC has a UXT 15 ther mostatic valve It is ...

Page 11: ...orce at the date of installation and provided that 1 The water quality shall be in accordance with European Council Directive 98 83 EC or revised version at the date of installation and is not fed with water from a private supply Particular Chloride content Max 250 mg l Sulphate content Max 250 mg l Combination Chloride sulphate Max 300 mg l in total 2 The OSO cylinder is filled with water before ...

Page 12: ...need to be replaced Some dripping a period of time pressure builds up is normal Alternatively an expansion causing the safety valve to open vessel can be fitted The heating element may not be Check the heating element o ring seal Leak warning outlet is dripping properly tightened or there may be and all connections a leak Other problems or if none of the Contact the installer supplier regarding ab...

Page 13: ...e O ring is placed in its correct position Tighten element H Open mixing valve 1 using knob A and check the element connection for leaks I Refit the wires to the element in their correct positions tighten properly J Refit the electric box lid and reconnect the power cable 8 K Adjust the mixing valve to the preferred temperature setting see page 10 using knob A A Replacing the thermostat a Disconne...

Page 14: ...monterad Nätkabel 3 m med jordad plugg fabriksmonterad Utan solvärme är kap för 200 300 l lik std Super S resp 120 200 l Twin Coil RI TC 100 200 300 för lav och högtemp energikälla RI TC har twin coil och är designad för uppv av varmvatten från två eksterna värmekällor el backup Skumisolerad med ECO Foam ISO 3582 sertifierad El element 5 4 3kW 400V 2 fas m termostat 60 90 C direkt eltilkoppling kr...

Page 15: ...l 820 mm 0 40 mm 1 4 avt drain 200 300 l 115 mm 3 4 Coil ret 200 300 l 220 mm 1 2 Sensor 200 l 565 mm 300 l 690 mm 1 2 P T 200 300 l 415 mm 1 2 Sensor 200 300 l 335 mm H 200 l 1130 mm 300 l 1580 mm Vv Kv Hw Cw 200 l 1210 mm 300 l 1660 mm 3 4 Coil tur flow 200 300 l 445 mm 0 40 mm SV safety valve 100 l 80 mm 200 300 l 110 mm 3 4 Coil ret 100 l 180 mm 200 300 l 220 mm 3 4 Coil tur flow 100 l 520 mm ...

Page 16: ...ms med 1 4 avt plugg nere i fronten Varning Säkerhetsventiler måste INTE fjärnas eller plug gas Om överloppsrör R monteras min innv ø18 mm ska detta dras med hällning oavstengbart och frostfritt till golvbrunn Ventilens funktion kontrolle ras årlig första gång efter ca 3 mån drift genom att öppna ventilen och kontrollera att vattnet rinner ohindrad till avloppet Blandningsventil Ecoline serien är ...

Page 17: ...erederen Det anbefales derfor en lägsta temperaturinställning på 65 C Termo staten är fabriksinställd på 75 C Återställningsbrytare finns placerad längst upp på TS2 termostaten Brytaren vill utlösas och bryta all el tillförsel till elementen om vattentemperaturen stiger till 98 C Om detta inträffer måste termostaten kontrolleras av auktoriserad personell före återställningsbrytaren intrycks Intern...

Page 18: ...n möjligen bytas en period byggs tryck upp som Något dropp är normalt Alternativt kan leder till at säkerhetsventilen öppnar et expantionskarl monteras Värmeelementet är inte gott nog åter Kontrollera elementens o ringstätning Droppande från varselhål nere i front draget eller det har uppstått en leckage och kontrollera dra åt alle rørkopplingar i en anslutning eller i trycktanken Övriga problem e...

Page 19: ...d hög kraft H Öppna blandningsventilen 1 med ratten A och kontrollera att elementen är tät I Koppla tillbaka ledningarna på elementen dra åt kopplingarna med hög kraft J Montera elcentral locket innan el tillförseln kopplas på 8 K Justera blandningsventilen till önskad temperatur se diagram på s 16 genom att ställa in med ratten A A Byte av termostat a Koppla från eltillförseln 8 b Demontera elcen...

Page 20: ... world class manufacturing with environmentally friendly ideals Email export osohotwater com Web www osohotwater com Tel 47 32250000 Fax 47 32250090 OSO Hotwater AS Industriveien 1 Postboks 112 3300 Hokksund Norway ...

Reviews: