Volta Pellet Stove Installation and Operation Manual
__________________________________________________________________________________________________ 17
3.6
FLOOR PROTECTION
For floor protection clearances refer to the following table.
FLOOR PROTECTION
LETTER
CANADA
USA
E
18″ (460 mm)
6″ (155 mm)
F
N/A (USA only)
6″ (155 mm)
G
8″ (205 mm)
N/A (Canada only)
H
8″ (205 mm)
N/A (Canada only)
CAUTION: THE STOVE MUST BE PLACED ON A CONTINUOUS (GROUTED JOINTS) NONCOMBUSTIBLE
MATERIAL SUCH AS CERAMIC TILE*, CEMENT BOARD, BRICK, MILLBOARD OR EQUIVALENT, OR ANY
OTHER APPROVED OR LISTED MATERIAL SUITED FOR FLOOR PROTECTION.
*Any type of tile will require a continuous non combustible sheet beneath to prevent the possibility of
embers falling through to the combustible floor if cracks or separation should occur in the finished
surface, this would include floor protection for built-in raised hearths. Check local codes for approved
alternatives.
4
VENTING SYSTEM
4.1
GENERAL
Even though the chimney draft is mechanical, a suitable venting system will ensure a natural draft
which will prevent smoke spillage in your home if a power outage occurs. Moreover, a suitable
venting system configuration will help getting the best efficiency out of your stove when installed in
accordance with the required EVL (see
Section 4.3
Equivalent Vent Length (EVL)
).
Even the best stove will not function safely and efficiently as intended if it is not connected to a
suitable venting system.
4.2
RECOMMENDATIONS
In Canada, we recommend that you use a listed pellet vent that meets the CAN/ULC S609 or ULC/ORD
C441 Standard. A pellet vent listed to ULC S629M is also suitable for installation with this stove.
For the United States, we recommend that you use a listed pellet vent that meets the UL 641
Standard. A pellet vent listed to UL 103 is also suitable for installation with this stove.
This stove can be vented in an existing factory-built or masonry chimney with the addition of a
stainless steel liner, provided the chimney is more than 4” in diameter. The liner should be listed and
should meet the ULC S635 or CAN/ULC S640 standard in Canada and the UL 1777 standard in the
USA. Refer to the instructions provided by the vent manufacturer, especially when passing through a
wall, ceiling or roof.