OSAKA

 - OF 33 AZ - OPERATING INSTRUCTIONS - Vr. 01 - PAG. 10

 

49 

dAL

  Temperature 

Alarms 

Differential 

0 ÷ 30 

°C/°F 

2.0 

50 

ALd

  Temperature Alarms 

delay 

OFF ÷ 99.59 

min.sec 

OFF 

51 

tAL

  Alarm memory 

no - yES 

no 

52 

PAL

  Temperature 

Alarms 

delay at power on 

OFF ÷ 99.59  

hrs.min 

2.00 

53 

dALd

  Temperature 

Alarms 

delay  and  unlock  display 
delay after defrost  

OFF ÷ 99.59 

hrs.min 

1.00 

54 

dALc

  Temperature 

alarms 

delay    after  continuous 
cycle 

OFF ÷ 99.59 

hrs.min 

OFF 

55 

oAd

  Alarm  delay  with  open 

door 

OFF ÷ 99.59 

min.sec 

OFF 

 
Group 

]

din 

(parameters relative to digital input) 

Par.

 

Description

 

Range

 

Def.

 

56 

diF

 

Function  and  function 
logic  of digital input: 
0 = No function 
1= Start defrost 
2= End defrost 
3= Continuous cycle 
4= External alarm 
5=  Door  open  with  fan 
block  
6=  Door  open  with  fan 
and compressor block 
7= 

Auxiliary 

output 

command 
8= Selection of active Set 
Point  
9=  External  alarm  with 
deactivation  of  control 
outputs 
10=  Switch  on/Switch  off 
(Stand-by) 

-10 / -9 / -8 / -7 
/ -6 / -5 / -4 / -3 

/ -2 / -1 / 0 / 1 / 

2 / 3 / 4 / 5 / 6 / 

7 / 8 / 9 / 10 

57 

did

 

Delay  in  acquiring  digital 
input 

OFF ÷ 99.59 

min.sec 

OFF 

 
Group 

]

AuS 

(parameters relative to auxiliary output) 

Par.

 

Description

 

Range

 

Def.

 

58 

FOA

  Function  mode  auxiliary 

output: 
0= No Function 
1= 

regulation 

output 

delayed 
2=  manual  activation  by 
key or digital input. 

0 / 1 / 2 / -1 / -

59 

tuA

  Time  relative  to  auxiliary 

output 

OFF ÷ 99.59 

min.sec 

OFF 

 
Group 

]

Out  

(parameters relative to configuration of outputs) 

Par.

 

Description

 

Range

 

Def.

 

60 

Out1

  Configuration  of  output 

function OUT1: 
OFF= No function 
Out= 

Temperature 

control (compressor) 
dEF= defrosting 
FAn= fans 
AuS= Auxiliary 
ALt= Silenceable alarm 
AL= 

Alarm 

not 

silenceable 
ALL= memorised alarm 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ -

AL/ -ALL 

Out 

61 

Out2

  Configuration  of  output 

function OUT2: 
see “Out1” 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ -

AL/ -ALL 

dEF 

62 

Out3

  Configuration  of  output 

function OUT3:  
see “Out1” 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ -

AL/ -ALL 

FAn 

63 

buF

  Configuration 

Buzzer 

function:  
see “Out1” 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ -

AL/ -ALL 

ALt 

 
Group 

]

PAn 

(parameters  relative  to  configuration  of  the 

keyboard) 

Par.

 

Description

 

Range

 

Def.

 

64 

Fbd

  Function 

mode 

key 

DOWN/AUX: 
OFF= No function 
1= 

Auxiliary 

output 

command 
2= 

Continuous 

cycle 

command 
3= Selection of active Set 
Point 
4=  Switch  on/Switch  off 
(Stand-by) 

OFF / 1 / 2 / 3 

/ 4 

OFF 

65 

USrb

  Function  mode  key  U: 

see “Fbd” 

OFF / 1 / 2 / 3 

/ 4 

OFF 

66 

PASS

  Access 

Password 

to 

parameter functions  

OFF ÷ 9999 

OFF 

 
Group 

]

CLO 

(parameters relative to the internal clock) 

Par.

 

Description

 

Range

 

Def.

 

67 

StCL

  Current time 

0.00 ÷ 23.59  

hrs.min 

0.00 

68 

CLOF

  Daily calibration of clock 

-20 ÷ 20 

sec 

 
 

6 - PROBLEMS, MAINTENANCE AND GUARANTEE

 

 
6.1 - SIGNALLING 
Error Signalling: 

 

Error

 

Reason

 

Action 

 

E1 

-E1

 

The  probe  Pr1  may  be 
interrupted  or  in  short 
circuit,  or  may  measure  a 
value  outside  the  range 
allowed 

Check 

the 

correct 

connection 

of 

the 

probe 

with 

the 

instrument  and  check 
the 

probe 

works 

correctly 

E2 

-E2

 

The  probe  Pr2  may  be 
interrupted  or  in  short 
circuit,  or  may  measure  a 
value  outside  the  range 
allowed 

EEPr

 

Internal memory error 

Check 

and 

if 

necessary 

re-

programme 

the 

parameters function. 

 
In  Cell  probe  error  status,  the  output  OUT  behaves  as  set  by 
the parameters “tonE” and “toFE”. 

Other Signalling:

 

Message

 

Reason

 

od

 

Delay in switching on in progress 

dEF

 

Defrosting in progress with  “dLo”=Lb 

PdEF

 

Post-

defrosting in progress with “dLo”=Lb 

CC

 

Continuous cycle in progress 

HI

 

Maximum temperature alarm in progress 

LO

 

Minimum temperature alarm in progress 

AL

 

Digital input alarm in progress 

AP

 

Door open  

 

Summary of Contents for OF 33 AZ

Page 1: ...5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7 1 ELECTRICAL DATA 7 2 MECHANICAL DATA 7 3 MECHANICAL DIMEN...

Page 2: ...e desired parameter can be selected and pressing the Set key the display will alternately show the parameter code and its setting that can be changed with the UP and DOWN keys Once the desired value h...

Page 3: ...lectronic devices or electromechanical safety and warning system They should be placed outside the measuring and control equipments possible protective devices responding to specific safety requiremen...

Page 4: ...y function through a contact that is normally open and closed when the alarm sounds ALt to control a silenceable alarm device through a contact that is normally closed and then open when the alarm sou...

Page 5: ...abled in WITH HOT GAS or INVERSION OF CYCLE during defrosting the outputs Out and dEF are enabled The automatic defrosting can take place at intervals or if the instrument has an internal clock at set...

Page 6: ...d When the probe Pr2 is used par Pr 2 on the fans as well as being conditioned by the parameters FCOF and FEdF are also conditioned by the temperature control It is possible to set the disablement of...

Page 7: ...zer with an alarm memory ALL or ALL it is necessary to set the parameter tAL yES 4 10 DIGITAL INPUT All the parameters concerning the digital input functions are contained in the group din The digital...

Page 8: ...the second is disabled In this mode the AUX output can be turned off automatically after a certain time that can be set on the parameter tuA With tuA OFF the output is activated and deactivated only...

Page 9: ...frost 2 OFF 00 00 23 59 hrs min OFF 23 dF 3 Time start defrost 3 OFF 00 00 23 59 hrs min OFF 24 dF 4 Time start defrost 4 OFF 00 00 23 59 hrs min OFF 25 dF 5 Time start defrost 5 OFF 00 00 23 59 hrs m...

Page 10: ...dEF FAn AuS ALt AL ALL ALt AL ALL Out 61 Out2 Configuration of output function OUT2 see Out1 OFF Out dEF FAn AuS ALt AL ALL ALt AL ALL dEF 62 Out3 Configuration of output function OUT3 see Out1 OFF Ou...

Page 11: ...250 VAC and OUT3 SPST NO 5A AC1 2A AC3 250 VAC 16 A Max for common pin 1 Electrical life for relay outputs 100000 operat VDE om Installation category II Measurement category I Protection class against...

Reviews: