background image

OSAKA

 - OF 33 AZ - OPERATING INSTRUCTIONS - Vr. 01 - PAG. 8

 

=  -4

  -  External  alarm  signal  with  contact  normally  closed  : 

similar to “diF”=4 but with function logic reversed. 

=  -5

  -  Cell  door  opening  with  fan  block  with  contact  normally 

closed : similar to “diF”=5 but with function logic reversed 

=  -6

  -  Cell  door  opening  with  compressor  and  fan  block  with 

contact  normally  closed  :  similar  to  “diF”=6  but  with  function 
logic reversed. 

=  -7

  -  Remote  control  of  auxiliary  output  AUX  with  contact 

normally  closed  :  similar  to  “diF”=7  but  with  function  logic 
reversed. 

= -8

 - Selecting the active set point with contact normally closed 

: similar to “diF”=8 but with function logic reversed. 

=  -9

  -  Signalling  of  external  alarm  with  disablement  of  all  the 

outputs with contact normally closed : si

milar to “diF”=9 but with 

function logic reversed 

=  -10

  -  Switching  on/off  (Stand-by)  of  instrument:  similar  to 

“diF”=10 but with function logic reversed. 
 

4.11 - AUXILIARY OUTPUT 

All the parameters concerning the auxiliary output functions are 
contained in the group 

]

AuS”.

 

The auxiliary outpurt can be configured to operate on any of the 
outputs by programming the parameter of the desired output = 
AuS. 
The  function  carried  out  is  defined  by  the  parameter 

“FOA”

 

and  the  function  is  conditioned  by  the  time  set  in  parameter 

“tuA”.

 

The  parameter  “FOA”  can  be  configured  for  the  following 
functions: 

= 0

  - Auxiliary output not active 

= 1

 - Regulation output delayed with contact normally open: the 

auxiliary  output  is  activated  with  delay  that  can  be  set  on  the 
parameter "tuA" compared to the output configured as Out. The 
output is then turned off at the same time as the OUT output is 
disabled. This function mode can be used as a command for a 
second compressor or for all other working utilities according to 
the  same  OUT  output  conditions,  but  which  must  be  delayed 
after  the  start  up  of  the  compressor  to  avoid  excess  electricity 
absorption. 

=  2

  -  Activation  by  front  key  (U  or  DOWN/AUX)  or  by  digital 

input  with  contact  normally  open:  the  output  is  activated  by 
pressing 

the keys F or DOWN/AUX suitably configured (“USrb” 

or  “Fbd”  =  1)  or  via  activation  of  the  digital  input  if  suitably 
configured  (“diF”=7).  These  commands  have  a  bi-stable 
function,  Which  means  that  when  first  pressed,  the output key 
is activated while the second is disabled. In this mode, the AUX 
output  can  be  turned  off  automatically  after  a  certain  time  that 
can be set on the parameter "tuA". With "tuA" = OFF the output 
is activated and deactivated only manually, using the front key 
(U  or  DOWN/AUX)  or  via  the  digital  input.  Differently,  the 
output,  once  activated,  is  turned  off  automatically  after  the  set 
time.  This  function  can  be  used,  for  example,  as  a  cell  light 
command, for non-misting resistance or other utilities . 

=  -1

  -  Delayed  regulation  output  with  contact  normally  closed: 

similar to “FOA”=1 but with function logic reversed. 

=  -2

  -  Activation  by  front  key    (U  or  DOWN/AUX)  or  by  digital 

input with contact normally closed: similar to “FOA”=2 but with 
function logic reversed. 
 

4.12 - FUNCTIONING OF 

KEYS “F” AND “DOWN/AUX”

 

Two  of  the  instrument  keys,  in  addition  to  their  normal 
functions, can be configured to operate other commands. 
The  F  key  function  can  be  defined  by  the  parameter 

“USrb”

 

while  the  DOWN/AUX  key  function  can  be  defined  by  the 
parameter

 

“Fbd”

 both contained in the group 

]

PAn”. 

Both  the  parameters  have  the  same  possibilities  and  can  be 
configured for the following functions: 

= 0

 - The key carries out no function. 

=  1

  -  Pressing  the  key  for  at  least  1  second,  it  is  possible  to 

enable/dis

able the auxiliary output if configured (“FOA”=2). 

=  2

  -  Pressing  the  key  for  at  least  1  second,  it  is  possible  to 

enable/disable  a  continuous  cycle  (see  continuous  cycle 
function). 

=  3

  -  Pressing  the  key  for  at  least  1  second,  it  is  possible  to 

select  one  of  the  2  memorised  set  point  in  rotation.  Once 
selection  has  been  made,  the  display  will  flash  the  active  set 
point code for about 1 sec. (SP 1or SP 2). 

=  4

  -  Pressing  the  key  for  at  least  1  second,  it  is  possible  to 

switch  the  instrument  from  the  ON  status  to  Stand-by  status 
and vice versa. 
 

4.13 - KEY USB + OSAKA SETUP: KEY PROGRAMMING

 

Extracting  the  box  you  have  access  to  a  white  connector  that 
allows easy programming with programming key 5 pin. This key 
allows repetitive schedules and save the settings in a practical 
and simple.  
There are 2 types of Key, the key enabling USB connection pc 
and  save  the  different  configurations  and  set  parameters  and 
Manual Key 5 pin only for connecting thermostats.  
 
An  advantage  and  recommendation  is  the  use  of  the  supplied 
power supply KEY without connecting the 

F 100 / TSF 100 / M1

 

to power. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

S U P P L Y

S U P P L Y  A D A P T E R

1 2  V D C

A C  S U P P L Y  

S U P P L Y  A D A P T E R

1 2  V D C

A C  S U P P L Y  

U S B

Summary of Contents for OF 33 AZ

Page 1: ...5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7 1 ELECTRICAL DATA 7 2 MECHANICAL DATA 7 3 MECHANICAL DIMEN...

Page 2: ...e desired parameter can be selected and pressing the Set key the display will alternately show the parameter code and its setting that can be changed with the UP and DOWN keys Once the desired value h...

Page 3: ...lectronic devices or electromechanical safety and warning system They should be placed outside the measuring and control equipments possible protective devices responding to specific safety requiremen...

Page 4: ...y function through a contact that is normally open and closed when the alarm sounds ALt to control a silenceable alarm device through a contact that is normally closed and then open when the alarm sou...

Page 5: ...abled in WITH HOT GAS or INVERSION OF CYCLE during defrosting the outputs Out and dEF are enabled The automatic defrosting can take place at intervals or if the instrument has an internal clock at set...

Page 6: ...d When the probe Pr2 is used par Pr 2 on the fans as well as being conditioned by the parameters FCOF and FEdF are also conditioned by the temperature control It is possible to set the disablement of...

Page 7: ...zer with an alarm memory ALL or ALL it is necessary to set the parameter tAL yES 4 10 DIGITAL INPUT All the parameters concerning the digital input functions are contained in the group din The digital...

Page 8: ...the second is disabled In this mode the AUX output can be turned off automatically after a certain time that can be set on the parameter tuA With tuA OFF the output is activated and deactivated only...

Page 9: ...frost 2 OFF 00 00 23 59 hrs min OFF 23 dF 3 Time start defrost 3 OFF 00 00 23 59 hrs min OFF 24 dF 4 Time start defrost 4 OFF 00 00 23 59 hrs min OFF 25 dF 5 Time start defrost 5 OFF 00 00 23 59 hrs m...

Page 10: ...dEF FAn AuS ALt AL ALL ALt AL ALL Out 61 Out2 Configuration of output function OUT2 see Out1 OFF Out dEF FAn AuS ALt AL ALL ALt AL ALL dEF 62 Out3 Configuration of output function OUT3 see Out1 OFF Ou...

Page 11: ...250 VAC and OUT3 SPST NO 5A AC1 2A AC3 250 VAC 16 A Max for common pin 1 Electrical life for relay outputs 100000 operat VDE om Installation category II Measurement category I Protection class against...

Reviews: