FREEZE PROTECTION OF THE HEAT RECOVERY CORE

Ventilators

MODEL

 

ODD-ERV-80 | ODD-ERV-120

Instruction Manual

1-888-543-6473
1-888-541-6474

13376 Comber Way 

Surrey BC V3W 5V9

[email protected] 
www.ortechindustries.com

375 Admiral Blvd

 

Missis

s

auga

ON L5T 2N1

The freeze protection function prevents freezing of the heat 
recovery core in the cold season. This function is activated 
automatically and cannot be turned off. The ventilation unit 
periodically switches from rated operation mode to the special 
defrost mode (the extract fan runs in high speed, the supply fan is 
off) and vice versa according to the signaling from the outdoor 
temperature sensor. The temperature conditions for this mode are 
described in the table on the left.

START-UP AND CHECK OUT PROCEDURE

Make sure power is disconnect by unplugging 
electrical cord

Check field-supplied control wiring to insure proper 
installation and that all connection are tight

Check field-supplied power supply for proper voltage

Make sure that unit is securely mounted or 
suspended and that there are no tools or loose debris 
in, around or on top of the unit

Check all duct connection to insure they are sealed

Check all duct outlets. All outlets MUST be open

Check unit filters

Close unit door

Make sure that the intake hood is positioned away 
from any exhausts or other sources of pollutants. The 
quality of the introduced fresh air is the most 
important function of this system

Instruct end user on proper operation procedures 
and leave use and care manual with them

TROUBLESHOOTING

Use the guide below to help find and correct system faults and then contact technical support 
before replacing the unit or components or for additional troubleshooting. 