background image

Instruction Manual

1-888-543-6473
1-888-541-6474

13376 Comber Way 

Surrey BC V3W 5V9

[email protected] 
www.ortechindustries.com

375 Admiral Blvd

 

Missis

s

auga

ON L5T 2N1

Line vs. Load

A cable consists of 2 or 3 wires

INSTALLATION GUIDE

L

INE Cable

Delivers power from the service panel (breaker 
panel or fuse box) to the GFCI. If there is only 
one cable entering the electric box, it is the 
LINE cable. This cable should be connected to 
the GFCI's LINE terminals ONLY.

LOAD Cable

Delivers power from the GFCI to another 
receptacles in the circuit. This cable should be 
connected to the GFCI's LOAD terminals only. 
The LOAD terminals are under the yellow 
sticker. DO NOT remove the sticker at this time.

Turn the Power OFF

Plug an electrical device, such as a lamp or radio, into the receptacle on which you are 

working. Turn the lamp or radio ON. Then, go to the service panel. Find the breaker or 

fuse that protects that receptacle. Place the breaker in the OFF position or completely 

remove the fuse. The lamp or radio should turn OFF.
Next, plug in and turn ON the lamp or radio at the receptacle's other outlet to make sure 

the power is OFF at both outlets. If the power is not OFF, stop work and call an electrician 

to complete the installation.

Identify Cables / Wires

IMPORTANT
DO NOT install the GFCI receptacle in an electrical box containing (a) more than 4 wires 
(not including the grounding wires) or (b) cables with more than two wires (not including 
the grounding wire). Contact a qualified electrician if either (a) or (b) is true.

If you are replacing an old receptacle, pull it out of 
the electrical box without disconnecting the wires

If you see one cable (2-3 wires), it is the LINE cable. 
The receptacle is probably in position C (see diagram 
below). Remove the receptacle and go to step 
"Connecting the Wires A

"

)

If you see two cables (4-6 wires), the receptacle is 
probably in position A or B (see the diagram below) 

Procedure: Box with Two Cables

 

(4-6 wires)

a)

Detach one cable's white and hot wires

 

from the 

receptacle and cap each one separately with a 

wire connector.

 

Make sure that they are from the 

same

 

cable

b)

Re-install the receptacle in the electrical

 

box, 

attach the faceplate, then turn the

 

power ON at 

the service panel

c)

Determine if power is flowing to the

 

receptacle. If 

so, the capped wires are

 

the LOAD wires. If not, 

the capped wires

 

are the LINE wires

d)

Turn the power OFF at the service panel, and 

label the LINE and LOAD wires. 

Then, remove the receptacle

e)

Go to step "Connecting the wires B"

Placement in Circuit

The GFCI's place in the circuit 
determines if it protects other 
receptacles in the circuit.

Placing the GFCI in position A will 
also provide protection to "load 
side" receptacles B and C. On the 
other hand, placing the GFCI in 
position C will not provide 
protection to receptacles A or B. 
Remember that receptacles A, B 
and C can be different rooms.

Connecting the Wires (choose A or B):

 A — One Cable (2-3 wires) Entering the Box

Connect the LINE cable wires to the LINE terminals:

The WHITE wire connects to the WHITE terminal (Silver)

The BLACK wire connects to the HOT terminal (Brass)

Connect the grounding wire (only if there is a grounding wire):

For a box with no grounding terminal, connect the LINE cable's bare copper (or
GREEN) wire directly to the grounding terminal on the GFCI receptacle

For a box with a grounding terminal, connect a 6" bare copper (or GREEN) 12 or
14AWG wire to the grounding terminal on the GFCI. Also, connect a similar wire
to the grounding terminal on the box. Connect the ends of these wires to the
LINE cable's bare copper (or GREEN) wire using a wire connector. If these wires
are already in place, check the connections.

Receptacles

MODEL

 

MH

20

-ST

Complete the installation:

Fold the wires into the box, keeping the 
grounding wire away from the WHITE and HOT 
terminals. Screw the receptacle to the box and 
attach the faceplate

Go to the next step "Test Your 
Work" (explained on the 

last

 page of this 

instruction manual)

Summary of Contents for MH20-ST

Page 1: ...l electrical codes 2 A GFCI receptacle does NOT protect against circuit overload short circuits or shocks 3 In the event of a ground fault a GFCI will trip and quickly stop the flow of electricity to prevent serious injury 4 You can still be shocked if you touch bare wires while standing on a non conducting surface such as an wooden floor 5 For installation in wet locations protect the GFCI recept...

Page 2: ...tion A or B see the diagram below Procedure Box with Two Cables 4 6 wires a Detach one cable s white and hot wires from the receptacle and cap each one separately with a wire connector Make sure that they are from the same cable b Re install the receptacle in the electrical box attach the faceplate then turn the power ON at the service panel c Determine if power is flowing to the receptacle If so ...

Page 3: ...e WHITE wire connects to the WHITE terminal Silver The BLACK wire connects to the HOT terminal Brass Connect the grounding wires only if there is a grounding wire Connect a 6 bare copper or GREEN 12 or 14AWG wire to the grounding terminal on the GFCI If the box has a grounding terminal also connect a similar wire to the grounding terminal on the box Connect the ends of these wires to the LINE and ...

Page 4: ...red and powered the red LED d will flash one time within 5 sec and the internal self testing circuit d will launch every 1 10 min When the GFCI displays an alarm during d its operation the red light will turn ON immediately and it will no d longer provide a ground fault circuit protection reminding the user d that the GFCI is end of life and MUST be replaced e Press the TEST button then RESET butt...

Reviews: