IG-284-EN version 03; 06/05/2020
7
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
General description
1.3.3. Base
Made up of the cable compartment and the gas relief
compartment:
Cable compartment
This is located in the bottom front section of the cubicle
and has a cover interlocked with the earthing switch, thus
allowing front access to the medium-voltage cables.
As
standard
, it is designed to contain up to:
• Two shielded screw-in terminals (reduced) per phase
or one terminal (reduced) plus surge arrester (reduced)
with space for the corresponding incoming power
cables.
• Cable ties for the power cables.
• Earthing bars.
As an
option
:
• Two symmetric terminals or symmetric terminal plus
symmetric surge arrester.
• Metallic voltage transformers.
Figure 1.3.
Cable compartment
Gas relief compartment
Ormazabal
's
cgm
.800 is designed and constructed to
withstand at least the thermal and dynamic eff ects of an arc
of 16 kA for 0.5 seconds should a defect result in an internal
arc in the gas compartment. The system conducts the gases
generated in a fully controlled manner to avoid any possible
injury to people in the equipment operation area.
Optionally
, a chimney can be positioned in the rear
of the cubicle to redirect the gases to the top section.
Please check with
Ormazabal
.