8.
Close the cover and check that all the strikers have been
reset.
Figure 7.51.
Closing the fuse holder
9.
Place the fuse and cable compartment access cover
(a) by pushing it downward and ensuring it is locked
on the cubicle, taking into account that the fuse status
indicator (b) is green.
Figure 7.52.
Closing cable and fuse compartment cover
10.
Start up the cubicle following the instructions set out in
these General Instructions document.
IG-196-US version 03; 13/04/2021
49
General instructions
cpg
.0 NEW MODEL: Medium-voltage
metal-enclosed switchgear with full insulation in gas,
up to 38 kV in accordance with IEEE Standards
Operation and commissioning sequence