7.2. Vacuum interrupter function operation sequence (cpg
.0-v
)
For cubicles of type:
•
cpg
.0-v up to 38 kV/ up to 1200 A/25 kA
The lever for the manual charging of the
aforementioned VACUUM INTERRUPTER closing
springs is identified by the hexagonal cavity in the end.
Figure 7.8.
Details of the vacuum interrupter manual spring charging lever
Connection
Figure 7.9.
Starting position of the
cpg
.
0-v
busbar disconnector
Insert the lever in the busbar disconnector driving shaft
Then turn 90° CLOCKWISE. Check that the disconnector
status indicator shows closed.
Figure 7.10.
Busbar disconnector connection sequence
IG-196-US version 03; 13/04/2021
30
Operation and commissioning sequence
General instructions
cpg
.0 NEW MODEL: Medium-voltage
metal-enclosed switchgear with full insulation in gas,
up to 38 kV in accordance with IEEE Standards
Summary of Contents for cpg.0-c