9
ATTENTION!
Blow through function is activated when the boiler reaches the set temperature.
ATTENTION!
Blow through will not activate when:
1. The temperature on the sensor will be
10 °C
higher than the temperature set for the boiler.
2. The temperature will be lower than set by the “HI” parameter.
ATTENTION!
Setting the operation time for 0 will turn off the blow through function
fan pause - stoking
Parameter setting the fan pause time necessary for stoking the boiler. Time range: 0:30 to 9:30
minutes.
4.5. Service mode - LANgUAge
Service mode is for setting the language of the control panel. To enter the LANGUAGE service
mode press for a few second until WORK PARAM. shows on the display. Choose the language
(Polish/English/German) using button.