1.  Introduction 

The OriLink® TCM module, (

T

ank

 C

ontrol

 M

odule), is used to control pumps and/or measure levels in tanks using 

floater based level switches. A TCM can be used both for fresh and waste oil tanks. 

 

The TCM (23408) is eighter a MPDM (23400) with another software (early model the chip should be labeled TCM 
1.xx.xx) or has the PCB 203 02 91 equipped with a chip marked TCM 2.xx.xx.. Because of this a lot of this manual is 
similar to the manual of the MPDM. 

NOTE!  

The Orilink® installation manual should be available when installing and configuring a TCM. 

2.  Mechanical installation 

The TCM is delivered mounted in a metal box with power supply. It can also be delivered as a PCB with mounting kit. 

 

Complete TCM in a box is mounted on a wall or other suitable place using the four-ø5 mm holes in the bottom corners 
of the box. 

 

If a PCB is used it is important that a power supply with enough performance is used. 

3.  Electric installation 

The power supply should be connected to mains 
230VAC in a proper way following valid rules. 
 
Alentec & Orion AB recommends that the 
connection be done through a 2-pole working 
switch. 
 
 
 
 
 
 
 

It has five connectors 

(A)

 for the OriLink® communication. Two of these connectors, 

MPDM IN 

and

 MPDM OUT

 

are not connected to 

+24V

 and are intended for a connection to another TCM, MPDM or other modules that already 

have +24VDC. This is to prevent conn24VDC from two power supplies.  

The other three connectors are used to connect external devices without a power source such as a Printer Module (PM), 
a LED Module (LED) and/or a KeyPad (KP). These connectors can only supply power to a single device. For more 
detailed information see the 

OriLink® Manual

 

NOTE! If the communication loop begin in one of these modules it must be connected to either MPDM IN or 

MPDM OUT or +24V must not be connected. 

The RESET-button 

(B)

 can be used to reset the module or reset the module address. Power supply is connected to the 

connector 

(C)

.  

NOTE! 

Check polarity, GND is closest to the hole! 

The connector 

(D)

 is used when you install a chassis-mounted key switch and diode. 

With the key switch you can set the status of the module to OFF-, NORMAL-, or 
OVERRIDE-mode. The diodes indicate setting. 

There are four connectors 

(E)

 24 V, OC, A, B and GND, one for 

each pump/tank. Solenoid valves and level sensors are connected to these 
connectors. 
“A” of a TCM port is connected to “order oil/emptying” of the level 
sensor. 
“B” of a TCM port is connected to “Stop level” of the level sensor. 
“GND” of a TCM port is connected to common of the level sensor. 
“+24V” of a TCM port is connected to one of the terminals of a solenoid 
valve and “Sol” is connected to the other. 

ALARM

Solenoid valve

STOP

+24 V

A

GND

B

Sol

Summary of Contents for OriLink 23408

Page 1: ...lish Manual for TCM module 23408 Rev R10 180409 OriLink Monitoring System Tank Control Module 23408 Covers TCM with PCB versions 203 02 62 C chip version 1 00 00 or later and 203 02 91 A chip version...

Page 2: ...reorder volume level 10 5 5 1 Set the tank stop volume level 10 5 5 2 Set tank bottom area 11 5 5 3 To configure a TCM port for a tank that does not have a constant area 11 5 6 DISPLAYING TANK CONTENT...

Page 3: ...to 24V and are intended for a connection to another TCM MPDM or other modules that already have 24VDC This is to prevent connecting 24VDC from two power supplies The other three connectors are used to...

Page 4: ...e is operational and working properly A steady light or completely off indicates a problem DIL switches for termination and BIAS are located at I J Shows the position of the replaceable communication...

Page 5: ...mediately enter set up mode from a KP and type 0 and then ENTER to get to the Main menu of the TCM see below NOTE Only one new module can be installed at a time If you press the RESET button on severa...

Page 6: ...nkNo is only for informational purpose Use correct TankNo or set all to 0 Enter menu TCM PortX by scrolling with or At PortX press ENTER Press ENTER to get the cursor Check the number of the tank that...

Page 7: ...ng the offset Offset adjusting is used to obtain 0 volume when the tank is empty If the sensor 23 417 is used a normal value is 0 080 The sign is typed on the keypad by first pressing down arrow yello...

Page 8: ...ng to 20 mA If a pressure sensor is used the value should be in bar For sensor part number 23 417 the value should be as default 0 400 Enter menu TCM PortX by scrolling with or At PortX press ENTER Sc...

Page 9: ...art number The fluid part number set in the TCM makes it possible to show the fluid part number in the info box for the graphic representation of the analogue sensor It should be set to the same value...

Page 10: ...k reorder volume level The tank reorder volume set in the TCM is used to create a true graphic representation of the analogue sensor status and start auto warning if that is enabled It should be set t...

Page 11: ...ed in the TCM Enter menu TCM PortX by scrolling with or At PortX press ENTER Scroll to SFS using or Press ENTER to get the cursor Type the sensor full scale value and press ENTER to acknowledge When t...

Page 12: ...g or Press ENTER to get the cursor Type the LED address and press ENTER to acknowledge When the cursor disappears it is finished Press EXIT two times to leave Set Up mode 5 6 2 Set LED update interval...

Page 13: ...and redundance The system must be told what hardware there is and how to use it properly This is done through the Tank Type Tank type is set by a string of 0 and 1 were the first position sets if it i...

Page 14: ...14 21 6 Menu tree...

Page 15: ...et 0X03 Where X is the port number Change Calibration 0X04 Where X is the port number Change Density of fluid 0X05 Where X is the port number Change Max volume of tank 0X06 Where X is the port number...

Page 16: ...24VDC with 10 bit A D converters Other RISC based microprocessor EEPROM 64 KB Connector E for 3 pos key switch Connector C for 24 VDC 6 3A power supply SetupLock jumper H not used Fuses T6 3A D and F...

Page 17: ...e point is open and the sensor works properly the following connection should be made The TCM port should be set to control the appropriate PC tank in relation to the physical tank Correct TankType TC...

Page 18: ...the tank module if the liquid is classed as flammable For this purpose the EX barrier 23178 and a special EX approved cable 23164 can be used The EX barrier the solenoid valve that controls the air t...

Page 19: ...for tanks with a height of 1 5 meters Max height depends on density of fluid The measuring resolution for a TCM with a 23 417 sensor is 4 mm for water and about 4 5 mm for mineral oil Connect the red...

Page 20: ...ld be set using with WinDB Manager MASK TankType 1 12 EX barrier 23 188 for analogue sensors An EX barrier is needed between the level sensor and the tank module if the liquid is classed as flammable...

Page 21: ...In a small system or at limited space it is possible to mount an additional module PCB in a TCM In this example a MPDM board is added To do this the TCM PCB has to be moved and turned one quarter of...

Reviews: