11
Installation
z
When drivers are installed in a close contact state
It is possible to install drivers closely in the horizontal direction.
In this case, install the drivers to a flat metal plate offering high heat conductivity [corresponding to
an aluminum plate of 350×350×2 mm (13.78x13.78x0.08 in.)].
[30 W, 60 W, 120 W]
•
Operating ambient temperature: 0 to +50 °C (+32 to +122 °F)
[200 W, 400 W]
•
Operating ambient temperature: 0 to +40 °C (+32 to +104 °F)
•
When using a DIN-rail or a mounting bracket, use in a state where the load factor is 90% or less.
25 mm (0.98 in.)
or mor
e
Installation method
z
Installation with screws
Install the driver through the mounting holes using two screws (M4: not included).
z
Installation to DIN rail
When installing the driver to a DIN-rail, use the DIN rail mounting plate
MADP02
(sold separately) and mount it to a
35 mm (1.38 in.) wide DIN rail. Refer to "
MADP02
handling guideline" for installation method.
z
Installation using driver mounting brackets
Use the included mounting screws to secure the mounting brackets to
the rear of the driver before installing inside the equipment.
Mounting holes for
mounting bracket
(M3, 4 locations)
Screws for mounting bracket
(M3, included)
Tightening torque: 0.5 to 0.6 N·m
(4.4 to 5.3 lb-in)
Mounting bracket
Note
•
Do not use the mounting holes of the driver mounting bracket for
any other purpose.
•
Be sure to secure the driver mounting bracket using the included
screws. The use of screws that would penetrate 3 mm (0.12 in.) or
more through the surface of the driver may cause damage to the
driver.
Dimensions
Mass: 0.8 kg (1.76 lb)
[Unit: mm (in.)]
23max.
(0.91max.)
120 (4.72)
5 (0.20)
R2.25 (0.089)
5 (0.20)
30
(1.18)
150 (5.91)
5 (0.20)
40 (1.57)
4.5 (0.18)
160 (6.30)
9.5 (0.37)
4.8 (0.19)
36.5 (1.44)
9 (0.35)
18
(0.71)
11
(0.43)
89
(3.50)
3
×
M3
Slits
Slits
Protective Earth Terminal 2
×
M4
ϕ
4.5 (
ϕ
0.177) Thru