Connection

6.10 Connecting the regeneration resistor (sold separately)

If vertical drive (gravitational operation) such as elevator applications is performed or if sudden start-stop operation 
of a large inertia is repeated frequently, use the regeneration resistor 

EPRC-400P

 (sold separately) or 

RGB100

 (sold 

separately).
Install the regeneration resistor in a location where heat dissipation capacity equivalent to a level achieved with a heat 
sink [made of aluminum, 350×350×3 mm (13.78×13.78×0.12 in.)] is ensured.
An available regeneration resistor varies depending on the output power. Refer to the USER MANUAL for details.

Note

Assign the TH input to the input terminal of CN5 when using the regeneration resistor. 

Connection method

 

Regenerative current flows through the two thick lead wires (AWG 18: 0.75 mm

2

) of the regeneration resistor. Connect 

them to the RG1 and RG2 terminals of CN1.

 

The two thin lead wires (AWG 22: 0.3 mm

2

) of the regeneration resistor are the thermostat outputs. Connect them to 

the TH input assigned to CN5 and IN-COM1.

 

Regeneration 

resistor

AWG22

TH input

IN-COM1

150 °C (302 °F)

[

N.C.

]

Connect to

 CN1

AWG18

R

RG2 terminal

RG1 terminal

Note

 

The TH input is not assigned to CN5 at the time of shipment. When using the regeneration resistor, change the “IN input 
function selection” parameter to assign the TH input. Refer to the USER MANUAL for details.

 

When the TH input is assigned to CN5, if the power consumption of the regeneration resistor exceeds the allowable 
level, the thermostat will be triggered to generate the regeneration resistor overheat alarm. If the regeneration resistor 
overheat alarm is generated, turn off the power and check the details of error.

 

When an external power supply is used for a power supply for input signals, turn on the external power supply before 
turning on the driver main power supply.

1. Assigning the TH input to CN5 

Change the “IN input function selection” parameter 
to change the assignment of input signals.  
Refer to the USER MANUAL for how to change.

2. Connecting the thermostat output to CN5 

The figure shows an example when the TH input is 
assigned to the IN8 terminal in the speed control 
mode to use the built-in power supply.  
Refer to the USER MANUAL when using an external 
power supply.

Summary of Contents for BX2 Driver Edition Series

Page 1: ...ration resistor sold separately 12 6 Connection 14 6 1 Connection example 14 6 2 Connecting the power supply CN1 15 6 3 Circuit breaker 15 6 4 Grounding 15 6 5 Connecting the motor CN2 CN3 CN4 16 6 6...

Page 2: ...this warning Operating manuals for the product Operating manuals for this product are listed below For operating manuals not included with the product contact your nearest Oriental Motor sales office...

Page 3: ...sing injury or damage to equipment Do not touch the motor or driver when conducting the insulation resistance measurement or dielectric strength test Accidental contact may result in electric shock Do...

Page 4: ...sulting in injury or damage to equipment For the power supply of I O signals use a DC power supply with reinforced insulation on its primary and secondary sides Failure to do so may result in electric...

Page 5: ...onnector part Fix using two banding bands or a wide clamp Fixing at one place on each side Fixing at two places on each side Connector Connector Banding band etc Banding band etc When installing the m...

Page 6: ...n or off the power supply via a solid state relay SSR may damage the motor and driver z z When the motor is used in vertical drive gravitational operation or in drive with a large inertia use a regene...

Page 7: ...7 Precautions for use...

Page 8: ...W 400 400 W Power supply voltage A Single phase 100 120 VAC C Single phase 200 240 VAC Three phase 200 240 VAC Identification code 4 3 Information about nameplate The following nameplate is an example...

Page 9: ...ned off the LED is turned off once the residual voltage in the driver drops to a safe level Motor connector CN2 MOTOR Connects the motor power connector of the connection cable Regeneration resistor t...

Page 10: ...vection and conduction through the enclosure Install the driver in a state where clearances of at least 25 mm 0 98 in in the horizontal and vertical directions between the driver and enclosure or othe...

Page 11: ...rately and mount it to a 35 mm 1 38 in wide DIN rail Refer to MADP02 handling guideline for installation method z z Installation using driver mounting brackets Use the included mounting screws to secu...

Page 12: ...Lead wire Terminal Heat shrinkable tube Solder Pass the lead wire through the terminal hole and give it two or three turns Dial Variable resistor 5 4 Installing the regeneration resistor sold separate...

Page 13: ...13 Installation...

Page 14: ...1 Regeneration resistor Connect to CN1 Note Be sure to use the dedicated connection cable sold separately to connect the motor Regardless of whether an electromagnetic brake is equipped or not always...

Page 15: ...nal L1 and the neutral side to terminal L2 If either of them is connected to terminal L3 the motor does not rotate Connect the R S and T phase lines to L1 L2 and L3 terminals respectively 6 3 Circuit...

Page 16: ...The built in power supply cannot be used in the case of source logic Do not turn the switch ON 6 7 Connecting the I O signals CN5 CN7 Connect the input signals to CN5 and the analog external input si...

Page 17: ...tting for the operating speed or torque limit can be performed For the external DC voltage use a DC power supply 0 to 10 VDC with reinforced insulation on its primary and secondary sides The input imp...

Page 18: ...CN5 and IN COM1 Regeneration resistor AWG22 TH input IN COM1 150 C 302 F N C Connect to CN1 AWG18 R RG2 terminal RG1 terminal Note The TH input is not assigned to CN5 at the time of shipment When usi...

Page 19: ...or in the clockwise direction 3 IN1 RVS This signal is used to rotate the motor in the counterclockwise direction 8 IN6 STOP This signal is used to stop the motor instantaneously 11 IN COM1 Input sign...

Page 20: ...ince it rotates lightly Doing so may damage the product z z Setting with analog external setting devices Using PAVR 20KZ sold separately When using the PAVR 20KZ turn the M0 input ON Turning the PAVR...

Page 21: ...key once again The display changes to 0 6 Operate the motor in JOG operation by pressing the key or key The operating speed is displayed during JOG operation The motor rotates in the clockwise directi...

Page 22: ...arameter refer to the USER MANUAL When a power supply is turned on the speed of the monitor mode is displayed initial setting Use the monitor mode when operating the motor Monitor mode Speed Load fact...

Page 23: ...r dielectric strength test on an encoder itself Doing so may damage the encoder Inspection item Check if any of the mounting screws of the motor and gearhead is loose Check if the bearing part ball be...

Page 24: ...me Connect the regeneration resistor Undervoltage The power supply voltage dropped below approximately 60 of the rated voltage Check the voltage of the main power supply Check the wiring of the power...

Page 25: ...ation data of different directions was linked in linked motion operation Five operation data or more was linked Positioning operation was performed at the operating speed of 0 r min Check the operatio...

Page 26: ...rmissible voltage range 15 to 10 Rated frequency 50 60 Hz Permissible frequency range 5 Rated input current Single phase 3 7 A Single phase 2 3 A Three phase 1 1 A Single phase 4 7 A Single phase 2 8...

Page 27: ...tegory Pollution degree 2 Protection against electric shock Class EMC Directive This product has received EMC compliance under the conditions specified in Example of installation and wiring on the USE...

Page 28: ...ducts mentioned in this manual are recommended products and references to their names shall not be construed as any form of performance guarantee Oriental Motor is not liable whatsoever for the perfor...

Reviews: