Step 8. Test Float Switches and Control Panel, cont.

Timed-Dose: “YG,R” or “YG,R,W” Float Switch Assemblies  
(S1PT or S1PTRO Control Panels)

•  Place the “Timer On/Off” and the “Redundant Off/Low-Level Alarm” (if 

included) switches in the “up” position. 
– The “Off” light on the timer in the control panel turns on.  
– The timer counts down and runs the pump when the “Off” cycle is  
  complete if the “Timer On/Off” switch remains in the “up” position  
  (during normal operation). 

•  Place the “High-Level Alarm” switch in the “up” position.  

– The audible alarm sounds; the panel door alarm light turns on.  
– The pump turns off automatically if using the timer override function. 

•  Place the “High-Level Alarm” switch in the “down” position.  

– The audible alarm goes silent; the panel door alarm light turns off. 
– The pump turns off automatically if using the timer override function. 

•  Place the “Timer On/Off” switch in the “down” position.  

– The “Off” light on the timer in the control panel turns off. 

•  Place the “Redundant Off/Low-Level Alarm” switch (if included) in the 

“down” position.  
– The audible alarm sounds and the panel door alarm light turns on. 

Timed-Dose: “Y,R,W” or “YG,R,W” Float Switch Assemblies  
(MVP-S Control Panels) 

•  Go to the logo unit’s “input” screen, per the instructions supplied in the panel. 
•  Place the “Redundant Off/Low-Level Alarm” switch in the “up” position.  

– The #1 input is highlighted. 

•  Place the “Timer On/Off” switch in the “up” position.  

– The #2 input is highlighted.  
– The timer counts down and runs the pump when the “Off” cycle is  
  complete if the “Timer On/Off” switch remains in the “up” position  
  (during normal operation). 

•  Place the “High-Level Alarm” switch in the “up” position. 

– The #4 input is highlighted, the audible alarm sounds, and the  
  panel door alarm light turns on.  
– The #3 input is highlighted if the override timer function is used.

•  Place the “High-Level Alarm” switch in the “down” position.  

– The audible alarm silences, the panel door alarm light turns off, and the  
  #4 input is not highlighted.  
– The #3 input is not highlighted if the override timer function is used. 

•  Place the “Timer On/Off” switch in the “down” position.  

– The #2 input is not highlighted. 

•  Place the “Redundant Off/Low-Level Alarm” switch in the “down” position.  

– The audible alarm sounds, the panel door alarm light blinks, and the #1  
  input is not highlighted.  
– The alarm condition ends when the “Redundant Off/Low-Level Alarm”  
  float switch is back in the “up” position.

Installation Steps

8b

Timed-Dose, “Y,R,W” or “YG, R, W” MVP control panels

Logo unit screen

Summary of Contents for Biotube ProPak

Page 1: ...Installation Manual 1800348 9843 15414594449 www orenco com Biotube ProPak LOS Pump Package Installation Manual 1 800 348 9843 1 541 459 4449 www orenco com...

Page 2: ...products come with installation instructions and all of these instructions are available in hardcopy form Contact your distributor or Orenco for copies or find instructions online in the Orenco Docume...

Page 3: ...which is available from your local distributor from Orenco and online at www orenco com products Note All pipe diameters given are US nominal IPS pipe sizes If you re using metric pipe you may need a...

Page 4: ...grades are met Step 2 Install Tank Adapters and Risers Step 2a Install the tank adapters if they haven t been installed Follow the manufacturer s instructions For Orenco PRTA24 or PRTA30 Tank Adapter...

Page 5: ...tions to test the seams between the access riser tank adapter and tank for watertightness Key Points Plug the tank s inlet and outlet before testing watertightness Fill the tank with water to a level...

Page 6: ...y Installation Instructions NIN MF DA 1 Float Switch Settings and Adjustments Instructions IMPORTANT DON T change the float tether lengths Step 5 Connect Pump Discharge to Transport Service Line Glue...

Page 7: ...a Open the discharge plumbing valve and service connections Step 7b Unsnap the float switch assembly and remove it from the riser If the assembly includes a Redundant Off Low Level Alarm float switch...

Page 8: ...larm switch in the down position The audible alarm goes silent the panel door alarm light turns off Place the Pump On Off switch in the down position The pump stops running Place the Redundant Off Low...

Page 9: ...the panel door alarm light turns on Timed Dose Y R W or YG R W Float Switch Assemblies MVP S Control Panels Go to the logo unit s input screen per the instructions supplied in the panel Place the Red...

Page 10: ...iser Make sure the coils don t tangle with the float switches Step 8e Place the Auto Off Man switch on the control panel to Auto make sure the control panel circuit breakers are in the On position and...

Page 11: ...Orenco Systems 800 348 9843 1 541 459 4449 www orenco com NIM EPS 1 Rev 6 10 21 Page 11 Biotube ProPak and LOS Pump Package Installation Manual...

Page 12: ...1 800 348 9843 1 541 459 4449 www orenco com NIM EPS 1 Rev 6 10 21 Orenco Systems Installation Manual Biotube ProPak LOS Pump Package...

Reviews: