background image

MNL940-003-000- 

 

13 

4.0 OPERATIONAL 

CONSIDERATIONS

 

 

4.1 LOADING 

LIMITATIONS:

 

 

The INV series are designed to produce a power level of 1200 Watts ( real power) under 

 

continuous operating conditions. In addition, they can supply bursts of over 1500 watts 

 

for several seconds. Peak repetitive currents on the order of 60 amps may also be 

supplied  

continuously as long as they do not exceed the RMS value of 10 amps.  

 

 This high peak current capability allows the INV 1210 series to start most high in - rush 
loads. It must be understood that the DC power source suppling the inverter must also 
have this capability in order to derive these benefits. A poorly regulated or high internal  
resistance DC power source will affect operation of the inverter.  

 

4.2

 

POWERING REACTIVE LOADS

 

 

Capacitors and inductors are reactive in nature. If the load is applied during the peak of 
the AC cycle there may be a considerable in rush of current several magnitudes larger 
than the steady state current. This current is only limited by any series resistance that may 
be present in the load circuit. Under the right conditions, this could trip the overload 
protection circuits in the inverter. 

 

 Several methods can be used to prevent tripping the protection circuits in the power 

 

source . One common method is to insert a limiting impedance in series with the load. 
This could be in the form of a fixed resistor or NTC (negative temperature coefficient) 
thermistor. Also, zero crossing switching can be employed. 

 

 Loads with a large parallel capacitance will draw large current spikes during the edge 

 

transitions of the output waveform. This may generate EMI (electro-magnetic  

 

interference). Also, loads that are pure inductors will produce “ringing” on the edges of 

 

the output waveform which will also cause EMI. If the load to be supplied are purely 

 

capacitive or inductive, the Behlman model INV1200 should be considered. The model 

 

1200 produces a sinewave output. 

 

4.3 POWERING 

LAMPS

  

 

 Tungsten filaments lamps, when cold, present a very low resistance. Once they are  
energized, their resistance quickly climbs to it’s steady state value. This characteristic 
must be accounted for when driving tungsten filament lamps. The same methods for 
driving reactive loads can be applied to tungsten. 

 

4.4 POWERING 

MOTORS

 

 

 Driving an AC motor presents a special problem. Most motors require a starting current 
that is several times higher than the running current. This current may last for a few 
cycles to several seconds depending on the construction and mechanical load on the 
motor. This current is sometimes referred to as the motor’s “locked rotor” current. This 
current is not to be confused with the in- rush current that usually occurs over the course 
of one or two cycles of the AC waveform. 

 

Summary of Contents for BEHLMAN INV 1210

Page 1: ...SERVICE ASSISTANCE CONTACT BEHLMAN CUSTOMER SERVICE DEPARTMENT PHONE TOLL FREE 1 800 874 6727 OR WRITE BEHLMAN CUSTOMER SERVICE DEPARTMENT 80 CABOT COURT HAUPPAUGE NY 11788 PHONE 631 435 0435 FAX 631...

Page 2: ...sence of flammable gases or fumes Operation of any electrical instrument in such an environment constitutes a definite safety hazard KEEP AWAY FROM LIVE CIRCUITS Operating personnel must not remove eq...

Page 3: ...itions due to the exposure of hazardous voltage that can be lethal if contacted Neither Behlman Electronics Hauppauge NY USA nor any of the subsidiary sales organizations can accept any responsibility...

Page 4: ...used the customer being liable for all shipping handling and repair costs When packing for reshipment use the original shock absorbent material and shipping container to preclude damage to the equipme...

Page 5: ...horization RMA number This number must be attached to the equipment sent back for warranty repair Equipment must be shipped back to Behlman prepaid No collect shipments will be accepted Behlman shall...

Page 6: ...3 0 OPERATING INSTRUCTIONS 3 1 Installation 3 2 Wiring 3 3 Controls and Indicators 3 4 Optional alarm contacts 4 0 OPERATIONAL CONSIDERATIONS 4 1 Load Limitations 4 2 Powering Reactive Loads 4 3 Powe...

Page 7: ...switch to AC when the DC input is lost The second option A1 will favor the AC line input and will switch to the inverter if the line is lost These features allow the unit to be incorporated into a us...

Page 8: ...e peak value of a 120Vac rms This type of waveform is known as Modified sinewave The control circuitry on the output inverter assembly also provides protective functions Output current is measured and...

Page 9: ...k mounting it is permissible to mount the inverter by the mounting ears only If the unit is intended for use in a mobile or other high vibration application the use of additional support for the rear...

Page 10: ...will place one side of the inverter output at the neutral potential It should be noted that this is only recommended to satisfy the NEC requirements The output of the inverter is isolated from the DC...

Page 11: ...Pull in cooling air min 3 clearance 3 STATUS LEDs Indicate presence of AC IN DC IN and INVERTER status optional 4 LINE BYPASS FUSE Protects input line when used as stand by Supply optional 5 OUTPUT C...

Page 12: ...MNL940 003 000 11 CONTROLS AND INDICATORS MODEL INV 1210 SERIES INVERTERS ALL MODELS...

Page 13: ...ch all loads off before switching on the inverter This will prevent multiple in rush currents from tripping protective circuits in the inverter 2 Switch on the inverter At this point the sound of the...

Page 14: ...thod is to insert a limiting impedance in series with the load This could be in the form of a fixed resistor or NTC negative temperature coefficient thermistor Also zero crossing switching can be empl...

Page 15: ...n doubt consult the motor manufacturer 4 6 POWERING NON LINEAR LOADS Loads utilizing rectifiers and SCRs interact with the AC power source and have a profound effect on the output waveform Consider th...

Page 16: ...quipment These devices require a sinusoidal voltage for proper operation and timing It should be noted that this unit produces a waveform with square edges These waveform produce harmonics at frequenc...

Page 17: ...sure AC input at rear panel Output distorted high peak load current Reduce loading if distortion is objectional DC breaker repeatedly trips DC polarity reversed or internal fault in inverter Check pol...

Page 18: ...MNL940 003 000 17 6 0 MECHANICAL OUTLINE...

Page 19: ...MNL940 003 000 18 REVISION HISTORY Rev ECO DESCRIPTION DATE N A INITIAL RELEASE 5 9 2016...

Reviews: