standby
Pilot. After the active Pilot
is offline, the
GUI closes. When
the failover is complete, you can log back into the GUI.
•
If you are replacing a component located on the standby Pilot,
Guided Maintenance brings the standby Pilot
offline. When
servicing the standby
Pilot, failover is not required.
•
If you are replacing a power supply or a fan module, you are not
required to bring the Pilot
offline. The power supplies and fan
modules are hot-serviceable.
Note:
You can replace one power supply without bringing the Pilot
offline, as long as the second power supply remains online and
operational.
Slide Pilot to Service Position
1 Extend the rack’s anti-tilt legs.
Figure 179: Pilot position during component replacement
Legend
1 Rack
2 Pilot chassis
3 Pilot rails
2 Slide the Pilot chassis fully forward until the slide lockout release tabs lock
into position.
Pilot Replacement Procedures
215