Servicing CRUs That Require Server Power-Off
85
Servicing CRUs That Require Server Power-Off
These sections describe how to service customer-replaceable units (CRUs) that require
you to power off the server. For more information about CRUs, see
“Customer-Replaceable Units” on page 19
Description
Use
Service the DIMMs.
“Servicing the DIMMs (CRU)” on page 85
Service the PCIe Risers.
“Servicing PCIe Risers (CRU)” on page 97
Service the PCIe cards.
“Servicing PCIe Cards (CRU)” on page 108
Service the internal USB flash drives.
“Servicing the Internal USB Flash Drives
Service the battery.
“Servicing the Battery (CRU)” on page 116
Related Information
■
“Servicing CRUs That Do Not Require Server Power-Off” on page 63
■
Servicing the DIMMs (CRU)
The Oracle Server X6-2 supports a variety of DDR4 DIMM configurations that can include
quad-rank (QR) and dual-rank (DR) DDR4 DIMMs.
Caution -
These procedures require that you handle components that are sensitive to
electrostatic discharge. This sensitivity can cause the components to fail. To avoid
damage, ensure that you follow antistatic practices as described in
Caution -
Ensure that all power is removed from the server before removing or installing DDR4
DIMMs, or damage to the DDR4 DIMMs might occur. You must disconnect all power cables
from the system before performing these procedures.
Summary of Contents for EXADATA X6-2
Page 1: ...Part No E62171 02 June 2016 Oracle Server X6 2 Service Manual ...
Page 2: ......
Page 12: ...12 Oracle Server X6 2 Service Manual June 2016 ...
Page 62: ...62 Oracle Server X6 2 Service Manual June 2016 ...
Page 226: ...226 Oracle Server X6 2 Service Manual June 2016 ...
Page 278: ...278 Oracle Server X6 2 Service Manual June 2016 ...
Page 284: ...284 Oracle Server X6 2 Service Manual June 2016 ...