MD-30C version 3.2.000
8
Microphone desk and
voice alarm fireman's panel
ME-200C
5.
CONNECTION
5.1.
Power supply
The microphone desk should be powered at 24VDC through the
DC IN 24V
terminal strip on the back plate.
5.2.
Audio and CAN bus connection
Through the RJ45 INPUT and OUTPUT connectors, the console transmits and receives CAN communication and audio signals to the
COMPACT system. For connection use RJ45 connectors with metal housing and STP CAT 5 cable.
Pin 1:
AUDIO H (HOT)
Pin 2:
AUDIO C (COLD)
Pin 3:
Not used
Pin 4:
CAN H
Pin 5:
CAN L
Pin 6:
Not used
Pin 7:
Not used
Pin 8:
Metal Shield:
24V DC
POWER SUPPLY
I924UP
(Not included)
GND
DIP switch 1
Figure 3
Figure 4