Opus Trio Scala Installation Manual Download Page 4

 

 

INSTALLATION INSTRUCTIONS 

 

CONTENTS 

Important notes 

page 2  Commissioning the stove  page 8 

Technical information 

page 3  Check for spillage 

page 

Dimensions and clearances page 4  Customer briefing 

page 10 

Installation 

page 5  Servicing 

page 

1

 

Important notes 

 

This stove is a fuel effect radiant convector. Before installation, ensure that the local distribution 

condition (identification of the type of gas and pressure) and the adjustment of the appliance are 

compatible. The data label is located at the rear of the stove. The installation must be in accordance 

with these Instructions and National Regulations and must be carried out by a qualified installer. In 

the UK the installation must also be in accordance with the relevant parts of BS5440 parts 1 and 2. 

 

 

Any flue damper plate or flue restrictor must be removed or fixed permanently in the fully open 

position, or shall only be fitted in accordance with National Regulations. In the UK the installation 

must also be in accordance with the relevant parts of BS5440 parts 1 and 2. 

This appliance is intended for use on a gas installation with a governed meter. 

 

If the chimney has previously been used to burn solid fuel, the chimney should be swept before the 

stove is installed. 

 

The flue pull should be checked prior to the installation of the stove. Apply a smoke pellet to the 

flue and ensure that the smoke is drawn into the flue. If there is not a definite flow, preheat the flue 

for a few minutes & re-test. 

 

Before the stove is installed a flue test in accordance with National Regulations should be carried 

out. The gas connection must be in accordance with National Regulations. 

 

The stove is fitted with a spillage monitoring system consisting of a thermal switch connected to a 

thermocouple interrupter. This system is not adjustable, and must not be put out of action. If any 

parts of the spillage monitoring system require replacement only original manufacturers’ parts must 

be used. 

 

All surfaces except the controls are considered to be working surfaces 

 

The stove should not be used for any other purpose than as a room heater and a decorative stove. 

The stove should not be operated with the door open, without the door attached or the glass in the 

door damaged, broken or missing. 

 

 

Summary of Contents for Trio Scala

Page 1: ...INSTALLA TION MANU AL O PUS TRIO SCALA GAS STOVE FIRED BY DESIGN ...

Page 2: ......

Page 3: ...INSTALLATION SERVICING INSTRUCTIONS TO BE LEFT WITH THE CUSTOMER For use in UK Ireland on Natural Gas G20 at a supply pressure of 20mbar GB IE ...

Page 4: ...440 parts 1 and 2 This appliance is intended for use on a gas installation with a governed meter If the chimney has previously been used to burn solid fuel the chimney should be swept before the stove is installed The flue pull should be checked prior to the installation of the stove Apply a smoke pellet to the flue and ensure that the smoke is drawn into the flue If there is not a definite flow p...

Page 5: ...W 4 3 kW 6 95 kW 4 3 kW 6 95 kW 4 3 kW HIGH LOW SUPPLY PRESSURE 20 1 20 1 20 25 1 MBAR GAS CONNECTION 8mm PIPE GAS CONSUMPTION 0 721 M3 H NOX CLASS 5 5 5 EFFICIENCY CLASS 2 2 2 INJECTOR STEREOMATIC No88 7 x 0 88mm AERATION 2X 6 3MM FLUE RESTRICTOR 62MM DIAMETER RING SETTING PRESSURE 11 1Mbar HOT 10 9 mbar COLD HIGH LOW 4 55 Mbar HOT 4 4 mbar COLD FLUE CONNECTION 125MM DIAMETER THERMAL SWITCH 120 º...

Page 6: ...4 Dimensions clearances FIG 1 Door locking screw ...

Page 7: ...ure that nothing combustible such as carpets soft furnishings curtains shelves etc are positioned within the minimum distances to combustibles as stated in the paragraph above Log Arrangement The logs should only be arranged as shown in the layout given in the Installation Instructions by a qualified person The stove must only be fitted with the ceramics supplied DO NOT use any extra logs or coals...

Page 8: ...ed ventilation is not normally required except in new build houses For Republic of Ireland refer to I S813 issued by the National Standards Authority of Ireland Gas Connection The gas supply connection is behind the lower door of the stove on the inlet to the gas valve An isolation elbow with pressure test point is supplied with the stove for easy connection The gas supply should be purged and any...

Page 9: ...ted on top of the granular dispersal medium as directed on theback of the packet Take care not to put embaglow material too near the pilot as this can interfere with ignition 3 Position logs B C D as shown Fig 4 4 Close the door and secure with the locking screw Fig 1 Fig 3 Fig 4 ...

Page 10: ...ent After fitting the batteries and replacing the cover the fire can now be operated Slide the Master switch to the right to the ON position I symbol To start the fire press the ON OFF button and hold for 1 second then release The burner will within around 1 to 10 seconds ignite and adjust to the maximum power setting This can takelonger on the first lighting as it has to clear out any air locks C...

Page 11: ...9 Draught diverter cover Remove 2 screws Fig 5 Draught diverter Bottom edge of draught diverter ...

Page 12: ...ice Replace the draught diverter cover CUSTOMER BRIEFING Hand these Instructions to the customer Advise the customer how to use the stove Explain to the customer that the stove has a flame failure and spillage monitoring system Point out the explanation of this system is in the Operating the Stove section of the instructions Advise that if the monitoring system repeatedly shuts off the stove it sh...

Page 13: ...ew securing the door Fig 1 and open the door 3 Remove the ceramics in the reverse order to that described in the POSITIONING THE LOGS section 4 Remove any deposition of dirt lint etc carefully from the burner tray main injector and pilot assembly with a soft brush 5 If necessary to remove the burner firstly isolate the gas supply and disconnect Disconnect the thermal switch underneath the gas valv...

Page 14: ... to this code of practice The appliance and chimney can be fully cleaned once the installation is complete Components for weatherproofing are installed correctly Smoke spillage test has been carried out CO Alarm fitted and tested Handover At handover all user instructions should be given to the user and an explanation of the appliance operation and safety issues should be given Additionally an exp...

Page 15: ...ImportedtotheUKFirepower Flightway Dunkeswell Honiton Devon EX144RD UK 08443320155 info firepowerheating co uk Opus Trio Gas August 2019 V002 FIRED BY DESIGN www opusstoves co uk ...

Reviews: