Servicing
It is essential that the stove is regularly serviced, and the flue system checked by a qualified person.
Servicing instructions
The stove is fitted with a spillage monitoring system consisting of a thermal switch connected to a
thermocouple interrupter. This system is not adjustable and must not be put out of action. If any parts
of the spillage monitoring system require replacement only original manufacturer’s parts must be
used.
The thermal switch rating is 120ºC. Quote this rating if ordering a new switch.
1.
The following servicing procedure should be carried out regularly and only by a qualified person.
Ensure that the fire is turned off and is cold.
2.
Slacken the screw securing the door (Fig.1) and open the door.
3.
Remove the ceramics in the reverse order to that described in the POSITIONING THE LOGS
section.
4.
Remove any deposition of dirt, lint etc carefully from the burner tray main injector and pilot
assembly with a soft brush.
5.
If necessary, to remove the burner firstly isolate the gas supply and disconnect. Disconnect the
thermal switch underneath the gas valve. Remove the 4 screws securing the burner and carefully
remove the burner. If removing the granular dispersal medium take care not to block the pilot
assembly. (fig.6)
6.
Replace the ceramics as described in POSITIONING THE LOGS section (Fig.3).
7.
Close the stove door; replace the screw securing the door handle or door.
8.
Check the supply pressure as described in the TECHNICAL INFORMATION section (P.3)
9.
Ensure correct operation of the flue as described in CHECK FOR SPILLAGE section (P.9 )
Fig.6