When the temperature sensor is not connected, the CPU will set the float charging voltage at 54V.
The DIP SW3 provides selection of the charging mode, when DIP SW3 is ON, UPS charger is CV
mode, when DIP SW3 is not ON, UPS changer has 2-stage control, quick charge then floating
charge.
Charging current
Charging voltage
Dip SW3 ON for CV charging.
Time
Float charge
Time
48V