28
Off-Grid
Off-Grid (I): Default setting for off-grid mode.
PV energy supply priority setting: 1
st
Load, 2
nd
Battery
PV power will provide power to the load first and then charge battery. Feed-in
to the grid is not allowed under this mode. At the same time, the grid relay is
connected in Inverter mode. That means the transfer time from inverter mode
to battery mode will be less than 15ms. Besides, it will avoid overload fault
because grid can supply load when connected load is over 4KW.
Battery charging source:
1.
PV or Grid: If there is remaining PV power after supporting the loads, it will
charge battery first. Only until PV power is not available, grid will charge
battery. (Default)
2.
PV only: It is only allow PV power to charge battery.
3.
None: It is not allowed to charge battery no matter it’s from PV power or grid.
Load supply source:
When PV power is available:
1.
1
st
PV, 2
nd
Battery, 3
rd
Grid (Default)
PV power will provide power to the load first. If it’s not sufficient, battery
power will provide power to the load. When battery power is running out or
not available, grid will back up the load.
2.
1
st
PV, 2
nd
Grid, 3
rd
Battery
PV power will provide power to the load first. If it’s not sufficient, grid will
provide power to the load. If grid is not available at the same time, battery
power will back up.
When PV power is not available:
1.
1
st
Grid, 2
nd
Battery
Grid will provide power to the load first. If grid is not available, battery power
will provide power backup.
Summary of Contents for Sp4000 Premium
Page 1: ...Sp4000 Premium Hybrid PV Inverter User manual Version 1 2 User Manual...
Page 20: ...18 You can set the related parameters in software Refer to the diagram below...
Page 38: ...36 Battery voltage or percentage Procedure Date and time Procedure...
Page 44: ...42 There is setting screen from software shown below...
Page 58: ...56 Parallel for output Enable Parallel for output Disable...