16
Setup of Functions
➎
Alarm Output Setting
ALAM
400
H (higher limit value) : Alarm output turns on when the
measurement value exceeds the
Setting value.
L (lower limit value) : Alarm output turns on when the
measurement value falls below the
Setting value.
The Unit has 3 Alarm Output Modes as below;
ALAM
50
OUT
NOR
OUT
DEL
OUT
ONES
ONE-SHOT Mode
Alarm output turns on when the value exceeds
or falls below the limit value and is kept for a
specific time.
NORMAL Mode
Alarm output is kept on as long as the value is
above or below the limit value.
DELAY Mode
Alarm output turns on when a specific time
period passes after the value exceeds or falls
below the limit value.
Measurement value
Alarm output
H
L
ON
OFF
t: Time to delay output
Measurement value
Alarm output
H
L
ON
OFF
t
Measurement value
t: Time to keep output on
Alarm output
H
L
ON
OFF
t
Alarm output mode, temperature of alarm output and alarm ON/OFF can be set.