  |  Fire Protection  |  Data sheet No. 41350  |  Version 01-2019 

6.

 

Installation outdoors or in a cold environment

• 

A special WDG-type splash-proof housing is available for protection of 
smoke detectors exposed to the open air or a cold environment. This 
housing prevents the warm air in the smoke detector duct from con-
densing. The interior of the housing is insulated with foam rubber.

7.

 

Installing the housing with the sensor

• 

Attach the housing base with the electronics and sensor to the adapter 
plate. The housing can be attached in any of the four orthogonal orien-
tations. The direction of the housing has no effect on the measurement 
result. You can optimally align the housing with the sensor.

• 

Wire the device according to the applicable circuit diagram.

• 

Caution: 

Wiring and electrical connections may only be done by a duly 

qualified electrician.

• 

Make sure that all cables are connected in accordance with the applica-
ble electrical regulations. The cable jacket must reach as close as possi-
ble to the terminal block. Wires longer than 10 mm must be fixed near 
the terminal block using a cable clip or the like or must be insulated in 
pairs with a suitable protective tube (see application example). 

• 

Check that the gaskets  in the housing top are correctly positioned.

• 

Complete the installation by snapping on and tightening the housing 
top (ensuring that the catch at the lower end of the housing snaps in 
correctly; 

observe the specified mounting torque of 1.2 Nm

). 

8.

 

Testing the duct smoke detector 

 

• 

After completing the installation work, properly wiring the device 
(please note the separate data sheets / circuit diagrams) and applying 
power, the duct smoke detector is operational.

• 

The green LED (12) lights up.

• 

Press the alarm / reset button (9) to perform a simple initial functional 
test. All LEDs must light up and all relays drop out. 

The units con-

nected to the relays are activated!

 The display (11) indicates the 

current degree of sensor contamination. On releasing the button, all 
LEDs go out except for LED (12), which shows the supply voltage, and 
the relays pull in. A test opening (14) is available for testing the duct 
smoke detector. Open the test hole plug. Then spray test spray into the 
test opening until the smoke detector triggers. Take care not to apply 
too much test spray, since this would contaminate the smoke detector, 
possibly causing it to indicate a higher contamination level after the 
next start or reset. 

• 

Caution:

 Take care to close the test hole opening after the test to 

prevent the smoke detector from drawing in false air. False air could 
prevent the smoke detector from triggering when it should. The alarm/
reset button lights up, and the relays drop out. The electronic system 
goes into alarm state and locks up. Press the alarm/reset button to 
release it. 

The sensor must be free of smoke and test gas during 

reset.

 If there is still test gas in the chamber, the device will indicate a 

higher contamination level. In this case, wait a while and then perform 
a reset by disconnecting the voltage or perform an external reset. If 
necessary, remove the housing cover and blow out the smoke detector.

9.

 

Final review

• 

Are all screws tight?

• 

Is the adapter plate properly mounted in terms of flow 
direction?

• 

Are all gaskets in the correct position?

• 

The blue LED must not light up when airflow > 1 m / s 
during operation.

Use the test opening for performing the functional test.

Caution:

 The test opening should always be closed 

during operation, as this would otherwise prevent 
smoke detection!

11

9

9

14

14

12

wiring example: 

1)  

The WDG-X special housing is not covered by the VdS 
approval.

Summary of Contents for KRM-X

Page 1: ...S485 MOD BAC only Accessories Mounting bracket KS X for insulated circular ducts KS X for insulated circular ducts in combination with WDG X Housing WDG X protective insulating housing with alarm disp...

Page 2: ...nected Note The floating switching contacts terminals 11 17 should be assigned as uniformly as possible to an installation category according to EN 60730 1 These switching contacts are to be used for...

Page 3: ...ng segment display 00 99 Contamination in Flashes starting at 70 contamination relay drops out at 99 the alarm LED alarm lights up Failure E g smoke detector missing communication with smoke detector...

Page 4: ...when airflow is too low and air relay only present on DIBt versions drops out Check smoke detector position in the duct check sampling tube TurboTube for contamination and clean if necessary Programm...

Page 5: ...unting bracket this makes it possible to mon itor ducts up to 100 mm There is no maximum width height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube...

Page 6: ...structurally possible If the positioning recommendations cannot be followed for structural reasons the KRM X should be mounted such that reliable smoke detection and airflow are nonetheless ensured T...

Page 7: ...lel to the flow direction Four self tapping screws not included in delivery serve for attaching the adapter plate to the sheet metal duct 4 Installation on the duct Rectangular air duct see picture on...

Page 8: ...The green LED 12 lights up Press the alarm reset button 9 to perform a simple initial functional test All LEDs must light up and all relays drop out The units con nected to the relays are activated T...

Page 9: ...ive to smoke while work is in progress If a brief shutdown cannot be cannot be tolerated for operational reasons measures must be taken to prevent a shutdown If necessary a bridge can be placed over t...

Page 10: ...eturn to its normal function and does it unlock again from the smoke alarm state and return to its normal function when the alarm has been reset Does the detector return to the alarm state and lock up...

Reviews: