KRM-X® Duct Smoke Detector

4

 | 

10

  |  Fire Protection  |  Data sheet No. 41350  |  Version 01-2019 

LEDs

Meaning

Comments

Alarm / reset 

(red)

Smoke alarm or 

failure

Reset after failure:

Briefly press alarm/reset button. KRM-X restarts immediately.

Reset after alarm:

Press and hold the alarm/reset button for at least 2 seconds until the red alarm LED in the 

button goes out. Do not release it until then. KRM-X will start again only after release. If the 

alarm/reset LED continues to flash while the button is pressed, the smoke detector is still 

filled with test gas/test spray/smoke and cannot be reset. In that case blow out detector 

out or wait.

Failure 

(yellow)

Circuit board 

defective or smoke 

detector missing

Check/replace circuit board or RM 3.3-X (ALN-E) smoke detector.

Smoke alarm 

(2 x red)

Smoke alarm or  

contamination > 99%

Red LEDs directly on the RM 3.3-X (ALN-E) smoke detector. LEDs remain on until reset has
taken place.

Power supply 

(green)

Supply voltage 

connected

Green LED lights up if supply voltage is connected.

Airflow (blue)

Insufficient airflow

Blue LED lights up when airflow is too low and air relay (only present on DIBt versions) 

drops out. Check smoke detector position in the duct, check sampling tube (TurboTube) 

for contamination and clean if necessary.

Programming the bus address and baudrate  

(Modbus/BACnet versions only):

Display view

Comments

Press buttons T3+T4 on circuit board (to the right of the display) simultaneously to switch from 
the contamination display to the bus address display (display flashes).

Display flashes

Use button T3 or T4 to enter the desired address (1–99). The default address on delivery is 99. 

The display returns to its previous state after 3 seconds without a button being pressed.

After pressing T3+T4 simultaneously the current bus address is saved and the two underscores 

appear for about one second.

Display and  

yellow LED flash

Now the baudrate can be selected (display and yellow LED flash); available baudrates:

01 = 9600 (default)
02 = 19200
03 = 38400
04 = 76800

After pressing T3+T4 simultaneously once more the current baudrate is saved and the two 

underscores appear for about one second, after which the device returns to the contamination 

display. 

Note: 

After 6 seconds without a button being pressed the device returns to the contamination display,  

and the current value is saved.

T3+
T4

Summary of Contents for KRM-X

Page 1: ...S485 MOD BAC only Accessories Mounting bracket KS X for insulated circular ducts KS X for insulated circular ducts in combination with WDG X Housing WDG X protective insulating housing with alarm disp...

Page 2: ...nected Note The floating switching contacts terminals 11 17 should be assigned as uniformly as possible to an installation category according to EN 60730 1 These switching contacts are to be used for...

Page 3: ...ng segment display 00 99 Contamination in Flashes starting at 70 contamination relay drops out at 99 the alarm LED alarm lights up Failure E g smoke detector missing communication with smoke detector...

Page 4: ...when airflow is too low and air relay only present on DIBt versions drops out Check smoke detector position in the duct check sampling tube TurboTube for contamination and clean if necessary Programm...

Page 5: ...unting bracket this makes it possible to mon itor ducts up to 100 mm There is no maximum width height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube...

Page 6: ...structurally possible If the positioning recommendations cannot be followed for structural reasons the KRM X should be mounted such that reliable smoke detection and airflow are nonetheless ensured T...

Page 7: ...lel to the flow direction Four self tapping screws not included in delivery serve for attaching the adapter plate to the sheet metal duct 4 Installation on the duct Rectangular air duct see picture on...

Page 8: ...The green LED 12 lights up Press the alarm reset button 9 to perform a simple initial functional test All LEDs must light up and all relays drop out The units con nected to the relays are activated T...

Page 9: ...ive to smoke while work is in progress If a brief shutdown cannot be cannot be tolerated for operational reasons measures must be taken to prevent a shutdown If necessary a bridge can be placed over t...

Page 10: ...eturn to its normal function and does it unlock again from the smoke alarm state and return to its normal function when the alarm has been reset Does the detector return to the alarm state and lock up...