Fire Protection  |  Data sheet No. 41350  |  Version 01-2019  | 

5

 | 

10

KRM-X® Duct Smoke Detector

Valid for soft-

ware 0020 

and higher

In the event of a smoke alarm

In the event of device failure / missing detector

KRM-X-1 / KRM-X-1-MOD /  

KRM-X-1-BAC /  

KRM-X-2 / KRM-X-2-MOD /

KRM-X-2-BAC

KRM-X-1 / KRM-X-1-MOD /  

KRM-X-1-BAC /  

KRM-X-2 / KRM-X-2-MOD /

KRM-X-2-BAC

Alarm

 relay 

11 / 12 / 13

Drops out

Drops out

Alarm

 relay 14 / 15

Drops out

Drops out

LED 

alarm / Reset

Lights up

Lights up

Fault

 relay

 18 / 19

 --------- 

Not present

 --------- 

Not present

Fault

 relay

Stays off

Lights up

Alarm reset or 

failure reset

Disconnect power or press alarm button or reset via terminal 

9/10, provided detector chamber has been cleared. 

Disconnect power or press alarm button or reset via terminal 

9/10, provided detector chamber has been cleared and fault 

rectified.

Behavior of the Alarm Relay and Fault Relay and Displays, Plus Reset Options

Installation Instructions and Positioning

The KRM-X must be positioned in accordance with the applicable 
local regulations on ventilation systems. Reliable smoke detection 
must be ensured. The air collecting tube may be cut to a length of 
160 mm, depending on the cross-section of the ventilation duct. 
It must not be cut to less than this minimum length of 160 mm. 
Using the KS-X mounting bracket, this makes it possible to mon-
itor ducts up to <100 mm ø. There is no maximum width, height 
or diameter for air ventilation ducts monitored with the 600 mm 
long standard air collecting tube under the VdS approval/  
DIBt certification. The indicated airflow direction must be 
observed when installing the tube adapter. The air collecting 

tube may be mounted laterally, below or above the air duct – the 
location makes no difference.
In the ideal case, as far as is structurally possible, install the KRM-X 
in a location where flow meters etc. are normally installed, so that 
there is a laminar airflow along the measuring tube. We recom-
mend mounting and installing the KRM-X at the same distance 
from heating, cooling and humidity devices and in a similar way 
as flow sensors. The distance of the KRM-X to fittings, valves,
filters, etc. should be 3 times the diagonal of the channel 
cross-section against the flow direction and 5 times with the flow 
direction, if this is structurally possible. The KRM-X, including the 

Example of positioning 
after a change of air duct 
direction (recommendation)

Example of positioning 
after an air outlet (recommendation)

air outlet

Where there are large temperature differences, 
outdoors for example, or in places that are 
dependent on outside temperature (roof, attic), 
the air duct smoke detector needs to be insulated. 
Oppermann Regelgeräte provides a special 
splash-proof housing (WDG-X) for this purpose.

5 d

h

3 d

h

5 d

h

Summary of Contents for KRM-X

Page 1: ...S485 MOD BAC only Accessories Mounting bracket KS X for insulated circular ducts KS X for insulated circular ducts in combination with WDG X Housing WDG X protective insulating housing with alarm disp...

Page 2: ...nected Note The floating switching contacts terminals 11 17 should be assigned as uniformly as possible to an installation category according to EN 60730 1 These switching contacts are to be used for...

Page 3: ...ng segment display 00 99 Contamination in Flashes starting at 70 contamination relay drops out at 99 the alarm LED alarm lights up Failure E g smoke detector missing communication with smoke detector...

Page 4: ...when airflow is too low and air relay only present on DIBt versions drops out Check smoke detector position in the duct check sampling tube TurboTube for contamination and clean if necessary Programm...

Page 5: ...unting bracket this makes it possible to mon itor ducts up to 100 mm There is no maximum width height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube...

Page 6: ...structurally possible If the positioning recommendations cannot be followed for structural reasons the KRM X should be mounted such that reliable smoke detection and airflow are nonetheless ensured T...

Page 7: ...lel to the flow direction Four self tapping screws not included in delivery serve for attaching the adapter plate to the sheet metal duct 4 Installation on the duct Rectangular air duct see picture on...

Page 8: ...The green LED 12 lights up Press the alarm reset button 9 to perform a simple initial functional test All LEDs must light up and all relays drop out The units con nected to the relays are activated T...

Page 9: ...ive to smoke while work is in progress If a brief shutdown cannot be cannot be tolerated for operational reasons measures must be taken to prevent a shutdown If necessary a bridge can be placed over t...

Page 10: ...eturn to its normal function and does it unlock again from the smoke alarm state and return to its normal function when the alarm has been reset Does the detector return to the alarm state and lock up...

Reviews: