OPERATION
26 / 56
X700-3000_usermanual_engl_20170405.docx
Figure 18: Display in standby mode
No power is available for the load connected. The battery is charged
if necessary.
High-efficiency mode
In high-efficiency mode, the load are supplied via the bypass. The in-
verter is always ready for use at the same time. If the supply network
is outside the tolerance, there is a smooth transition to normal mode.
The battery is charged in high-efficiency mode.
Figure 19: Display in high-efficiency mode
Bypass mode
Bypass mode can be activated in normal mode by pressing the and
buttons together for 2 seconds. To switch back to normal mode,
press and buttons also together until the continuous alarm stops.
In the event of an overload, the UPS system automatically switches
into bypass mode. A beep sounds every 10 seconds.