INSTALLATION
15 / 56
X700-3000_usermanual_engl_20170405.docx
5. The UPS system carries out a self-test, after which “OK” ap-
pears on the display. The UPS system is now operating in nor-
mal mode and supplying the load with reliable power.
6. If an additional emergency power off switch has been installed,
the emergency stop function needs to be tested.
7. Switch the load on one by one.
PLEASE NOTE
The internal batteries charge up to 90% of their full capacity in
less than four hours. ONLINE recommends charging the bat-
teries for 48 hours after installation or extended periods of
non-use.
The batteries start to charge as soon as the UPS system is
connected to the supply network and supplied with power, ir-
respective of the operating mode.
Starting in battery mode
1. Hold the “ON / / ” button on the UPS system down until you
hear a beep.
2. The UPS system is starting, the display then shows the battery
status (see Chap. 4.4
Operating statuses
) and supplies the load
connected with reliable power.
3. If the
display is lit, fix all warnings (see Chap. 7.3
Trouble-
shooting
) and restart the UPS system.
Switching off
1. Hold the “OFF /
” button on the UPS system down for 2
seconds. When the continuous beep ends, the UPS system
switches to standby mode.
PLEASE NOTE
If the “OFF /
” button is released after less than 2 seconds,
the unit is not switched off.