OPERATION
22 / 56
X700-3000_usermanual_engl_20170405.docx
4.3 Settings
1. Open configuration menu: Switch to standby- or bypass mode
and press button for 2 seconds.
2. Selection of menu options: Press or button until you reach
the menu option you want (see Table 6:
Configuration menu
).
3. Select menu option: Press OFF /
button.
4. Change menu setting: Press or button until you reach the
setting you want (see Table 6:
Configuration menu
).
5. Confirm setting: Press OFF /
button.
6. Exiting configuration menu: go to menu “00” or press and
buttons at the same time.
Setting
Available options
Standard
Select output voltage:
[208] = 208V
[220] = 220V
[230] = 230V
[240] = 240V
“230V”
Frequency converter mode:
Switch frequency converter mode on or
off
[ENA] = on (bypass mode not possible)
[DIS] = off
“DIS”
Output frequency:
If frequency converter mode is possible,
the output frequency is in normal and bat-
tery mode
[50] = 50 Hz
[60] = 60 Hz
No function if menu 2: frequency con-
verter mode = DIS
“50”
High-efficiency mode:
[ENA] = on
[DIS] = off
“DIS”