5. Wire the two door switch wires to the 2-pin terminal block header by loosening the lock down screws on the
header. Insert the wires and tighten the screws to secure the wires.
6. Reinsert the terminal block header to the receptacle on the lower circuit board
7. Reinstall the bottom plate containing the dual port sensor by routing the door switch wires trough the wire slot on
the bottom plate cover – make sure to reattach connecting cable to dual port sensor if previously removed.
Applying slight outward pressure on the sides of the sensor housing allows bottom plate to slide in. Make sure the
bottom plate slides into the retention tab slots on the housing.
8. Reattach the device cover.
The sensor is now configured to monitor the door status set by the magnetic door switch.
9. Log into OneVue and set the sensor's Door Delay. Go to Devices > Sensors > select sensor > select Show Advanced
Options > set Door Delay (minutes).