2. If Signal OK is not displayed, initiate a manual check-in. From the front of the sensor, press and release the check-in
button . It emits a series of audio beeps indicating its connection sequence. During an active check-in
connection, additional pressing of the check-in button is ignored.
• 1 beep: device booted
• 2 beeps: device connected to network
• 3 beeps: device connected to OneVue
Step 6: Verify OneVue settings
Verify the following settings are configured to meet the requirements of the condition being monitored.
1. Monitored Asset settings (Go to Monitoring > Monitored Assets)
Each Primex sensor device is assigned to a Monitored Asset and its readings or monitored conditions generate the
Monitored Asset's current and historical readings. In addition, sensor operating condition data is linked to its
assigned Monitored Asset. When a sensor enters a Warning or Alarm state, its assigned Monitored Asset is also
set to an Alarm or Warning state.
• Sensor assigned to a Monitored Asset. Go to Devices > Sensors > select sensor > verify assigned Monitored
Asset.
• Monitored Asset assigned to sensor is added to an Alert Rule.
• Monitored Asset assigned to sensor is added to a Report Profile.
• Users responsible for the monitored condition are assigned to Monitored Asset's Business Unit.