29733 R2  06/01/2003

 

10

The power requirements for the HO-B Series models are: 
120 VAC, 1 

Æ

, 60 Hz., 12A. 5-ton models: 120 VAC, 1 

Æ

60 Hz., 16A. 
 
Accessories requiring 120 VAC power sources such as 
electronic air cleaners and humidifier transformers may 
be powered from the ST9103 EFT. Do not use the direct 
drive motor connections as a power source, since there 
is a high risk of damaging the accessories by exposure to 
high voltage from the auto-generating windings of the 
direct drive motor. 
 
Thermostat wiring connections and air conditioning 
contactor low voltage connections are shown in the wiring 
diagrams. Some micro-electronic thermostats require 
additional controls and wiring. Refer to the thermostat 
manufacturer's instructions. 
 
The thermostat should be located approximately 5 feet 
above the floor, on an inside wall where there is good 
natural air circulation, and where the thermostat will be 
exposed to average room temperatures. Avoid locations 
where the thermostat will be exposed to cold drafts, heat 
from nearby lamps and appliances, exposure to sunlight, 
heat from inside wall stacks, etc. 
 
Normal heat anticipator setting: 0.1 A. For more precise 
adjustment, the heat anticipator may be adjusted to the 
amperage draw of the heating control circuit as 
measured between the "R" and "W" terminals of the 
thermostat. To reduce the risk of damaging the heat 
anticipator, do not measure circuit without first removing 
one of the two wires first. To determine the heating circuit 
amperage draw: 
1.  Disconnect one of the “R” or “W” wires from the 

thermostat terminal. 

2.  Connect an ammeter between the wire and the 

thermostat terminal to which it was attached. 

3. Note the amperage reading when the heating 

contacts are closed. (System switch must be on 

HEAT

” if so equipped. 

4.  Re-connect the thermostat wire. If the thermostat is 

serving a combination heating and air conditioning 
system, pay particular attention to polarity. 

5. When the thermostat is reconnected and re-

plumbed, adjust the heat anticipator setting to match 
the observed amperage reading. 

10.  HUMIDIFIER 

A humidifier is an optional accessory available through 
most heating supplies outlets. Installation should be 
carried out in accordance with the humidifier 
manufacturer's installation instructions. Water or water 
droplets from the humidifier should not be allowed to 
come into contact with the furnace heat exchanger. 
Terminals (115 v) are provided on the ST9103 EFT 

control. Do not use direct drive motor connections as a 
source of power for 120 VAC humidifiers and humidifier 
transformers. 
 

11.  OIL TANK 

Oil storage tanks must be selected and installed in 
compliance with applicable codes; in the United States, 

NFPA 31

Standard for the Installation of Oil Burning 

Equipment

, Chapter 2. Observe all local codes and by-

laws. And in Canada, 

CAN/CSA-B139

Installation Code 

for Oil Burning Equipment

, Section 6 

 
In general, the oil tank must be properly supported and 
remain stable in both empty and full condition. The oil 
tank must be fitted with vent and supply pipes to the 
outdoors. Refer to the above-mentioned codes for sizing. 
The vent pipe must be no less than 1¼ inches I.P.S., and 
terminate with an appropriate vent cap in a location 
where it will not be blocked. The fill pipe must be no less 
than 2 inches I.P.S., and terminate with an appropriate 
cap in a location where debris will not enter the fill pipe 
during oil delivery. 
 
If located indoors, the tank should normally be in the 
lowest level, (cellar, basement, etc.). It must be equipped 
with a shut-off valve at the tank outlet used for the oil 
supply. The oil tank must be located as to not block the 
furnace / room exit pathway. Observe all clearances 
specified in the above-mentioned codes. 

12.  PIPING INSTALLATION 

In the United States the installation must be in 
accordance with the requirements of NFPA No. 31 and 
local codes and regulations. 
 
In Canada, the entire fuel system should be installed in 
accordance with the requirements of CAN/CSA B139, 
and local regulations. Use only approved fuel oil tanks 
piping, fittings and oil filters. 
 
Ensure that all fittings used in a copper oil line system are 
high quality flare fittings. Do not use compression fittings. 
 
Do not use Teflon tape on any fittings. 
 
Pressurized or gravity feed installations must not exceed 
3 PSIG. Pressures greater than 10 PSIG may cause 
damage to the shaft seal. If the height of the oil stored in 
a tank above the oil burner exceeds 11½ feet, it may be 
necessary to use a pressure-regulating device approved 
for this purpose. 

Summary of Contents for Air Furnace

Page 1: ...REGULATION OF AUTHORITIES HAVING JURISDICTION AND NFPA STANDARD 31 U S A OR CSA STANDARD B139 CAN FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors or liquids in the vicinity of t...

Page 2: ...e Beckett Oil Burner 4 tons of cooling Highboy 2 nd Generation Heat Exchanger Nominal Output BTUH 80 Compact Highboy 120 Standard Highboy Breech Location F Front Cooling Airflow 3 3 Tons 4 4 Tons 5 5...

Page 3: ...n Set Up 16 21 Operating Instructions 17 Table A 1 Beckett AF Oil Burner Set Up 18 Table A 2 Riello 40F Oil Burner Set Up 18 Table A 3 Direct Drive Blower Set Up 19 Table A 4 Direct Drive Blower Chara...

Page 4: ...ecedence over the general instructions provided with this installation manual When in doubt please consult your local authorities All models are shipped assembled and pre wired The furnace should be c...

Page 5: ...arging right by following these steps 1 Rotate the furnace 90 to the desired position 2 Remove the three nut and washer sets fastening the oil burner assembly to the furnace Beckett Burner or loosen t...

Page 6: ...t be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position The air heated by the furnace shall not pass through a refrigeration uni...

Page 7: ...surrounding objects Observation Extend chimney above all surrounding objects within 30 feet B Chimney Cap or ventilator Observation Remove C Coping restricts opening Observation Make opening as large...

Page 8: ...e chimney at a rate of one quarter inch to the foot The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace The flue pipe should connect to the chimney such tha...

Page 9: ...rotected against over heating by fixed high temperature limits These controls are factory set and are not field adjustable If an over temperature condition is detected one or both limit switches will...

Page 10: ...on should be carried out in accordance with the humidifier manufacturer s installation instructions Water or water droplets from the humidifier should not be allowed to come into contact with the furn...

Page 11: ...0 230 9 5 25 100 11 20 65 For additional information see the installation information sheet included in the documents envelope or affixed to the oil burner NOTE Both the Beckett and Riello oil burners...

Page 12: ...ctrode porcelains should be free of cracks the electrode tips should be tapered and free of burrs and the contact rods must be clean and be in firm contact with the ignition transformer contact spring...

Page 13: ...a sign of unburned fuel This indicates poor combustion This type of problem may be caused by excess draft excess air or contaminated fuel Do not ignore this indicator STACK TEMPERATURE Stack temperatu...

Page 14: ...odating both wires on a single motor tap It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut As a safety precaution...

Page 15: ...ntly high voltages to damage accessory equipment Use the terminals provided on the ST9103 EFT DO NOT START THE BURNER OR BLOWER FAN UNLESS THE BLOWER ACCESS DOOR IS SECURELY IN PLACE Additional ST9103...

Page 16: ...ly air and return air temperatures when the furnace has reached steady state conditions This is the point at which the supply air temperature stops increasing relative to the return air temperature Th...

Page 17: ...to start the furnace during these conditions and who to call for emergency service 21 OPERATING INSTRUCTIONS Before Lighting Open all supply and return air registers and grilles Open all valves in oi...

Page 18: ...United States the R W Beckett AFG Burner may be equipped with Beckett s Inlet Air Shut Off Beckett Part No AF A 5861 to increase efficiency It reduces the amount of air passing through the oil burner...

Page 19: ...on temperature rise Upper values may exceed measured airflow values in Table A 3 2 Nominal Values Only TABLE A 4 DIRECT DRIVE BLOWER CHARACTERISTICS CFM External Static Pressure inches w c Furnace Mo...

Page 20: ...TERISTICS CFM External Static Pressure inches w c Furnace Model Motor hp Blower Temp Rise DT Motor FLA Motor Pulley Turns Out 0 20 0 30 0 40 0 50 0 60 0 70 0 1596 1518 1435 1330 1247 1184 1 1505 1434...

Page 21: ...ons inches Plenum Openings Cabinet Supply Air Return Air Flue Width A Depth B Height C D x E Side F x G Bottom Dia Height H Filter Perm Ship Weight lb 80F 22 31 49 20 x 20 14 x 22 14 x 22 5 42 16 x 25...

Page 22: ...29733 R2 06 01 2003 22 WIRING DIAGRAM OIL FURNACE WITH ST9103 EFT R7184 CONTROL Appendix B WIRING...

Page 23: ...29733 R2 06 01 2003 23 WIRING DIAGRAM OIL FURNACE WITH ST9103 EFT RIELLO OIL BURNER Appendix B WIRING...

Page 24: ...well as 115 volts to a line voltage humidifier or humidifier step down transformer Both sets of terminals are inch quick connect type rated at 1 A each The EAC terminals provide power to an electronic...

Page 25: ...rk for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored If fl...

Page 26: ...TAT SATISFIED R7184 SHUTS OFF Burner Motor Solenoid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENC...

Page 27: ...good contact between control box spades and sub base terminals Defective control box Replace Verify electrical connections Check for seized pump motor or fan against housing Defective motor capacitor...

Page 28: ...alve closed dirty filter damaged supply lines Defective or dirty oil valve stem nozzle or pump strainer Broken pump drive key defective pump no oil pressure Ignition electrodes shorted cracked porcela...

Page 29: ...seconds b Burner motor is de energized even though thermostat is still calling for heat c If circulator fan has started it continues through the selected heat fan off delay period Established flame f...

Page 30: ...call for heat a Circulator fan turns off when heat fan off delay time is complete b Normal operation resumes ST9103 control is in standby mode awaiting next thermostat command FAN Continuous circulati...

Page 31: ...flame or viewing ambient light The resistance of the cad cell may be checked while the R7184 is in the run state by pressing the reset button The LED diagnostic light will flash the following code TA...

Page 32: ...n there is a call for heat Procedure Status Corrective Action 1 Check that limit switches are closed and contacts are clean This includes the burner motor reset button N A N A 2 Check for line voltage...

Page 33: ...ndicator light flashing at 1 Hz rate second on second off Procedure Status Corrective Action 1 Check that the limit switches are closed and contacts are clean 2 Check for line voltage power at the oil...

Page 34: ...by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of this table If not in restricted mode...

Page 35: ...n socket Reconnect line voltage power and close line switch Start burner Burner keeps running System is OK Indicator light is on Remount control onto burner housing Go to step 6 10 Check cad cell Disc...

Page 36: ...ND GENERAL TROUBLESHOOTING Problem Possible Cause Remedy Thermostat not calling for heat Check thermostat and adjust Also check thermostat for accuracy if it is a mercury switch type it might be off l...

Page 37: ...l is getting dirty If cad cell is poorly aimed realign it NOTE The photocell should have a resistance of 100K W in absence of light a maximum of 1500 W in the presence of light Ensure that room light...

Page 38: ...ose as possible to this fan off temperature Fuel oil leak Check fuel oil line for leaks Repair or replace if necessary Stack temperature too high Check stack temperature Stack temperatures will normal...

Page 39: ...an motor amperage draw Check motor ventilation ports clean if necessary Replace motor if necessary Furnace will not warm home to desired temperature Burner motor stopping intermittently on overload Ch...

Page 40: ...or Contact Address Postal Code Telephone No After Hours No Service Contractor if different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Oil Supplier Contact Tele...