5 - 7.5 HP Direct Drive Owner’s Manual

I.  System Start-Up Information

1. Read the installation and maintenance instructions as well as the recommended

    safety practices in this manual.
2. Install Ductwork completely:

A.) Seal ductwork with silicone sealant or duct tape.

B.) Have Dust Bin in place and sealed.

3. Have licensed electrician wire Fan / Blower according to wire diagram in this

    owner’s manual.
4. Have licensed electrician check current draw on motor with all gates open. Current

draw should not exceed maximum motor amperage. (OAS is not responsible for

destroyed motors due to improper wiring or incorrect installation.)

Caution

The Dust Collector & Fan/Blower is heavy. Handling and

installation should always be performed by experienced and

trained personnel who have experience with rotary equipment.

In addition to the following instructional manual, care should

be taken to ensure compliance with specific safety

requirements mandated by federal, state and local codes.

Warning

Do not operate Fan / Blower without connecting dustbin.

Keep clear of exhaust. Keep hands and objects clear of inlet

and outlet.

Warning

Check amperage draw during operation with all blast gates

open. Make certain amperage is not outside operating limit

indicated on motor plate! If amperage is too high - shut down

immediately! (See Troubleshooting section.)

Summary of Contents for XXK050100

Page 1: ...5 7 5 HP Direct Drive Cyclonic Dust Collectors Oneida Air Systems Inc 1001 West Fayette St Syracuse N Y 13204 Phone 1 800 732 4065 315 476 5151 Fax 315 476 5044 www oneida air com Owner s Manual 10_08...

Page 2: ...l before installing or operating system I II III IV V VI VII VIII IX X XI XII XIII XIV XV XVI 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20 System Start Up Information Direct Drive Configurations Gene...

Page 3: ...troyed motors due to improper wiring or incorrect installation Caution The Dust Collector Fan Blower is heavy Handling and installation should always be performed by experienced and trained personnel...

Page 4: ...water gauge whichever comes first Never allow gauge to reach 5 XXK050100 1 phase XXK070300 3 phase 9a 0 1 2 3 4 5 INCHES W C 8a 8b 8c 8e 8d 7 5 hp Direct Drive System XXK070300 3 phase 1 Motor Blower...

Page 5: ...tion Class F4 Voltage 208 230 460 Amperage 19 6 18 4 9 2 Made in U S A Integral Fan Blower 7 5hp 2 Pleated Cartridges 260 sq ft Spun Bonded polyester BIA ZH1 487 test Rated C Captures 99 99 of test ma...

Page 6: ...IV Dimensions O A S 2008 c 5 7 5 HP Direct Drive Owner s Manual 5 10 031 I D 7 64 I D 1 25 Flange 52 25 82 or 106 for Twin Drum 60 134 25 or 158 25 33 Approx 100 33 56 105 or 129 122 or 146...

Page 7: ...nt B Back Requires Fork Truck for installation 1 Bolt stand together laying down Orient square cross brace 7 Cross brace 6 must be oriented to face plenum Note There will be NO lower brace on front so...

Page 8: ...sher on bolt then attach hex nut Tip the fan housing and cone upright The system is very top heavy Cyclone Inlet and Fan Blower are independent Filters can be to the right or left of the unit 7 Bolt F...

Page 9: ...nnector is air tight or motor damage could result Stay clear of fan exhaust while collector is operating Collector Hose Clamp Hose Clamp Flex Hose Dust Bin 6 7 Attach the ductwork from the woodworking...

Page 10: ...shown on the nameplate for all other motors Do not use protection with larger capacities than recommended Three phase motors must have all three phases protected 2 Cleanliness Keep both the interior...

Page 11: ...nclip and carefully empty dust bin All steps should be done with a dust mask and eye protection and System off 1 Compressed air from outside Blast air along pleats of the filter at about a 20 angle Bl...

Page 12: ...ound Connect house ground wire to green chassis screw in motor wire housing box Motor Wire Box Green Chassis Screw Top View Outlet Inlet 1 Blue 8 Red J Brown 5 Black Power Line 1 Tie together and insu...

Page 13: ...g across the Line Starters Nema Type 1 Enclosure with Start Stop in cover and class 10 overload Industrial switches can also be purchased through your local electrician Due to varying electrical codes...

Page 14: ...pe too small a hood port or too small a branch line See branch line diameter chart in ductwork guide Be sure that your filters are clean See filter cleaning directions Filters filling with large chips...

Page 15: ...low 420 microns in size 017 of an inch in certain concentration ranges when ignited can deflagrate burn quickly An ignition source such as a spark or ember can ignite a dust mixture resulting in an ex...

Page 16: ...idental contingent special or consequential damages arising from the use of our product Oneida Air Systems does not warrant or authorize use of wood dust collectors for other purposes This includes wo...

Page 17: ...e to the port labeled on the back of the pressure gauge 5 Make sure the tubing is not crushed or kinked along its entire length cut shorter if necessary 4 When the gauge rises to 3 it s time to clean...

Page 18: ...3600 RPM motors are to be relubricated every 5500 hours Table 1 Service Conditions Table 2 Lubrication Interval Multiplier Per Baldor specifications add 30 ounces 8 4 grams of Mobil Polyrex grease by...

Page 19: ...per must be installed by a licensed electrician The jumper is not required if you are using 3 phase power Remove the blank plate and install the start stop pushbutton into the starter cover You must m...

Page 20: ...ntrol circuit Most OAS Starters are shipped with 240v coils Plug the Start Stop Push Button Assembly into keyed receptacle As shown below Run power to the starter and from the starter to your motor Se...

Page 21: ...t Install this Jumper for Single O Using the Same Gauge Wire Sized Connected to L1 L2 Omit this Wire for Single O Move this Wire to L2 for Single O Note Select Size of Fuse or Circuit Breaker Per Arti...