3-2
•
Cranking Limiter:
Thermally activated device lim-
its cranking time to 45 - 90 seconds, depending on
ambient temperature. At the end of the cranking pe-
riod, a red pushbutton pops out, which cannot be re-
set until one minute has elapsed.
Other Optional Control Features
•
Low Oil Pressure Shutdown:
The engine is
equipped with a low oil pressure cutoff switch
(LOPCO) to shut down the engine if oil pressure
drops below 14 psi (97 kPa)
±
2 psi.
•
High Air Temperature Shutdown:
The engine is
equipped with a high air temperature cutoff switch
(HATCO) to shut down the engine if engine tem-
perature rises above 375
°
F
±
15
°
F (190.5
°
C).
•
AC Control With Meters:
The AC control panel has
a voltmeter, ammeter, frequency meter, phase se-
lector switch, output voltage adjusting rheostat and
resettable exciter field circuit breaker.
•
AC Control - Housed Sets:
The AC control panel
has a voltmeter, an ammeter for each line, a circuit
breaker for each line, a frequency meter and a run-
ning time meter.
FIGURE 3-2. DJB GENERATOR SET
G1246
CONTROL
PANEL
TRANSFER
PUMP
OIL
FILL
PRIMARY
FUEL FILTER
SECONDARY
FUEL FILTER
O8L
FILTER
OIL
DRAIN
INJECTION
PUMP
VACU-FLO
AIR SCROLL
LIFTING
BRACKET